| 1 | Disconnecting / taking down electrically indoor/outdoor stepup/stepdown transformer of capacity upto 200 KVA from HT/LT terminals and lowering down/getting out from 2/4 pole structure/plinth or inside sub station and deposited to MES store yard complete all as specified and directed .Note:- (a) The rates quoted is deemed to be included for hydra, men power and other items required for disconnecting / transport of transformer. |
| 2 | Supply and installation, commissioning and testing Transformer of capacity 200 KVA, 11/0.433 KV, 3 phase, 50 HZ, ONAN cooled oil immersed copper wound, outdoor type, step down Transformer complete with first filling of IS335 ISI marked, filtered and dehydrated transformer oil and other standard fittings/ accessories and 7 position with OFF LOAD tap changer tapping range up to +5% to 10% in step of 2.5% BEE compliance level III. The transformer shall be DYN-11 vector group and confirming to latest IS 1180 all as specified and directed. The transformer shall have following accessories:- (a) Oil conservator with filling hole and drain cock.. (b ) Oil level Gauge. (c) Oil seal type transparent breather with silica gel. (d) Two numbers earthing terminals with lugs. (e) Oil drain valve /filter valve. (f) Radiators with valves.(g) Lifting lugs with fastening holes. (h) Thermometer dial type 0-120 degree C. (k) Rating & specification plate.. (l) 04 Nos cast steel bi-directional detachable rollers. (m) Explosion vent with diaphragm & sight glass. (n) Transformer must have its neutral brought out for earthing on LV side. (o) Transformer must be earthed by two independent earthing with GI strip for body and other two independent earths for neutral. Neutral earthing of transformer should be done by using GI earth plate and GI earth strip.(o)Transformer shall be installed as described in IS 10028( Part-II) and in confirming with IE rule. (q) Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side and LT side. |
| 3 | Supply and installation, commissioning and testing of Transformer, capacity 100 KVA, 11/0.433 KV, 3 phase, 50 HZ, ONAN cooled oil immersed copper wound, outdoor type, step down Transformer complete with first filling of IS335 ISI marked, filtered and dehydrated transformer oil and other standered fittings/ accessories and 7 position with OFF LOAD tap changer tapping range up to +5% to 10% in step of 2.5% BEE compliance level III. The transformer shall be DYN-11 vector group and confirming to latest IS 1180 all as specified and directed. The transformer shall have following accessories:- (a) Oil conservator with filling hole and drain cock.. (b ) Oil level Gauge. (c) Oil seal type transparent breather with silica gel. (d) Two numberes earthing terminals with lugs. (e) Oil drain valve /filter valve. (f) Radiators with valves.(g) Lifting lugs with fastening holes. (h) Thermometer dial type 0-120 degree C. (k) Rating & specification plate.. (l) 04 Nos cast steel bi-directional detachable rollers. (m) Explosion vent with diaphragm & sight glass. (n) Transformer must have its neutral brought out for earthing on LV side. (o) Transformer must be earthed by two independent earthing with GI strip for body and other two independent earths for neutral. Neutral earthing of transformer should be done by using GI earth plate and GI earth strip.(o)Transformer shall be installed as described in IS 10028( Part-II) and in confirming with IE rule. (q) Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side and LT side. |
| 4 | Supply and laying in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 sq. mm, 3 core complete all as specified and directed. |
| 5 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil) for laying of cables or GI pipe and getting out including levelling of bottom surface to required level complete all as specified and directed |
| 6 | Returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed. |
| 7 | Removing excavated material (ie soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete |
| 8 | Supply and laying Sand coarse dry as in cushioning of under ground electric cable in trenches, laid to a uniform thickness of 23 cm (15 cm under the cable & 8 cm over the cable) and gently punned down to 18 cm thickness all complete as specified and as directed. |
| 9 | Supply and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm for cable protection of 11 KV cables complete as specified and directed. |
| 10 | Supply, laying, testing and commissioning in replacement Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed. |
| 11 | M&L in repair for earthing with copper plate electrode of size 600mm x 600 mm x 3.15mm buried directly in ground (earth pit not less than 2.25 Mtr below normal ground level) connected to copper earth strip of size 20mm x 3mm by means of bolts, nuts, check nuts and washers of copper including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe medium grade 20mm dia charcoal or coke and common salt in alternative layer n.exc 150mm thick compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type C-1 using 20mm graded stone aggregate and RCC cover of size 540 x 540 x 50 mm in RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 100mm centre to centre both ways and suitable handle made of 10mm dia round bar including aluminium strip of size 25mm x 3mm for extension of earth lead and necessary excavation, earth work in soil/ loose soil and disposal to a distance not exceeding 15 Mtr and necessary connection and testing complete all as shown on electrical plate No 3 and all as specified and as directed. |
| 12 | Supply installing testing and commissioning,in replacement, factory made and tested, CPRI approved LT main feeder pillar Outdoor type, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-65 class protection and made of 3.15 mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opening and locking arrangement with necessary bus bar arrangement with insulated Aluminium bus bar 600 Amps rating for phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves, and providing extended bus bars with chamber arrangement for outgoing cables, copper control wiring of required size for instruments and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform of suitable size:- |
| 13 | Incoming:- |
| 14 | MCCB 400 Amp 36 KA 4 Pole, 50 HZ Thermal - Magnetic Release-01 No |
| 15 | Outgoing:- |
| 16 | MCCB 200 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 17 | MCCB 160 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 18 | MCCB 100 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 19 | MCCB 63 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 20 | Digital Ammeter 0-100 Amp with built in selector switch - 01 No |
| 21 | Digital Voltmeter 0-500 Volt with built in selector switch - 01 No |
| 22 | CT - 250/5 - 1 Set of three |
| 23 | Indicating lamp (RYB)-03 nos |
| 24 | Supply installing testing and commissioning,in replacement, factory made and tested, CPRI approved LT main feeder pillar Outdoor type, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-65 class protection and made of 3.15 mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opening and locking arrangement with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves, and providing extended bus bars with chamber arrangement for outgoing cables, copper control wiring of required size for instruments and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform of suitable size:- |
| 25 | Incoming:- |
| 26 | MCCB 200 Amp 36 KA 4 Pole, 50 HZ Thermal - Magnetic Release-01 No |
| 27 | Outgoing:- |
| 28 | MCCB 160 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 29 | MCCB 100 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 30 | MCCB 63 Amp 25 KA 4 Pole Thermal - Magnetic Release-01 Nos |
| 31 | Digital Ammeter 0-100 Amp with built in selector switch - 01 No |
| 32 | Digital Voltmeter 0-500 Volt with built in selector switch - 01 No |
| 33 | CT - 250/5 - 1 Set of three |
| 34 | Indicating lamp (RYB)-03 nos |
| 35 | M&L in repair for earthing with galvanized steel earth plate electrode of size 600mm x 600 mm x 6.0mm buried directly in ground (earth pit not less than 2.25 Mtr below normal ground level) connected to galvanized earth lead strip of size 25mm x 4mm by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe medium grade 20mm dia charcoal or coke and common salt in alternative layer n.exc 150mm thick compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type C-1 using 20mm graded stone aggregate and RCC cover of size 540 x 540 x 50 mm in RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 100mm centre to centre both ways and suitable handle made of 10mm dia round bar including aluminium strip of size 25mm x 3mm for extension of earth lead and necessary excavation, earth work in soil/ loose soil and disposal to a distance not exceeding 15 Mtr and necessary connection and testing complete all as shown on electrical plate No 3 and all as specified and directed. Please Enable Macros to View BoQ information |