| 1 | SUB HEAD-A (PIPING & VALVES)Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shadecomplete as required :(i) 25 mm dia (DSR ref.27.7.1) DSR 2025 (Electrical) |
| 2 | (ii) 32 mm dia (DSR ref. 27.7.2) DSR 2025 (Electrical) |
| 3 | (iii) 40 mm dia (DSR ref. 27.7.3) DSR 2025 (Electrical) |
| 4 | (iv) 50 mm dia (DSR ref. 27.7.4) DSR 2025 (Electrical) |
| 5 | (v) 65 mm dia (DSR ref. 27.7.5) DSR 2025 (Electrical) |
| 6 | (vi) 80 mm dia (DSR ref. 27.7.6) DSR 2025 (Electrical) |
| 7 | (vii) 100 mm dia (DSR ref. 27.7.7) DSR 2025 (Electrical) |
| 8 | (viii) 150 mm dia (DSR ref. 27.7.8) DSR 2025 (Electrical) |
| 9 | Supplying, fixing, testing and commissioning of Sulice valve of PN 1.6 rating with bronze /gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS -780 of following sizes as required :(i) 100 mm dia (DSR ref. 27.12.5) DSR 2025 (Electrical) |
| 10 | (ii) 150 mm dia (DSR ref. 27.12.6) DSR 2025 (Electrical) |
| 11 | Supplying, fixing, testing and commissioning of Butterfly valve of PN1.6 rating with bronze /gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS-13095 of following sizes as required :(i) 150 mm dia (DSR ref. 27.11.6) DSR 2025 (Electrical) |
| 12 | (ii) 100 mm dia (DSR ref. 27.11.5) DSR 2025 (Electrical) |
| 13 | Providing, installation, testing and commissioning of non-return valveof following sizes confirming to IS: complete with rubber gasket, GI bolts, nuts, washers etc.as required :(i) 100mm dia (DSR ref. 27.14.5) DSR 2025 (Electrical) |
| 14 | (ii) 150mm dia (DSR ref. 27.14.7) DSR 2025 (Electrical) |
| 15 | Providing and fixing of industrial type pressure gauge with gun matal / brass valve complete as required (DSR/22 16.8) DSR 2025 (Electrical) |
| 16 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. (DSR/25. 27.22) DSR 2025 (Electrical) |
| 17 | SUB- HEAD B(FIRE HYDRANT ACCESSORIES)Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed stainless steel (DSR ref. 27-09-2) DSR 2025 (Electrical) |
| 18 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mmdia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless steel (DSR-27-16.2) DSR 2025 (Electrical) |
| 19 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipments on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 mtr (DSR-27-17-1) DSR 2025 (Electrical) |
| 20 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd.for suitable dia MS pipe connection conforming to IS 904 as required :(DSR2025-27-19-2) (a) 4-Way DSR 2025 (Electrical) |
| 21 | Supplying testing of under noted size of Aluminium conductor XLPE insulated PVC sheathed & sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cable conforming to relevant IS code and as per specification in ground (including trenches) through pipe or on wall / racks cable trays including dressing and clamping the cable with MS zinc passivated clamps etc. as required. Complete in all respect to the entire satisfaction of the Engineer-in-Charge. (Make-polycab)(i) 4x10 sq. mm( DSR/22 9.1.32) DSR 2025 (Electrical) |
| 22 | (ii) 4x16 sq. mm ( DSR/22 9.1.33) DSR 2025 (Electrical) |
| 23 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts& nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness (DSR /22 3750) DSR 2025 (Electrical) |
| 24 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLSouter sheath complete asrequired. (DSR ref. 28.5.2) DSR 2025 (Electrical) |
| 25 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: DSR/25 27.18.1 DSR 2025 (Electrical) |
| 26 | Providing and Fixing of Manual call boxes of MS Type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc ( Make-AGNI) DSR-28.1.3 DSR 2025 (Electrical) |
| 27 | Providing and Fixing of Fire alarm sounders (electronic) with facility to make announcement, mounted in M.S. Box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching ttransformer etc( Make-AGNI) DSR-28.1.6 DSR 2025 (Electrical) |
| 28 | Providing and Fixing of Main panel 10 zone suitable for following zones complete with visual indications for short curciut fault,open curciut fault,fire condition and all other standard facilities as per IS-2189 with complete all interconnection and connection as required.etc( Make-Panel-AGNI/Amplifire-Ahuja) DSR-28.1.9.3 DSR 2025 (Electrical) |
| 29 | SITC of smoke detector with built in LEd and mounting base complete with all connection etc as required.(AGNI/Apollo) DSR-28.1.2 DSR 2025 (Electrical) |
| 30 | Painting on G.S. sheet with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : New work (two or more coats) including a coat of approved steel primer but excluding a coat of mordant solution DSR Civil/25 13.53.1 DSR 2025 (Electrical) |
| 31 | S/D following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.(i) 2x1.5 sqmm (DSR/25 1.17.2) DSR 2025 (Electrical) |
| 32 | (ii) 3x1.5 sqmm (DSR/25 1.17.3) DSR 2025 (Electrical) |
| 33 | (iii) 4x1.5 sqmm (DSR/25 1.17.4) DSR 2025 (Electrical) |
| 34 | (iv) 5x1.5 sqmm (DSR/25 1.17.5) DSR 2025 (Electrical) |
| 35 | (v) 6x1.5 sqmm (DSR/25 1.17.6) DSR 2025 (Electrical) |
| 36 | Supplying and fixing of following sizes of medium class 20 mm dia PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (DSR/25 1.21.1) DSR 2025 (Electrical) |
| 37 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. SOR/2018 1132 |
| 38 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. SOR/2018 1132A (Electrical) |
| 39 | Providing, fixing, testing and commissioning of 15 mm dia. sprinkler head with standard response Quartzoid Bulb of rating 68 degree C complete with all accessories as required and as per enclosed specification (UL Listed) Upright type in chrome finish (Standard Coverage) (DSRNo-27.21.1) DSR 2025 (Electrical) |
| 40 | S/F air vassel made of 250 mm dia 8mm thick MS sheet,1200mm in height with air release valve on top and flanged connection to riser drain arrangment with 25mm dia gun metel wheel valve with required accessories,pressure gauge and painting with synthetic enamel paint of approved shade as required.(DSR.NO-27.20 DSR 2025 (Electrical) |
| 41 | Providing and Fixing flow switch in sizes MS pipe including connection etc as required.(a) 150 mm dia (DSR ref. 27.23.2) DSR 2025 (Electrical) Please Enable Macros to View BoQ information |