| 1 | Taking out old unserviceable XLPE cables and supply, laying, jointing and testing of XLPE insulated, armoured, heavy duty LT under ground cable 1100 Volts grade with aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed . |
| 2 | Description all as per ser item No 1.00 above but 16 Sqmm 2 Core. |
| 3 | Description all as per ser item No 1.00 above but 16 Sqmm 4 Core. |
| 4 | Description all as per ser item No 1.00 above but 25 Sqmm 3.5 Core. |
| 5 | Description all as per ser item No 1.00 above but 35 Sqmm 3.5 Core. |
| 6 | Excavation in trenches not exc 1.5 M wide and not exc 1.5 M in depth and getting out in soft/loose soil or hard/dense soil for taking up or laying of cable all as specified and directed. Note : Due to site conditions not permissable JCB or any Plants for excavation. |
| 7 | Excavation in trenches exceeding 1.5 M wide and exceeding 1.5 M in depth and getting out in soft/loose soil or hard/dense soil for taking up or laying of cable all as specified and directed. |
| 8 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cms complete all as specified and directed. |
| 9 | Removal of surplus soil not exceed to a distance of 50 M where directed at a level not exc . 1.5M above the starting point |
| 10 | Supply and laying dry river sand laid in trenches as cable cushioning and covering complete all as specified and directed. Note : Punned thickness only measured and paid |
| 11 | M & L for brick well burnt locally available sub class 'B' laid over sand cushioning to cable in trenches keeping width of brick parallel to the length of cable complete all as specified and directed. |
| 12 | S & F in replacement of Street light bracket made out of GI tubing 32 / 40 mm dia, light grade of approx length 1.2 mtr long bend to shape suitable for security light fittings with necessary MS clamps - 02 Nos with one coat of anti corrosive primer and two coats of aluminium paint including nut, bolt, washers etc all as specified. |
| 13 | S & F in replacement Thermoplastic Cable Junction Box/Distribution Board IP 65 with metric knockouts for cable entry of size 10 to 25 sq mm x any core including fastening clamp with LT pole, box size : 333 x 233 x 120 mm hinged cover with locking arrangements including with terminals TPN strip, with 01 No MCB SP 6A x complete all as specified. |
| 14 | S & F in replacement Energy efficient LED street Light Luminaire 70 watts capacity comprises a die-cast aluminium housing including connections with 2 run of 2.5 Sq mm aluminium unsheathed wire multistranded from LT over head line / junction box to the connector of fitting, complete all as specified. |
| 15 | S & F in replacement Energy efficient LED street Light Luminaire 60 watts capacity comprises a die-cast aluminium housing including connections with 2 run of 2.5 Sq mm aluminium unsheathed wire multistranded from LT over head line / junction box to the connector of fitting, complete all as specified. |
| 16 | Supply and fix in replacement cross arms channel, bracing, support, clamps etc fabricated structured steel, sections, including nuts, bolts, washers etc and cutting to required length beat to any shape drilling holes, fixed on poles or jointed by means of elect welding complete incl painting with 2 coats of aluminum paint over a coat of red oxide primer after preparation of surfaces incl taking down / dismantling the old items complete all as directed. |
| 17 | M&L for Galvanised steel tube, light grade with all fittings for cable protection fixed with poles of 50 mm bore including complete all as specified and directed. |
| 18 | Disconnectig the bindings of loose overhead conductors of LT lines from insulators and restringing the same for proper sag and rewinding incl aluminium winding wires,tapes etc and jumpering for any type of conductor complete all as directed. |
| 19 | Supply and fixing in replacement insulator pin type porcelain vitereous, white brown or green insulator including one galvanised mild steel spindle , two galvinised washer and one GI nut 100 mm hight and 65 mm dia for 1100 Volt grade complete all as directed. |
| 20 | Supply and fixing in replacement insulator shackle type porcelain vitereous , white brown or green insulator including one galvanised mild steel strap, washer ,insulator bolts , washer and nuts for working pressure 1100Volts hight 100mm , dia 115mm , section of strap ( 31 X 5 )mm dia of bolt 14mm complete all as directed by Engr in charge. |
| 21 | Supply and errection of steel tublar swaged poles complete with cast iron base plate,finial taper plug,bolts,nuts,screws as specified type 410SP-31 (9.0 mtr long) and shifting of conductors and insulators etc incl painting the exposed portion of the pole with two coats of aluminium paint over a coat of red oxide primer and interally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer. Marking of pole number with black paint in yellow circle all as specified and directed by Engr-in-Charge. |
| 22 | M&L for PCC 1:4:8 type D2 using 40mm stone aggregate for pole foundation complete all as directed |
| 23 | M & L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate including use and waste of form work / using as coping / any description all as dirceted. |
| 24 | Supply and fix inreplacement timer switches for street /security lights astro type ( Having longitude and latitude of Indian cities in memory) 415 V three phase of 20 to 32 Amp rating with three pole power contactor, timer relay, incoming MCCB having thermal and magnetic protection TPN 40 to 63A capacity 4 pole, protection such as over load and single phase relay fitted inside sheet steel enclosure of 3 mm thick outdoor type of suitable size incl fixing arrangements in wall / floor / pole complete all as specified and as directed. |
| 25 | M&L in replacement for Earthing complete with GI earth plate 60x60cmx6mm thick electrode and 32x6mm GI strip as earthing lead burried directly in ground (Earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metre below normal ground level, conneceted to GI strip 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 and incl earth work, PCC pit and RCC cover, watering pipe 20mm dia light grade, funnel, wiremesh, charcoal dust, 40mm dia light grade protection pipe and salt etc and connected to earthing test point incl necessary earth work complete all as specified and as directed. |
| 26 | Taking down Aluminum strip of size 20 x 3mm with saddles and fixing screws etc. for roof conductors and down conductors above ground and refixing in the same location with new nuts and bolts, screws of suitable size and length and connected to air termination rod on top of the Over Head Water tank of height not more than 30 mtr from ground level complete all as directed |
| 27 | S & F in replacement Copper strip 20 x 3.15 mm having 99.9% pure copper with saddles and fixing screws etc. for roof conductors and down conductors above ground incl taking out old one all as specified for Over Head Water tank of height not more than 30 mtr from ground level. |
| 28 | S & F in replacement integral LED aviation light comprising of aluminium housing with polycarbonate enclosure with necessary fixing arrangement such as GI pipe, fixing clamp, brackets, etc., complete all as specified for Over Head Water tank of height not more than 30 mtr from ground level. |
| 29 | S & F in replacement 1 x 45 watts LED street light made up of pressure die cast housing with toughned glass and individual LEDs with secondary optics and IP66 protection for building security lights all as specified. (Make : Bajaj /Philips/CG |
| 30 | S & F Air termination, single pointed copper rod 12 mm dia and 300 mm long for OH Water tank of height not more than 30 mtr from ground level. |
| 31 | S & F in Replacement Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8 mm dia 25mm long hex. Head screw |
| 32 | Taking out old unserviceable PVC cables and supply and fixing of FR PVC round sheathed copper conductor (flexible) industrial cable,1100 Volts confirm to IS 694 fixing/ laying on poles, through pipes, fixed to walls etc cross sectional area for following sizes complete, all as specified and directed. |
| 33 | Description all as per ser item No 32.00 above but 2.5 Sqmm 2 Core. |
| 34 | Taking out old unserviceable PVC conduit of any size from poles/wall/surface etc and supply and fixing in replacement PVC conduit of min 20 mm dia as per IS with connected supporting brackets/clamps for fixing/ laying on poles, floor, wall suitable with existing fixtures etc complete all as specified and directed . |
| 35 | Supply and fixing in replacement LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 36 | Supply and fixing in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 37 | Supply and fixing in replacement LED post top made in die cast aluminium bottom housing and spun aluminium top reflectror with decorative clear acrylic diffuser 25 watt ( 3000k) 230 V AC outdoor type IP65 protection opal with connected items to fixing on existing complete all as specified and directed by Engr-in-charge. |
| 38 | S&L in Repiacement of Stranded Aluminium Conductor cable PVC sheathed 1100 Volts 6 Sqmm, flat twin core all as specified and directed. |
| 39 | S&L in Repiacement of Stranded Aluminium Conductor cable PVC sheathed 1100 Volts 10 Sqmm, flat twin core all as specified and directed. |
| 40 | Supply and fixing landscape LED spike/bush light 1 x 09 W, 220V, with die -cast aluminium housing designed for outdoor usage, IP65 protection connecting with flexible copper conductor cable of suitable size from ceiling rose complete. |
| 41 | S&F LED bulp 3 to 5 watt 220 volt suitable for all type of holders complete all as specified and directed |
| 42 | S&F LED bulp 7 to 10 watt 220 volt suitable for all type of holders complete all as specified and directed |
| 43 | Notes :- Amount of Credit Schedule for Schedule 'A' Part-ll shall be deducted from total quoted amount of BOQ to arrive at the contract sum. Please Enable Macros to View BoQ information |