| 1 | Carrying out testing of Fire fightining sys of Phase I, II & III & test certificate from concerened Testing lab of fire fighting in every quaterly in presence of Rep from MH auth & Engineer in charge/JE. Note:- Spare parts shall be mesured and paid separetly. |
| 2 | Supply only Pressure gauge 100 mm dia 0-21 Kg rating complete including replacement of Old/ UNSV old pressure gauge all as specified and directed. |
| 3 | Supply only CI butter fly valve 80 mm complete including replacement of Old/ UNSV unsv butter fly valve all as specified and directed. |
| 4 | Supply only CI butter fly valve 100 mm complete including replacement of Old/ UNSV unsv butter fly valve all as specified and directed. |
| 5 | Supply only CI butter fly valve 150 mm complete including replacement of Old/ UNSV unsv butter fly valve all as specified and directed. |
| 6 | Supply only CI butter fly valve 200 mm complete including eplacement of Old/ UNSV unsv butter fly valve all as specified and directed. |
| 7 | Supply only CI non return valve 80 mm complete including replacement of Old/ UNSV unsv non return valve all as specified and directed. |
| 8 | Supply only CI non return valve 100 mm complete including replacement of Old/ UNSV unsv non return valve all as specified and directed. |
| 9 | Supply only CI non return valve 150 mm complete including replacement of Old/ UNSV unsv non return valve all as specified and directed. |
| 10 | Supply only Smoke Detectors Addressable type Photoelectric /Optical with base with self built intelligence , complying with EN 54 part 7 and IS 11360 all as specified and directed. |
| 11 | S&F in Replacement of Old/ UNSV MS ERW pipe 25 mm dia including all fittings complete all as specified and directed. |
| 12 | S&F in Replacement of Old/ UNSV Sprinkler quick / early response type, automatic glass bulb sprinkler pendent type, operating type heat sensitive temperature rating 68 degree (red bulb) of sze 15mm dia and complying with IS 15105 complete all as specified and directed. |
| 13 | S&F in Replacement of Old/ UNSV CPU Card in Main panel Processor: Microcontroller faster than 25 MHz,Memory: Over 4 MB of buffered static RAM, 2 MB of flash memory,Management: Controls smoke detectors, MCPs (manual call points), and hooters. complete all as specified and directed by Engr in -charge |
| 14 | S&F in Replacement of Old/ UNSV Addressable manual call point break glass/resettable type colour red operating voltage 24 Volt DC conventional fire alarm system, complying with IS 2189 complete with LED indication specified and directed by Engr in -charge |
| 15 | S&F in Replacement of Old/ UNSV Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of 5 DB of 200 mtr range complying with IS 2189 at MH complete all as specified and directed by Engr in -charge |
| 16 | S&F in Replacement of Old/ UNSV remote Response Indicator LED type operating voltage 24 Volt DC in fire alarm complying with IS 2189 at MH complete all as specified and directed by Engr-in-charge |
| 17 | S & F wiring with PVC insulated steel armoured copper conductor cable of size 1.5 Sq mm x 2 core on wall / surface with MS saddles complete all as specified and directed by Engr-in-charge |
| 18 | S & F 100mm dia Cast Iron (CI) Foot Valve with inbuilt strainer , flanged type suitable for fire pump suction line, complete with gasket, bolts,nuts complete all as specified and directed by Engr-in-charge |
| 19 | S & F 150mm dia Cast Iron (CI) Foot Valve with inbuilt strainer ,flanged type suitable for fire pump suction line, complete with gasket, bolts,nuts scomplete all as specified and directed by Engr-in-charge |
| 20 | S & F 200mm dia Cast Iron (CI) Foot Valve with inbuilt strainer ,flanged type suitable for fire pump suction line, complete with gasket, bolts,nuts complete all as specified and directed by Engr-in-charge |
| 21 | Supply,fixing and testing of MS ERW pipes 100mm dia Class 'C' thickness of pipes4.85mm as per IS 1239 for under ground/laying or fixing on walls / roofs with supports for hydrant system including transportation provision of specials like bends tees reducers flanges etc semless welded in proper position,all bends tees and junctions etc as required wrapping with waterproofing membrane (min 3 mm thick) tape providing tapping for pressure gauge and other instruments making holes/chasing in walls masonary, testing, flushing & cleaning of pipe line by water & making good the same as original complete all as specified and directed by Engr-in-charge |
| 22 | Supply,fixing and testing of MS ERW pipes150mm dia Class 'C' thickness of pipes4.85mm as per IS 1239 for under ground/laying or fixing on walls / roofs with supports for hydrant system including transportation provision of specials like bends tees reducers flanges etc semless welded in proper position,all bends tees and junctions etc as required wrapping with waterproofing membrane (min 3 mm thick) tape providing tapping for pressure gauge and other instruments making holes/chasing in walls masonary, testing, flushing & cleaning of pipe line by water & making good the same as original complete all as specified and directed by Engr-in-charge |
| 23 | S&F in replacement of Hose reel drum 30M long, 19mm internal dia, red colour working pressure minimum 7kg/cm2, brust pressure 21 kg/cm2 complete all as specified and directed by Engr-in-charge. |
| 24 | S&F in replacement of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out sidecomplete all as specified and directed by Engr-in-charge |
| 25 | M&L Pipe Support for all types of pipes including hangars / fastners / elbows/ supports / tees complete all as specified and directed by Engr-in-charge |
| 26 | Supply and fixing in replacement of short branch pipe gun metal 63mm intantaneous inlet, made threaded outlet,15mm bore nozzle long complete all as specified and directed by Engr-in-charge |
| 27 | Supply and fixing in replacement of Rein forced rubber lined (RRL) fire hose complete all as specified and directed. Size - 63 mm dia and 15mtr long complete all as specified and directed by Engr-in-charge |
| 28 | Supply and fixing in replacement of 8 zone Microprocessor Based Local Fire Alarm Control Panel shall be compliant with BS EN 54 Part 2 (Control and indication ) and Part 4 (Power Supply) , made out of CRCA Sheet as per suitable gauge, duly powder coated in approved colour with louvers for ventilation, locking arrangement, having provision of each zone address/location programming via key pad , each zone power isolation & loop voltage cut-off facility, Minimum 999 event data logging storage, High resolution LCD display. Incorporated Software controlled. Having C/NC/NO potential free relay control for FIRE, OPEN & SHORT. Walk test facility and Heavy duty power supply of 230V AC and frequency of 50 Hz 6 Amp 24 volt DC separate output for battery charger all the feature accommodate in single wall mount with locking arrangement cabinet, complete all as specified and directed by Engr in -charge |
| 29 | Supply and fixing in replacement of Single headed Lending Valvemade ofstainless steel of 63 mm (2.5 inches) Nominal Diameter, complete all as specified and directed by Engr-in-charge |
| 30 | Supply and fixing in replacement of Fire Hose Delivery Coupling made of Stainless steel of Size - 63 mm dia (Nominal dia), working pressure approx 14 bar complete all as specified and directed by Engr-in-charge |
| 31 | Supply and fixing in replacement of Four way fire brigade connection of size 63mm dia, Material: Durable construction typically using Stainless Steel (SS) often painted with a red oxide primer.pressure usually up to 14kg/cm2 complete all as specified and directed by Engr-in-charge |
| 32 | Supply and fixing in replacement of Water flow indicator (paddle type) complete . Size - 4\\" or 6\\" complete all as specified and directed by Engr -in -charge. |
| 33 | Supply and fixing in replacement of forged brass valve 15/20 mm complete all as specified and directed by Engr -in -charge. |
| 34 | Supply and fixing in replacement of Brass air release valve of size 20 mm dia complete all as specified and directed by Engr -in -charge. |
| 35 | Supply and fixing in replacement of brass shut off Nozzel 20 mm dia suitable for fire hose reel system complete all as specified and directed by Engr -in -charge. |
| 36 | Material & Labour for painting of fire fighting pipeline up to 200mm dia pipe with one coat of synthetic enamel paint of approved/Red colour or shade as approved by Engineer-in-Charge including preparation of surface after removing existing paint,filling depressions & applying two coats of red oxide complete all as specified & directed by Engineer - in-Charge |
| 37 | M&L for Cleaning of fire fighting water storage sump which is underground and close to motor op room and having a depth of around 6 mtr deep and removing mud upto distance of 25 mtr from the site so that it can run on DG set also complete all as specified and directed by Engr -in -charge. |
| 38 | Excavation in trenches in any type of soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out soil including forming bottom surface to required slope gradient for laying cables pipes/poles foundation etc complete all as specified and directed by Engr -in -charge. |
| 39 | Returning filling in including spreading levelling , watering and well ramming in layers of 25cm thick complete all as specified and directed by Engr -in -charge. |
| 40 | Removal of surplus excavated soil not exceeding 50mtr distance and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr -in -charge. |
| 41 | Mechanically Laundry Plant |
| 42 | Comprehensive periodic maintenance, repair & servicing of Flat work rotary drying ironer SFW/20/E series Electrically heated 415 volts, 50 Hz, 3 Phase Make : Supershine Laundry systems Model - SFW/20 / E. Ser No 2022 01 Roll including taking down the u/s items. Note :- Replacement of parts shall be measured and paid seperately under relevenat items from item no 43 to 48.(a) Testing of all the parts of Flat work drying ironer(b) Free run of the machine & checking the temp at different time interval(c) Removing blockage from the pipe occur & make the iron surface well polished(d) Repair of the iron stand for keeping drying ironer(e) Carrying out the overhauling of the parts & greasing |
| 43 | Comprehensive periodic maintenance, repair & servicing of Flat Bed press Pneumatically operated with front push button SFB series Electrically heated 415 volts, 50 Hz, 3 Phase Make : Supershine Laundry systems Model - SFB/30 / E. Ser No 2023 and 2024. (Total unit - 02 no.) including taking down the u/s items. (a) Making the flat bed surface even & remove any obstruction & wear tear in the flat bed surface (b) Reparing the stand so that it can take load of the structure c) Carrying out the overhauling of the parts and make them greasing & oiling remove anty rust on it.(d) Testing of all the parts of Flat bed press Note :- Note :- Replacement of parts shall be measured and paid seperately under relevenat items from item no 49 to 55. |
| 44 | Supply only Teflon Type Press Head and bottom cover for Steam Iron Press Machine all as specified and directed by Engr in -charge. |
| 45 | Supply only Penumatic Hand Iron With boiler steam pressure of range 3 to 6 bar (approx. 40–85 PSI). all as specified and directed by Engr in -charge. |
| 46 | Supply only Steam pressure Switch of pressure range: 0.2 - 6.0 bar adjustable, preset to 3.2 bar all as specified and directed by Engr in -charge. |
| 47 | Supply only Main Roller Bearing Gear Side (Bearing No.22220 Plain Koyo/NTN/NSK/FAG) complete all as specified and directed by Engr-in-charge |
| 48 | supply only Main Roller Bearing Blower Slide (BearingNo.22228 Plain Koyo/NTN/NSK/FAG) complete all as specified and directed by Engr-in-charge |
| 49 | Supply only Bearing for Conveyer Roller (1207 Plain Koyo/NTN/NSK/FAG) complete all as specified and directed by Engr-in-charge |
| 50 | Supply only Pressure Gauge for Air Regulator (Dia-40mm with Back side thread acomplete all as specified and directed by Engr -in -charge. |
| 51 | Supply only Pressure Gauge(Dia-65mm with Back side thread complete all as specified and directed by Engr -in -charge. |
| 52 | Supply only Polyster Padding for laundary ironing machine denisity 700-4200g/m2, width up to 4.2 mtr or customized, colour white/Off white , Thermal conductivity- heat transfer to fabric for uniform ironing, Moisture Handling- helps moisture absorb and transnmit moisture way during steam ironing complete all as specified and directed by Engr-in-charge |
| 53 | Supply only Digital Temp. controller- Selectron (Make 230V, Digital Temperature Controller complete all as specified and directed by Engr -in -charge. |
| 54 | Supply only Thermocouple (J Type Thermocouple-3 mtr length) complete all as specified and directed by Engr -in -charge. |
| 55 | Supply only Contactor(16-32 Amp) 3 pole complete all as specified and directed by Engr -in -charge. |
| 56 | Supply only of V Belt M suitable for Washer Extractor complete all as specified and directed by Engr -in -charge. |
| 57 | S&F in Rewinding of Electric Motor up to10 KW, 3 Phase, 415 Volts, 50 Hz, complete all as specified and directed by Engr-In-Charge. |
| 58 | S&F in Rewinding of Prime mover capacity 0.75 KW/ 1.0 HP Squirrel Cage induction motor, 3 Phase, 2830 Rpm, suitable for Flat work rotary drying ironer complete all as specified and directed by Engr -in -charge. |
| 59 | S&F in replacement of 2000 ltr Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position etc complete all as specified and directed by Engr -in -charge. |
| 60 | Supply and fix EPDM straight hose pipe 25/40/75mm dia of suitable reqd length for loundry plant complete all as specified and directed by Engr -in -charge. |
| 61 | Supply and fix of gun metal Ball Valve 25 mm suitable for Washer Extractor complete all as specified and directed by Engr -in -charge. |
| 62 | Supply and fix of MCB TPN 40-100 Amp 'C' type, 415 Volts, 50 Hz suitable for Existing size and model complete all as specified and directed by Engr -in -charge. |
| 63 | S&F in Repair maint in replacement of old unserviceable MCCB with new MCCB, 4 pole, 415 Volts, up to 200 Amps with breaking capacity 36 KA, complete all as specified and directed by Engr -in -charge. |
| 64 | M& L for monthly maintenance, repairs and servicing of 05 No Electrically operated hospital stretcher cum passenger lift and 01 No dumb waiter (goods elevator) complete with panel boards and ARD including replacement of unserviceable spares and consumables items not specifically covered in Schedule Ä all as specified and directed. Make of lifts :- Escon/Thysun Krup/Arohi Elevator.Note :-(a) Contractor shall ensure smooth operation/functioning of lifts.(b) Maintenance of lifts shall be carried out strictly as per auth manufacturers of lifts.(c) Spares/parts necessiated for repair/ maintenance/servicing of lifts other than mentioned here-in-after in schedule 'A' shall be provided by the contracter at his own arrangements and cost there of shall be deemed included in unit rate quoted by the contracter.(d) Panelty of Rs. 2000/ per day shall be recovered from the contractor if repair to lift is not attended within 72 hours from the time of breakdown and lift remains unfunctional. |
| 65 | M& L for Rewinding of squirrel cage induction motor of capacity 7.5HP with super enamelled copper winding wire of existing guage/dia including necessory insulating material, varnishing etc including taking out from site to workshop and return back after repair & re-installing. Make of copper winding wire :- Devidyal/Atlas, complete all as specified and directed by Engr-in-charge.Note :- Replacement of parts shall be measured and paid seperately under relevenat items from item no 66. |
| 66 | M& L for Rewinding of squirrel cage induction motor of capacity 10 HP with super enamelled copper winding wire of existing guage/dia including necessory insulating material, varnishing etc including taking out from site to workshop and return back after repair & re-installing. Make of copper winding wire :- Devidyal/Atlas, complete all as specified and directed by Engr-in-charge. Note :- Replacement of parts shall be measured and paid seperately under relevenat items from item no 67. |
| 67 | Supply only bearing of size as per existing suitable for induction motor of capacity 7.5 HP to be fixed under item No. 67 here-in-before complete all as directed.Make:- TATA or SKF or NBC or MNR as approved by GE. |
| 68 | Supply only bearing of size as per existing suitable for induction motor of capacity 10.0 HP to be fixed under item No. 68 here-in-before complete all as directed.Make:- TATA or SKF or NBC or MNR as approved by GE. |
| 69 | Supply only bearing of size as per existing suitable for induction motor of capacity 20.0 HP to be fixed under item No. 73 here-in-after complete all as specified and directed.Make:- TATA or SKF or NBC or MNR as approved by GE. |
| 70 | M& L for Rewinding of squirrel cage induction motor of capacity 20 HP with super enamelled copper winding wire of existing guage/dia including necessory insulating material, varnishing etc including taking out from site to workshop and return back after repair & re-installing. Make of copper winding wire :- Devidyal/Atlas, complete all as specified and directed by Engr-in-charge. Note :- Replacement of parts shall be measured and paid seperately under relevenat items from item no 68. |
| 71 | S& F in replacement of steel wire rope 13 mm dia suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 72 | S& F in replacement of travelling cable of size 0.75 Sq mm 12 Core suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 73 | S& F in replacement of travelling cable of size 0.75 Sq mm 24 Core suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 74 | S& F in replacement of travelling cable of size 0.50 Sq mm 12 Core suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 75 | S& F in replacement of travelling cable of size 1.5 Sq mm 20 core suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 76 | S& F in replacement of travelling cable of size 1.00 Sq mm 24 core suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 77 | S& F in replacement of gate bearing suitable for16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 78 | S& F in replacement of elevator gate shoe complete as recommended as per manufacturer's catloge/Model suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 79 | S& F in replacement of break shoe suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 80 | S& F in replacement of steel wire rope 10 mm dia suitable for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 81 | S& F in replacement of steel wire speed governor rope of size 8.0 mm dia suitable for16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 82 | S& F in replacement of car shoe for 16/26 poassanger lift complete as per manufecturer mannual/catelogue complete all as specified and directed by Engr -in -charge. |
| 83 | Supply and fix in replacement of existing Collapsable channel gate for 16 passanger lift Heavy duty opening 900 X2100 mm Channel Size - 20×5 MMChannel :- 9 NosTop Track :- 1200 MMMS Bearing, Plastic Door Liner, Handle etc. complete recommended as per manufacturer. |
| 84 | Supply and fix in replacement of existing Collapsable channel gate for 26 passanger lift ,Heavy dutu opening 1200 X2100 mm Channel Size - 20×5 MM Channel :- 11 NosTop Track :- 1500 MMMS Bearing, Plastic Door Liner, Handle etc complete recommended as per manufacturer. |
| 85 | Supply and oiling to all machines gear box for 16/26 passanger lifts using Gear oil for syanthetic 220 grade complete all as specified and directed by Engr -in -charge. |
| 86 | M & L for carrying out routine half yearly inspection of lifts as per IS by the Govt approved lift inspector with submission of test reports.complete all as specified and directed by Engr -in -charge. |
| 87 | M&L for repair of existing Main card for passanger & goods lift, ADCO AD009/3000 SMD Rev F supply voltage 12/9 volts DC complete with fixing and testing all as specified and directed. |
| 88 | M&L for replacemnt of control panel micro-processor based down collective selection logic operation with saven segment display 12 volts ADCO AD3000 Control System is a main control card for elevators, designed for both V3F (Variable Voltage Variable Frequency) and standard operations. It is an SMD (Surface Mount Device) based controller, suitable for simplex down collective, collective selective, and automatic/double door operations up to 2 m/sec speed, Input/Output: All inputs/outputs are opto-isolated and available in 12VDC or 24VDC, Programming: Features 5 buttons and a 4-seven-segment display for parameter adjustment, Protection: Short-circuit protected 7-segment and signalization outputs, Make- ADCO |
| 89 | M&L replacement of old unserviceable Rubber lift floor mat of car cabin of minimum 3mm thickness non skid/non slip cut to cabin floor dimension with beveled edges suitable for 16/26 passanger lift as per required size complete all as specified and directed by Engr -in -charge. |
| 90 | Repair and tightening the of all control cable connections of car and machine control room and replacement of as adequate size lugs ,thimbles with MS tray and flexible PVC pipe for safety measures for passanger and goods lift, complete all as specified and directed by Engr -in -charge. |
| 91 | S&F in replacement of emergency alarm systems for lifts, The system is a crucial safety device designed to alert maintenance personnel and building management in case of passenger entrapment, power failure, or any emergency situation inside the lift car. power supply 12V-220V power options, for 16/26 passanger lift complete all as required and directed by engineer in charge. |
| 92 | M&L for replacemnt of relay card for main card ADCO for lifts control logic supply 12V DC, ,Safety circuits voltage is typically 110V AC for safety loop, control for motor direction, main contactor control, break control, and safety interlooks for passanger and goods lifts complete all as required and directed by engineer in charge |
| 93 | M&L for replacemnt of break coil for 16/26 passanger lift complete all as specified and directed by Engr -in -charge. |
| 94 | M&L for taking out the old UNSV main drive and repair the drive for 16/26 passanger lift to be make the same fuctional complete all as specified and directed by Engr -in -charge. |
| 95 | M&L for taking out the old u/s main drive(V1000 Yashkawa) of lift and replacement of 16/26 passanger lift of (Make :Arohi elevator,Thyson krup, Escon) should be make fuctional complete all as specified and directed by Engr -in -charge. |
| 96 | M&L for replacement of drive Resistance of 16/26 passanger lifts complete all as specified and directed by Engr -in -charge. |
| 97 | M&L for replacemnt of Elevetor limit switch Material: Thermoplastic/Plastic, Power/Voltage: 230VAC, Current Rating:4Amp, complete all as specified and directed by Engr -in -charge. |
| 98 | M & L for replacement of Elevator Car Operating Plate Display Type : SEVEN SEGMENT, Power Source: CONTROL PANEL, complete all as specified and directed by Engr -in -charge. |
| 99 | M & L for replacement of lift operating pannel Display Type : SEVEN SEGMENT, Power Source: CONTROL PANEL, complete all as required and directed by engineer in charge |
| 100 | S&F in replacement of Voice card suitable for lifts complete recommended as per manufacturer complete all as required and directed by engineer in charge |
| 101 | S&F in replacement of Elevator cabin fan of size 225 mm, single phase, 230 volts, 50Hz, suitable for lifts complete all as required and directed by engineer in charge |
| 102 | M&L for replacemnt of Elevetor Retiring Camwith Supply Card RCR-01, Voltage: 110VDC, Stroke:45 MM, Weight: 5 kg complete all as required and directed by engineer in charge |
| 103 | M&L for replacemnt of Thimble Wire rope hanger Material : Casted, Size : 8 MM, Diameter: 5-10 MM, Weight: 1.5 Kg suitable for passanger and goods lift complete all as required and directed by engineer in charge |
| 104 | M&L for replacemnt of Hydrolic door lock set CONTACT STRUCTURE - 1N CREATED VOLTAGE - 220V RATED CURRENT - 2A ENCLOSURE - COLD ROLLED PLATE PROTECTION GRADE - IP20 for passanger and goods lifts complete all as required and directed by engineer in charge |
| 105 | M&L for replacemnt of Overspeed Governor Tensioner 300 mm dia Material: METAL , Lifting Height: <=60 mtr, Number Of Stops: 10-15 for passanger and goods lifts complete all as required and directed by engineer in charge |
| 106 | M&L for replacemnt of Overspeed Governor Set OSG Material: Metal, Lifting Height: < = 60m, Maximum Speed: 2.5 m/s, Number Of Stops: 10-15, Rated Speed: v=0.25 ~ 2.5 m/s, Rope Diameter: 8MM, Tension Force: 500 ~ 1600N suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 107 | S&F in replacement of Counter Guide Shoe 175 Design: GS-COUNTER, Maximum Speed: 1.5 MPS for passanger and goods lifts complete all as specified and directed by Engr -in -charge. |
| 108 | S&F in replacement of Elevator Counter Shoe 450, Maximum Speed: 1.75, Material Grade: MS suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 109 | S&F in replacement of Elevator Door Shoe 150,SIZES : 200x25mm & 150x25mm suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 110 | S&F in replacement of Elevator Door Lock 1250, CONTACT STRUCTURE - 1N CRATED VOLTAGE - 220V RATED CURRENT - 2A ENCLOSURE - COLD ROLLED PLATE PROTECTION GRADE - IP20 suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 111 | S&F in replacement of Elevator Door Open Bell 450, Material: Thermoplastic/Plastic, Tune Type: VOCAL IN DIFFERENT LANGUAGES, Voltage: 24VDC suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 112 | S&F in replacement of Elevator Rope Holder 205 suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 113 | Supply and fixing Lift Header Rope 650, Material: Stainless Steel, Surface Finishing: zinc coated suitable for for passanger and goods lifts complete all as required and directed by engineer in charge |
| 114 | Supply and fixing Elevator Maintenance Inspection Box 1250 Material of Enclosure: Plastic ABS / Polycarbonate Degree of Protection for passanger and goods lifts complete all as required and directed by engineer in charge |
| 115 | Supply and fixing Elevator Cable Hangers 200 suitable for 16/26 passanger lift complete all as required and directed by engineer in charge |
| 116 | Attending emergency break down & making functional of 05 No Electrically operated hospital stretcher cum passenger lift and 01 No dumb waiter (goods elevator) complete with panel boards and ARD including replacement of unserviceable spares and consumables items not specifically covered in Schedule Ä\\" all as specified and directed.Notes:- (i) The cost of parts/ accessories/ materials if reequired to be replace, same shall be paid seperately under respective items here-in-after as Supply only as considered/ taken for item complete all as required and directed by engineer in charge |
| 117 | Supply and fixing Counter weight pully of nominal outer dia 460mm, 5 group suitable for 13mm steel wire rope, 50mm dia steel shaft alongwith bearing and safety pin for 26 passanger lift including taking down old unsv pully for using safety measures and tools all as specified and directed by Engr-in-charge. |
| 118 | Supply and fixing power indication lamps (RYB) for main panel of lift ,with complete accessories 230 volts, single phase complete all as specified and directed by Engr -in -charge. |
| 119 | Sewage Treatment Plant |
| 120 | M & L for disconnecting electrical connection & outlet pipe connection ,taking out non clogging submersible pump set complete with motor of capacity 10 HP to 12.5 HP from the sewage collection sump lowered at the depth of 6 to 10m from the ground level complete with HDPE pipe and submersible cable,transported to authorized work shop for repair/servicing , transported back to existing location and lowering the same along with HDPE pipe and electric cable including fixing of cable to pipe with PVC strip, replacement of rusted clamps,mild steel bolts, nut and washers with stainless still nut and bolt, dismantling of old rusted lifting chain and fixing new chain, complete all as directed by Engr- in - charge:Note- (i) Repairing of pump & motor will be measured & paid separately.(ii) New Chain will be measured & paid separately (iii) Cable & HDPE pipe if found unserviceable shall be measured & paid separately . |
| 121 | M&L for Repairing /Servicing of electric motor cap 12.5 HP couplled to non clog submersible pump , AC 3 phase, by dismantling the motor and coupling pulley and sent to work shop for repair. Removal of existing burnt out copper winding wire , cleaning of slots using suitable reagents and rewinding with super enamelled copper winding wire of appropriate gauge to achieve required RPM, varnsihing, drying, ovening, overhauling , greasing , painting and assembling the same after complete repair, connecting with pump and making necessary electrical connection and testing of motor after installation complete all as specified and directed by Engr-in charge. Note: Contractor shall be responsible for maintaining required RPM after repair ,non compliance of speed considered as incomplete repair. |
| 122 | M&L for repair of earthing with galvanized steel earth plate electrode 60 cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanized earth lead strip 25x4mm (earthing lead from earth electrode to test point upto 7.5m ) by means of bolts, nut, checknuts and washers of galvanized iron or steel all as shown in electrical plate No 5 of MES Schedule Pt-I 1991, GI earth lead strip of size 25mm x 4mm protected by GI pipe 40mm dia light grade and connected to earth test point including excavation & earthwork including testing on completion complete all as specified and directed. |
| 123 | M & L for disconnection of Electrical/Mechanical connection and taking out carefuly of Sewage transfer pump 7.5 HP (3 phase, 415V 50 HZ, AC Supply) from collection tank of any make and rewinding the same with super enameled copper wire of existing gauge/specification making of heat varnishing, greasing and two coat spray/ brush painting with synthetic enemel paint of recommended colour including replacement of bearings NDE and DE as per existing specification and size including refixing the motor in position making all electrical and mechanical connections and testing complete all as specified and as directed . NOT: Rate included taking out pump from the collection tank. |
| 124 | Supply and fixing power indication lamps with complete accessories 230 volts, single phase as per existing duly approved. |
| 125 | Schedule of credit amount of Rs 90370.00 to be deducted during AOC Please Enable Macros to View BoQ information |