| 1 | Wiring for Light point/Fan point/Exhaust fan/Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable, (Havells/Anchor/Eq Make) in surface/recessed Conduits laid in slabs (Including Cost of Conduit 25mm) with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified/Schneider/ Havells/ Legrand/Anchor roma plus/ABB/Eq.Make & along with 2.5 Sqmm (P+N+E) Circuit Wire of same make as mentinoned above & items shall be approved before execution of work by SDO. |
| 2 | Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Anchor/Eq Make) |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified /Legran/Anchor roma plus/Schneider/ABB/Eq Make & shall be approved before execution of work by SDO. |
| 4 | Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Havells/ABB/Eq. Make) |
| 5 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Havells/ABB/Eq Make) |
| 6 | 63 Amp. |
| 7 | 40 Amp. |
| 8 | Supplying and Fixing of MCB way 12-way , horizontal typed , sheet steel, Double Door Distribution Board, SPN 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ABB/Eq Make) |
| 9 | Supply/Installation/Testing and Commissioning of 15W + LED Conceal/Surface (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/Halonix/Eq Make. |
| 10 | Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB of Following Sizes including connection etc USHA/Havells/Crompton/Eq. Make.(Min 1-Star) |
| 11 | 2x10 Sq.mm Service line (copper wire) of Havells/Polycab/Anchor/Equivalent Make Please Enable Macros to View BoQ information |