| 1 | Wiring for Light point/Fan point/Exhaust fan/Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable, (Havells/Polycab/Anchor/Eq Make) in surface/recessed Conduits laid in slabs (Including Cost of Conduit 25mm) with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified/Schneider/ Havells/ Legrand/Anchor roma plus/ABB/Apar/ Grandlay/ Eq.Make to be approved by EIC & along with 2.5 Sqmm (P+N+E) Circuit.Wire of same make as mentinoned above & items shall be approved before execution of work by SDO. |
| 2 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required,ISO/IEC Certified of Havells/ Legrand/Anchor/Schneider /ABB /Eq Make & shall be approved before execution of work by SDO. |
| 3 | Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/Anchor /Eq Make & shall be approved before execution of work by SDO |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified /Legran/Anchor roma plus/Schneider/ABB/Eq Make & shall be approved before execution of work by SDO. |
| 5 | Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/ Recessed Conduit (Havells/Polycab/Anchor/Apar/ Grandlay/ Eq.Make to be approved by EIC) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified Havells/Legrand/ Anchor roma plus/Schneider/ABB/Eq.Make & shall be approved before execution of work. |
| 7 | Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Havells/Polycab/Anchor/Apar/ Grandlay/ Eq.Make to be approved by EIC) & shall be approved before execution of work (Including Cost of Conduit/Channel) |
| 8 | 2x10 sq.mm+ 1x10 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards. |
| 9 | Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP, 240V,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/ Siemens/ Legrand/ Havells/ABB/Eq. Make) |
| 10 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Havells/ABB/Eq Make) |
| 11 | 40Amp. |
| 12 | 63Amp. |
| 13 | 100 Amp DP for main Supply |
| 14 | Supplying and Fixing of MCB 12 way , horizontal typed , sheet steel, Double Door Distribution Board, SPN 240V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ABB/Eq Make to be approved by EIC) |
| 15 | Supply/Installation/Testing and Commissioning of 15W + LED Conceal/Surface depending on the type of ceiling (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/Halonix/Eq Make to be approved by EIC |
| 16 | Supply/Laying/Connecting and Commissioning of 25 sq.mm 2-Core XLPE/PVC insulated and un-armoured 1.1 KV grade Aluminum Cable of Havells/Polycab/Eq. Make to be approved by EIC with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution) Please Enable Macros to View BoQ information |