| 1 | M & L for carrying out repairs to PCC earth pits by plastering to make the good defective/ damaged surfaces including preparation of surfaces and applying a coat of white wash including clearing vegetation/ levelling the soil upto 0.50 mtr distance around the earth pit complete all as specified and as directed. |
| 2 | M & L for PCC (1:3:6), type C1 earth pit chamber of outer size 450X450 X300 mm and inner Size 350X350X 300 mm including necessary earth work including taking down existing damaged earth pit chamber complete all as specified and as directed. |
| 3 | M & L for RCC 1:2:4, type B1 earth pit cover of required size 450 x 450 x 100 mm with 6 Nos. 8 mm dia high strength deformed steel TMT bars on both ways (horizontal & vertical) including with handle arrangement and necessary earth work including taking down existing damaged earth pit cover complete all as specified and as directed. |
| 4 | M&L for earthing complete with Galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanized earth strip 25x3 mm size connected by means of bolts, nuts, check nuts and washer of galvanized iron or steel, provision of 32 mm dia GI pipe light grade for protection of GI earth strip and 20mm dia GI pipe light grade for watering arrangement and PCC (1:3:6), type C1 chamber. MS funnel, wire mesh, 100 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos. 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I incl dismantling of old unsv earthig complete all as specified and as directed. Note: (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation, returning & filling, PCC chamber pit, RCC cover & test point.(iii) All accessories required for galvanized steel plate electrode required, as specified and as directed.(iv) If the desired earth resistance is not achieved during testing as per IS , the complete earthing shall be replaced / repaired by the contractor at his own cost and no extra claim shall be admissible. |
| 5 | M&L for earthing complete with Galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanized earth strip 32x6 mm size connected by means of bolts, nuts, check nuts and washer of galvanized iron or steel, provision of 40 mm dia GI pipe light grade for protection of GI earth strip and 20mm dia GI pipe light grade for watering arrangement and PCC (1:3:6) , type C1 chamber. MS funnel, wire gauge. 50 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos. 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I incl dismantling of old unsv earthig complete all as specified and as directed. Note: (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation, returning & filling, PCC chamber pit, RCC cover & test point.(iii) All accessories required for galvanized steel plate electrode required, as specified and as directed.(iv) If the desired earth resistance is not achieved during testing as per IS , the complete earthing shall be replaced / repaired by the contractor at his own cost and no extra claim shall be admissible. |
| 6 | M & L for taking down of unserviceable GI earthing strip of any size complete all as directed. |
| 7 | Supply and fixing GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles/ walls or any other indicated situation for loop earthing etc. as required for 32 mm x 6 mm thick, Galvanised strip, complete all as specified and directed. |
| 8 | Supply and fixing GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles/ walls or any other indicated situation for loop earthing etc. as required for 25 mm x 3 mm thick, Galvanised strip, complete all as specified and directed. |
| 9 | M & L for taking out old GI tubing of any grade and size in trenches/floor/fixed to pole for earth protection complete all as specified and directed. |
| 10 | Supply and laying GI tubing, 40 mm dia bore, light grade with all fittings complete all as specified and directed. |
| 11 | Supply & laying GI tubing, 20 mm dia bore, Light grade with all fittings complete all as specified and directed by Engineer in Charge. |
| 12 | Dismantling/ strip opening of earth strip of any type and M&L for testing of earth pits for earth resistance value with fully functional earth meggar, submitting the earth test report to Engineer in Charge and taking necessary action as directed for improving the earth value by pouring salt/ charcoal/ earth enhancing compound/ change of earth plate/ new earth pit as required for obtaining earth value with in limits as per IS standard complete all as specified and as directed.Note : Salt, charcoal, earth enhancing compound, earth plates and excavation earth work shall be measured and paid separately under relevant item. |
| 13 | Supply and pour crystalline salt complete all as specified and as directed. |
| 14 | Supply and pour charcoal/ carbon breeze complete all as specified and as directed. (25 Kg each bag) |
| 15 | Supply & lay earth enhancement compound complete all as specified and as directed. (25 Kg each bag) |
| 16 | Supply and laying as in repair Galvinised steel earth plate, size of 60 cm x 60 cm x 6.00 mm complete all as specified and as directed. |
| 17 | M & L for excavation of earth for earth plate of size 600 mm x 600 mm and deep 2.25 Metre taking out of soil and retuning refilling after filling of earth plate and required charcoal and salt and removing surpluse soil at 50 mtr complete all as specified and as directed. Note: Earth plate, charcoal and salt shall be measured and paid seperately. |
| 18 | M & L for taking down of old post insulator and S&F post insulator for earthing strip complete all as specified and as directed. |
| 19 | S&F as in repair GI Funnel with wire mesh for watering to earth pit complete all as specified and as directed. |
| 20 | Supply & fixing BLDC ceiling fan 1200mm sweep with anti corrosive aluminium blades, suitable electronic remote as per OEM design, down rods and connected accessories, 230 V, 1200 mm sweep. 350 RPM, Min air delivery 220 CFM, 5 star rated, equipped with silent brushless direct current motor (BLDC) of wattage < 28W, motor warranty not less than 5 years including provision of cable from ceiling rose/connector to fan including taking down unserviceable ceiling fan and deposited to MES store yard complete all as specified and as directed. |
| 21 | Supply & fixing electric water heater, storage type, electro plated steel body as per OEM design with element free induction heat transfer technology through induction coil capacity 25 litre, BEE 5 star rated with reduction heating time 10-12 mins and with digital temperature display, live temperature with smart mode, automatic operation of water heater for on and off time complete with all accessories such as safety valve, thermostat, NRV, connection piece fastner bolts including stainless steel hose pipe including taking down unserviceable ceiling fan and deposited to MES store yard complete all as specified and as directed. |
| 22 | S&F as in repair metallic exhaust fan of size 300 mm with louvre, 230V, RPM 1400, metal body including taking down old unserviceable exhaust fan and deposited to MES store yard complete all as specified and as directed. |
| 23 | S&F as in repair fresh air exhaust fan of size 250 mm, 230V, RPM 1400, PVC body complete all as specified and as directed. |
| 24 | S&F as in repair metallic exhaust fan of size 450 mm with louvre, 230V, RPM 1400, metal body including taking down old unserviceable exhaust fan and deposited to MES store yard complete all as specified and as directed. |
| 25 | S&F Wall fan of size 400mm sweep with blades, 1350 RPMmounting accessories kit, blade guard set, guard ring, AC 230V, surge protection up to 4 KV complete all as specified and as directed. |
| 26 | M&L for submain wiring with two single core PVC insulated unsheathed multistranded copper conductor cable of size 4 sqmm (FRLSH) and one single core PVC insulated unsheathed multistranded copper conductor cable green colour of size 4 Sqmm (FRLSH) as earth lead in and including concealed with PVC conduit medium grade of suitable size or surface wiring with PVC casing caping of suitable size and making good the disturbed wall surfaces to match with existing specification including takind down unserviceable submain wiring complete all as specified and as directed.Note : (i) Three run of cable with one run of PVC conduit/PVC casing and caping will be measured as one length.(ii) Wiring shall be concealed/ on surface with rigid PVC conduit medium grade/PVC casing caping as per site requirement. |
| 27 | Supply & fixing Single pole and neutral enclosure with a two pin and earth plug and socket suitable for RCBO 2 pole, 20 to 40 amps rated complete all as specified and as directed.Note : RCBO will be measured and paid separately. |
| 28 | S&F RCBO 25 Amps, double pole 240V, AC type, 30 mA with sheet metal enclosure complete all as specified and as directed. Please Enable Macros to View BoQ information |