| 1 | Oxygen System |
| 2 | Oxygen Manifold and control panel |
| 3 | The manifold and control panel should comprise of two banks of 10+10 cylinders each In additional bank of 10 cylinders should be supplied and installed for emergency supply of oxygen. |
| 4 | The control panel should be meant for the supply of oxygen at 1500 litres per minute |
| 5 | The unit (control panel)should comply with international standards like NFPA/ HTM-2022/ BIS/CDSSO |
| 6 | The control panel will need to be adjusted at a pressure to ensure 4 bar pressure in the two blocks of the hospital |
| 7 | The control panel should be from reputed manufacturers like: Becon Maedas/Ohio Medical/ Penlon/ Medicop/ Drager/Atlas COPCO/Aktive EuCE or USFDA certified |
| 8 | Feed Gas:Medical grade oxygen as per Indian Pharmacopeia 99.5% at pressure 130 – 140 bar |
| 9 | Gas Delivery Temperature (–) 10oC to (+) 30oC and ambient relative humidity of exceeding 80% |
| 10 | Altitude above MSL: 2250 meters |
| 11 | Frost formation and pressure drop is common problem in winters and rainy season. Therefore heating arrangement for the control panel have to be provided and be documented and quoted. |
| 12 | Safety relief valves, pressure gauges, NRVs and Alarms etc should be provided with means to prevent tampering by Un-authorized persons. Beacon Medeas, Greggersen, Aktiv, Rajmed Wed Med, Greggersen, chicargo Pneumatic, Penlon, Trident,Atlas copco,Ohio,Deltap,GCE medical |
| 13 | Supply Installation and Testing commissioning of 4+4 Emergency Manifold and piston operated regulator. |
| 14 | Wall outlets oxygen |
| 15 | Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. Beacon Medeas, Greggersen, Aktiv, Rajmed Wed Med, Greggersen, chicargo Pneumatic, Penlon, Trident,Atlas copco,Ohio,Deltap,GCE medical |
| 16 | Probes for Wall Outlets |
| 17 | OXYGEN FLOW METER WITH HUMIDIFIER BOTTLE (CE MARKED) |
| 18 | The oxygen manifold should comply with HTM 02-01/NFPA 99/ DIN / EN / ISO-7396-1 standards. |
| 19 | Back Pressure Compensated flow meter for accurate gas flow measurement with following features: |
| 20 | A) Control within a range of 0-15 LPM. |
| 21 | B) It should meet strict precision and durability standard. |
| 22 | C) The flow meter body should be made of brass chrome plated materials. |
| 23 | D) The flow tube and shroud components should be made of clear, impact resistant polycarbonate. |
| 24 | E) Flow tube should have large and expanded 0-15 LPM range for improved readability at low flows. |
| 25 | F) Inlet filter of stainless steel wire mesh to prevent entry of foreign particles |
| 26 | G) The humidifier bottle is made of unbreakable & reusable polycarbonate /polysulfone/polypropylene material autoclavable at 121 degree centigrade.Beacon Medeas, Greggersen, Aktiv, Rajmed Wed Med, Greggersen, chicargo Pneumatic, Penlon, Trident,Atlas copco,Ohio,Deltap,GCE medical |
| 27 | Vaccum System |
| 28 | Skid mounted vacuum system |
| 29 | The mVAC Medical Vacuum Supply System shall conform to ISO 7396-1 depending on model selected.(Duplex )The Medical Vacuum Supply System shall ensure the minimum pipeline vacuum level of -450mmHg is maintained at the plant service connection point at the rated volumetric ‘free air’ flow rate with either two pumps in standby (ISO7396-1) or with one pump on standby. The bacteria filtration system shall be ‘duplexed’ such that each filter can be isolated for replacement of the filter cartridgeThe BMV pumps are single-stage, oil-sealed and air-cooled rotary vane vacuum pumps driven by an electric motor. The pumps have been specifically designed to work with clean air, inert gas or small amounts of water vapor the pump has an inlet port with exhaust port and a gas ballast valve. Vacuum pumps shall be air-cooled, oil lubricated rotary vane type suitable for both continuous and frequent start/stop operation. The typical working range for pump applications is 400 mbar(a) to 100 mbar(a), for example -600 mbar(e) to -900 mbar(e). A rotor with three vanes is positioned inside the pump cylinder and it is supported by means of two bearings. Rotors shall be driven by IE3 efficiency electric motors. Pump inlets shall include an integral non-return valve to prevent oil suck back and pressure increases in the vacuum system. Each vacuum pump shall have an integral separator filter to ensure a virtually oilfree exhaust. Frame Mounted: Medical Vacuum Supply System. Plant Output (liters/minute) 630 System Flow (m3/hr) 101, System Flow (liters/minute) 1380 , Noise level/pump (dBA)* 65 , Motor rating per Pump (kW) 2.2 , Individual Pump control unit panel supply- (Voltage/Freq./ Phase) 415 V / 50 Hz / 3 phase Individual Pump control unit panel supply cable size mm2 (Amps) 2.5 (17) Motor rated supply per pump (A) 4.9 , Full load current per pump (A) 5 ,Starting current per pump (A) 28.8 , Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlas copco,Ohio,Deltap,GCE medical |
| 30 | Control System The central control system shall provide an intelligent human machine interface incorporating on board flash memoryand real-time clock for recording operational parameters in the event log. The central control system shall operate atlow voltage and include BMS connection for common fault. Visualization of plant inputs, outputs, and status through aweb browser, using a simple. The central control unit shall incorporate a user friendly 4.3” high-definition touchscreendisplays with clear pictograms and LED indicators, providing easy access to system operational information. The controllershall be equipped with an integrated 4G module for remote monitoring of the equipment.Cascading of vacuum pumps shall be achieved by measuring the vacuum level at the plant inlet with a pressure transducer. A mechanical back-up facility shall ensure continued operation in event of a control system malfunction. The control system shall normally employ automatic rotation of the lead pump to maximize pump life and ensure even wear.AKTIV, PENLON, HISPL,Beacon Medeas, Greggersen, chicargo Pneumatic, Trident,Atlas copco,Ohio,Deltap,GCE medica |
| 31 | Vacuum Receiver(s) 1500 LTR Vacuum receiver(s) shall be supplied with relevant test certificates and have a total volume of at least 100% of the plant output in 1 minute in terms of free air aspired at normal working pressure. Each vacuum receiver shall be powder coated from inside and outside.B-TECH ENGINEER,AKTIV,WEDMED,RAJMED,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlas copco,Ohio,Deltap,GCE medical |
| 32 | Duplex Vacuum Bacterial Filters |
| 33 | Bacteria Filters The duplex bacteria filter system shall incorporate high efficiency filter elements. A differential vacuum indicator shall be installed across the filter to indicate blockage. Additional pressure sensors shall be installed at the inlet and outlet of the filter to measure the pressure drop across the filters. Each filter shall be designed and sized to carry the full plant design flow capacity with a pressure drop not exceeding 33mbar (25mmHg). Bacteria Filter elements shall have penetration levels not exceeding 0.005% when tested by the sodium flame method in accordance with BS 3928:1969 and utilizing particles in the 0.02-to-2micron size range. Drain flasks shall be connected to each filter. Drain flasks shall be manufactured from transparent Pyrex® with a polymer coating on the inner and outer surfaces to maintain a seal in the event of inadvertentbreakage of the Pyrex® flask. All drain flasks shall be suitablefor sterilization and be connected via a manual isolating valve.BEACON MEADAS, Tri Dennt, Greggersen, HISPL,Coair,, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlas copco,Ohio,DeltaP, GCE medical |
| 34 | Wall outlets Vaccum (Specs same as given for Oxygen Outlets)Beacon,Medeas, Greggeersen,Dragger. |
| 35 | Ward Vacuum Units ( CE Marked)- Beacon Medeas, Greggersen, Aktiv, Rajmed Wed Med, Greggersen, chicargo Pneumatic, Penlon, Trident,Atlas copco,Ohio,Deltap,GCE medical. |
| 36 | It should comply with HTM 02-01/NFPA 99/ DIN / EN / ISO-7396-1 standards. |
| 37 | It must consist of the following:- |
| 38 | 1. 1 no of Suction Regulator and 1no of 1000 ml polysulfone /polycarbonate/polypropylene collection jar. |
| 39 | 2. Suction Regulator: Suction regulator should be supplied with a safety jar, including and antibacterial filter and an anti-overflow safety device. Should have wide membrane continuous suction controller |
| 40 | 3. Should have vacuum levels: 0-760 mm of Hg |
| 41 | 4. Should have vacuum gauge fitted with a protective bumper device. |
| 42 | 5. Should have on/off knob allowing for the quick restoration of a readjusted vacuum level. |
| 43 | 6. Must have central adjustment knob with a color coded for 0 to 760 mm of Hg. Should have Polysulfone/polycarbonate 100cc safety jar, autoclavable at 121º C, unbreakable, fitted with an anti-overflow safety device and equipped with a plastic antibacterial filter. It should be totally transparent, to ensure perfect sucked liquid visibility. |
| 44 | H.P. antistatic rubber tube SITCofCompressedairH.P. antistatic rubber tube, The highpressure tubeshouldbemadeofantistaticrubberas per ISO standards and colour coded, etc. complete as required. |
| 45 | Thearter suction Trolly |
| 46 | System Configuration ( poly carbontate) 2 Collection Jars 2200 ml each with safety overflow protection and autoclavable at temperature of 121°C for 15 minutes (Max. 5 cycles) Catheter Jars autoclavable at a temperature of 121°C for 15 minutes (Max. 5 cycles) Hooks to suspend rolled vacuum tubes Line Vacuum Controller (Regulator) compatible to inlet 0-760 mmHg Vacuum Vacuum Trap with safety jar & Hydrophobic Bacterial Filter for protection of the vacuum regulator and the hospital vacuum network Selector switch with \\"ON-OFF\\", \\"RIGHT-LEFT\\" functionsHSIPL, Rajmed, Wed Med, Aktive,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon, Trident,Atlas copco,Ohio,DeltaP, GCE medical |
| 47 | Air System |
| 48 | Air Compressor Coair, Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon, Trident, Atlas copco, Ohio, DeltaP, GCE medical |
| 49 | Design enhancements improve overall system efficiency, coupled with an incredibly simple unit to maintain that |
| 50 | fits the most challenging space constraints, this next generation Scroll/oil lubricated screw Medical Air Compressor |
| 51 | compressor is medical grade as per ISO 7396-1 or HTM 0201 or NFPA99 compliance |
| 52 | • Designed to standards and procedures, fully NFPA 99 compliant. |
| 53 | HP 10 |
| 54 | Bar 7.5, kw 7.5, kw 7.5, Psig 109, I/S 21.0, M3/h 75.6, CFM 44.3, DB(A) 61 |
| 55 | Air Dryer |
| 56 | The compressed wet air flows through the pre filter. The Liquid water particles get filtered by the filter. The filtered air flows in to the adsorber tower filled with desiccant where it loses all the moisture to the desiccant. Purified (Moisture and oil free) air further passing through the series filter to achieve the desired quality level as per Breathing Standard. |
| 57 | The compressed wet air flows through the pre filter. The Liquid water particles get filtered by the filter. The filtered air flows in to the adsorber tower filled with desiccant where it loses all the moisture to the desiccant. Purified (Moisture and oil free) air further passing through the series filter to achieve the desired quality level as per Breathing Standard. |
| 58 | Standard Features Single breathing Air unit with CO and Dew Point Monitor (Simplex) Dual breathing Air unit with CO and Dew Point Monitor (Duplex) One Stand by unit with manual redundancy. |
| 59 | Operating ConditionsVoltage : 100 - 240 VAC, 50/60Hz, 1phPower Consumption : 40 Watt MaxMaximum working pressure : 16 bar (g)Minimum working pressure : 4 bar (g)Rated inlet Temperature : 38°CRated inlet pressure : 7 bar(g)CO Level : 10 PPM (Alarm set point)as per NFPA 99Air Quality : 2°C PDP (Alarm set point)as per NFPA 990.01 micron particle level.Cycle Time : 4 minDewpoint dependent change overThe Series has robust valving and includes highquality coalescing pre-filter, a particulate fine-filter, aActivated carbon filter, and Bacterial filter mounted as astandard feature |
| 60 | Activated Carbon FilterThis filter is used to remove oil and hydrocarbon vaporfrom the compressed air stream coming from the dryer.Odor and Taste free air at the outlet. |
| 61 | Bacterial Filter Bacterial filters (0.01 Micron) provide effective protection against various types of particles including bacteria, viruses, and moisture droplets in the dry air out from the dryer. These are help to protect the patient, and the breathing circuit, hospital pipe line from contamination, odor and taste free dry air at the outlet. |
| 62 | controller provides complete control of the system with LEDindication/description of each step in the sequence ofoperation. A high quality Carbon Monoxide (CO) Monitor and Dew point monitor ensures the continuous monitoringof CO in PPM level and Water vapor concentrations indewpoint deg oC in the Digital display to ensure the safetyof all users. |
| 63 | Compact digital carbon monoxide (CO) monitor, Dew point monitor. If the set value exceeds the standard value,it will give the alarm in the front panel. Purge savingManual Purge economiser.Dewpoint sensor for automatic purge control. ConstructionCorrosion free aluminium towers and blocks. All pipeline are in SS/Copper. DisplayLED indication for tower operation and sequence of operations. Easy IntegrationEasy installation and integration with existing equipment: All system tie-in points are on one side. SafeHeavy-duty adsorption vessels, designed and certified for an unlimited number of cyclic loads. CustomizationAn extended list of options allow you to define your specific Trident Twin-Tower PSA breathing air dryeradjusted to your individual need. |
| 64 | Breathing Air Quality : Statement of conformity for Dryer and Filter |
| 65 | NFPA99 ISO 8573 Class - 2 : Outlet air quality |
| 66 | OSHA : Grade D 97 / 23 / CE : Pressure Directive 89 / 392 / CEE : Machinery Directive |
| 67 | European Pharmacopoeia 73 / 23 / CEE : Low Voltage |
| 68 | IS/ISO 7396 CRN |
| 69 | AIR Receiver(s) 1500 LTR AIR receiver(s) shall be supplied with relevant test certificates and have a total volume of at least 100% of the plant output in 1 minute in terms of free air aspired at normal working pressure. Each Air receiver shall be powder coated from inside and outside.Aktiv Penlon,Rajmed Wedmed, Coair, Beacon Medeas, Greggersen, chicargo Pneumatic, Trident,Atlas copco,Ohio,DeltaP, GCE medical , B-tech |
| 70 | Wall outlets Air ( 4 bar) |
| 71 | Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. Make Beacon Medeas, Greggersen, Penlon,draggerCoair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon, Aktiv, Trident, Atlas copco, Ohio, DeltaP, GCE medicalBeacon Medeas, Greggersen, Penlon, Dragger Coair, Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlascopco, Ohio, DeltaP, GCE medical |
| 72 | SITCofCompressedair H.P. antistatic rubber tube, The highpressure tubeshouldbemadeofantistaticrubberas per ISO standards and colour coded, etc. complete as required.Aktiv Penlon,Rajmed Wedmed,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Trident,Atlas copco, Ohio, DeltaP, GCE medical |
| 73 | Wall outlets N2O |
| 74 | Oxygen, air and vacuum outlets HTM or NFPA compliant should be quoted along with 2 probes for each out let. Both imported and indigenous outlets and probes should be quoted separately. The outlets and probes should be as specific and non- interchangeable. The gas outlets have heavy duty constituents and smooth connection and disconnection. The outlets must be labeled and color coded. Imported units should have UL Listing and Indian units must be IS/CE certified. Make Beacon Medeas, Greggersen, Penlon,draggerCoair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlas copco,Ohio,DeltaP, GCE medicalAktiv Penlon,Rajmed Wedmed,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Trident,Atlas copco, Ohio, DeltaP, GCE medical |
| 75 | Pressure Reduction Station ( 4 bar ) |
| 76 | Precise pressure reduction control for optimal performance. Compact design and easy installation. Robust construction ensures long-term durability. Filters and strainers. Suitable for medical air and surgical air. Pressure reduction station ensure high accuracy in outlet pressure contBeacon medas, penlon,Rajmed,Wedmed, Aktive, Coair, Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon, Trident, Atlas copco, Ohio,DeltaP, GCE medical |
| 77 | Medical Grade Copper Pipeline With Tubings, Fittings, Pressure GaugesMandev Tubes, Maxflow, Satyam,Nefton, Rajco |
| 78 | The copper pipes shall be copper annealed ASTM B/75/B68 or equivalent standards. |
| 79 | The Diameter of the pipe should be suitable for 1000 LPM average flow and this pipeline will have to be divided into two in the oxygen supply plant and attached to two pipelines systems presently feeding the hospital. |
| 80 | Grossly the diameter should not be less than 38mm X 1.5mm or thicker so as to bear pressure of 10 -12 bar |
| 81 | All pipe work materials shall be manufactured by BS EN ISO 9001:2000 registered companies marking for sizes up to 108 mm, copper pipes shall be permanently and durably marked at regular intervals along its length with the following information |
| 82 | - The harmonised standard number EN 13348; |
| 83 | - Lloyds/BSI Kitemark or equivalent approved to EN 13348:2008 |
| 84 | - Nominal dimensions, diameter x wall thickness; |
| 85 | - Temper designation to EN 1173; |
| 86 | - Manufacturer's identification; |
| 87 | - Date of production: year and month (1 to 12) |
| 88 | - Confirmation of degreasing for oxygen |
| 89 | Brazing shall be carried out flame source, temperatures and materials as per HTM/ NFPA recommendations |
| 90 | Brazed Pipeline Joints (Copper to copper) should be made using a silver-copper-phosphorous brazing alloy CP104 (5% Silver Brazing Filler metals Rod) to BS EN 1044-1999, no flux to be used. |
| 91 | Copper Fittings: |
| 92 | Medical Gas Pipeline Fittings shall be end feed type, manufactured from the same grade of copper as the pipes and be in accordance with the requirements of BS EN 1254-1:1998 Part 1. The manufacturing company should comply with BS EN ISO 9001:2000 and should be Kite Marked/Lyods or equivalent to EN 1254-1 (up to 54mm). Fittings should be factory degreased suitable for oxygen use and be supplied individually sealed in protective polythene bags. Fittings should be certified for medical use and accompany with oil analysis certificate and conformity certificate indicating suitability for medical use. |
| 93 | Protection for pipes |
| 94 | The pipelines in the bare area like space between buildings should be suitably protected and covered with fire resistant/ retardant insulation in such a manner that inner copper pipe does not come in contact with outer GI pipe. High Quality GI pipe quality covers which should be welded in such a way that only authorized person can open it using proper tools only. Further these should be of such a material and supported in such a manner so as to take load of monkeys/ langoors. Any such supports required should be quoted in the technical bid in the civil work. |
| 95 | Uncovered Sections of GI pipe will have to be protected with weather resistant stainless steel barbed wire. |
| 96 | The pipeline should be suitable for tolerating temperatures of (–) 10oC to (+) 30oC and high ambient humidity exceeding 90% and ice formation during winters. Given the length of the pipeline and climatic conditions, provision for expansion and shrinkage of metal should be incorporated. |
| 97 | All end connections, pressure gauges, valves and fittings of cascade shall be within tamper proof, see through and wire cage enclosure. These shall be on one side of cascade frame for ease of operation. |
| 98 | Parts of the pipe between the building blocks may have to be supported with columns/ beams of iron angle or concrete if necessary, which will have to be done by the firm laying down the pipeline. |
| 99 | The copper tube used for venting (if any) shall be of ASTM B75, B68. |
| 100 | Sizes of pipeline with above specification to be used. |
| 101 | O.D. 42mm x 1.2mm thick |
| 102 | O.D. 35mm x 1.2mm thick |
| 103 | O.D. 28mm x 0.9 mm thick |
| 104 | O.D. 22mm x 0.9mm thick |
| 105 | O.D. 15mm x 0.9mm thick |
| 106 | O.D. 12mm x 0.7 mm Thick |
| 107 | Pipes to be paid as per actual basis. Unused spare lengths will be returned |
| 108 | Pipe line Alarm with Area Isolation (AVSU)Mandev Tubes, Maxflow, Satyam,Nefton, Rajco |
| 109 | AVSU is a modular Area Valve Service Unit (AVSU) with integrated Local Area Alarm. It is manufactured under : Quality Management Systems. It is designed to provide minimum 2 gas and maximum 5 gas service including vacuum. |
| 110 | Microprocessor based module Highly accurate “Heavy Duty” pressure transducer Powder coated aesthetically designed enclosure Enclosure separable from the base for ease of installation Reusable lock assembly Audio mute option PED: 2014/68/EU certified full port Ball Valve (PN 30) Long extension copper pipes to connect MGPS network Designed to serve 2, 3, 4 & 5 gas module Suitable for all medical Gases & Vacuum Adjustment & parameter setting by touch button Operational parameters can be set in-situ Digital & illuminated LED display of “Normal”, “High” & “Low” Digital pressure unit display options - psi / bar or kg/cm |
| 111 | Ball Valves are used to start or stop a flow. In Medical Gas Pipeline System (MGPS), the valves are normally kept open i.e. allow the gas to flow unless it is required to shut-off the gas supply for scheduled maintenance or emergency situation. The importance of full bore ball valves is to reduce pressure drop to almost negligible in the pipeline distribution system so that the designed pressure is available at the outlet point. |
| 112 | 3 GASES |
| 113 | 4 GASES |
| 114 | Master alarm for Plant room Penlon,Rajmed solution, Dragger,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Penlon,Rajmed solution, Dragger,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident, Atlas copco, Ohio, DeltaP, GCE medical |
| 115 | Shut off Valves with Brass Fittings Penlon, Rajmed, wedmed, aktiv,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon,Aktiv, Trident,Atlas copco, Ohio, DeltaP, GCE medical |
| 116 | HORIZONTAL BED HEAD PANEL (CE MARKED) |
| 117 | Bed Head Panel should conform to NFPA99/HTM-02-01/ISO-7396-1/DIN/EN. |
| 118 | • Efficient, safe &. Robust design in extruded aluminum section |
| 119 | • Smooth curved surfaces, and choice of base colour and fascia plates. |
| 120 | • Unit should have integrated rail system to mount accessories. |
| 121 | • The headwall system should be constructed of aluminum extrusions joined together to |
| 122 | form a carcass to suit the particular application. Unit shall be factory assembled for |
| 123 | electrical and mechanical components. |
| 124 | • Segregation of services i.e. electrical wiring supply and Medical gasesshall be maintained throughout. |
| 125 | • Front fascia plate should be removable individually to access for respective service. |
| 126 | • Bed space management system with optional equipment rail.Penlon,dragger,Coair,Beacon Medeas, Greggersen, chicargo Pneumatic, Aktiv, Trident,Atlas copco,Ohio, DeltaP, GCE medical |
| 127 | • Medical gas pipe line outlets should be factory fitted by & tested by the manufacturer. Outlets configuration as per hospital requirement. |
| 128 | • Following accessories should be provided locally with HBHP; |
| 129 | i) 5/15 Amp Modular Electrical Sockets with switches = 6 sets |
| 130 | Bed Head Panel should CE marked. (3 GASES ) |
| 131 | Single arm Cealing Pendent AnaesthesiaCoair,Beacon Medeas, Greggersen, chicargo Pneumatic, Penlon, Aktiv, Trident,Atlas copco, Ohio, DeltaP, GCE medical |
| 132 | Single arm pendants with 330 rotation should be quoted. It should have 5 gas outlets, 4 electricity outlets and a weight bearing capacity of 15 Kgs or more. The pendant should be sturdy and stable at all points of movement. |
| 133 | 330° Utility console rotation-Utilitas C. 330° Utility console rotation+ 330° Arm rotation Utilitas C1. High Payload. True Versatility. Flexible Solution. Effortless maneuverability. Optimum functionality. Easy access to console facia. Bedside safety. User-friendly positioning of Medical Devices.-All services integrated into the pendant system ensuring optimal safety.-Convenient positioning of gas, equipment, electrical and specialty services.-Service head ergonomics – Shelves / Monitor mounting solutions.-Hose connection - Gas specific NIST connectors. Power supply - Low smoke halogen cable through spiral conduit terminating at junction box. Hygiene- Minimum visible screws, combined with smooth surfaces for easier cleaning and disinfection . -Configuration can be customized within the limits of applicable standards .--220V AC Electrical socket -Four shutter type multi-standard sockets compatible to 5-6-10-13A plugs and three 16A sockets will be provided.-Earthing - Protective Earth . -Body (Pendant) Alloy 6063 T6 : Extruded aluminium profile (T = not less than 2.5mm). -Suspension Assembly Pre-engineered Rust-proof (passivate) Trivalent Zinc plated (8-10µm) steel. -Finish (Pendant) Epoxy coating to RAL 7035 (Textured). -SEEB (Optional) Plug and socket for Supplementary Equipotential Earth Bonding. -Mounting Complete mounting system with NIST connection for gas & vac services and terminals for power connection. - Communication Ports 1 - RJ45 Data socket, 1 - RJ11 Telephonic socket |
| 134 | N20 Manifold and control panel |
| 135 | The manifold and control panel should comprise of two banks of 4+4 cylinders each In additional bank of 8 cylinders should be supplied and installed for emergency supply of N20. |
| 136 | The control panel should be meant for the supply of N20 at 500 litres per minute |
| 137 | The unit (control panel)should comply with international standards like NFPA/ HTM-2022/ BIS/CDSSO |
| 138 | The control panel will need to be adjusted at a pressure to ensure 4 bar pressure in the two blocks of the hospital |
| 139 | The control panel should be from reputed manufacturers like: Becon Maedas/Ohio Medical/ Penlon/ Medicop/ Drager/Atlas COPCO/Aktive EuCE or USFDA certified |
| 140 | Feed Gas:Medical grade oxygen as per Indian Pharmacopeia 99.5% at pressure 130 – 140 bar |
| 141 | Gas Delivery Temperature (–) 10oC to (+) 30oC and ambient relative humidity of exceeding 80% |
| 142 | Altitude above MSL: 2250 meters |
| 143 | Frost formation and pressure drop is common problem in winters and rainy season. Therefore heating arrangement for the control panel have to be provided and be documented and quoted. |
| 144 | Safety relief valves, pressure gauges, NRVs and Alarms etc should be provided with means to prevent tampering by Un-authorized persons |
| 145 | Supply Installation and Testing commissioning of 1+1Emergency Manifold and piston operated regulator |
| 146 | Electrical control pannel with phase rectifier Please Enable Macros to View BoQ information |