| 1 | Lump sum price worked out by the contractor for \\"BUILDING WORKS\\" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 2 | Lump sum price worked out by the contractor for \\"INTERNAL WATER SUPPLY \\" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \\"HARDSTANDING AND PARKING TILES \\" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \\"SEWAGE DISPOSAL\\" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \\"AREA DRAINAGE \\" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \\"BOUNDARY WALL AND STEEL GATE\\" as listed in Schedule ‘A’ Part-VII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \\"EXTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \\"EXTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \\"DEMOLITION AND DISMANTLING WORK\\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \\"SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK\\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 12 | Sch 'A' Part-XII MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XI (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK schedule). |
| 13 | INTERNAL WATER SUPPLY |
| 14 | M&L for 15mm bore, angle stop valve cast copper alloy fancy type screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipe or for unions etc. complete all as specified & directed. |
| 15 | S&F Hand Shower (Health Faucet) (ABS Body) with 8mm Dia, 1.2 Meter Long Spirochrome flex tube & Wall Hook etc. complete all as specified & directed. |
| 16 | M&L for construction of refuse bin complete all as shown on (drawing no. TD/2004/27 sheet no.1/2 & 2/2), as specified and as directed. |
| 17 | INTERNAL ELECTRIC SUPPLY |
| 18 | S&F of lamp holder, including 9 watt LED Bulb insulated body with back plate suitable for batten fittings and complete all as specified and directed. |
| 19 | S&F Sheet metal enclosure distribution board VTPN,4 way, 415 volt, double door powder coated, protection class IP-54, isolated neutral bar, mechanical impact strength IK 09 suitable for mounting MCB & /MCCB DBs confirrming to IS-13032, IS-8632,BS5484 with min 200 Amp raiting copper bus bar and grouting, fixing on wall with nut bolts wasshers proper with pcc works and complete all as specified and as directed by Engr-In-Charge. |
| 20 | S&F blanking plates make Havells and Equivalent complete all as specified and directed. |
| 21 | Supply and installation of smart single phase meter with the following specfication : (i) AC single phase two wire,temper proof static meter fo class 1.0,240 volts,50 Hz, 10 to 60 Amps confirminmg to IS 16444 and relivant IEC std with inbuilt 865-867 MHz radio frequency communication facility with self healing mesh network with default and on demand display, billing data generation facility, anti temper features, micro processors and LED /LCD best circuitry.(ii) Meter should support the following data : 15 load survey data for energy, monthly billing survey for commulative energy and maximum demand.(iii) Meter should have connect/disconnect functionality operatable from prepaid billing software.(iv) The meter should support open communication protocall DLMS with the software. |
| 22 | SEWAGE DISPOSAL |
| 23 | M&L for providing,laying,testing and commissioning of 150mm bore Double wall corrugated pipe(Remarks DWC) pipes of SN-8 Grade for sewer line as per IS- 14333,16098 (Parts) : 3013 below ground at requred depth including all jointing fixtures carriage,barricading,lighting arrangment, cutting of any type road etc.Complete all as specified & directed. |
| 24 | M&L for RCC Septic tank (50 users) designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls , Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft , manhole openings with cover connection etc., complete with effective depth of 1.5 meter and overall depth of 3 meter for with up flow filter etc. complete all as specified & directed. |
| 25 | M&L for Soakage wells exc, in any type of soil, foundation in PCC (1:3:6) , walls of honey combed with top ring and solid RCC slab in M-25 concrete, including intercepting chamber, screen chamber, Brick work in CM 1:4, RCC cover slab in M-25/SFRC cover,interconnecting pipes of RCC/DWC complete filled with bricks bats, complete of size 2.40m dia x 3.00 deep etc. complete all as specified & directed. |
| 26 | EXTERNAL ELECTRIFICATION |
| 27 | Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof IP-54 protection CPRI approved, factory fabricated, cubical panel free standing type, made out of 3.00 mm thick CRCA sheet with locking arragement , factory made powder coated as approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 160 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 60 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by Engr-in-Charge. |
| 28 | Item 14.01 (contd/-) (i) MCCB, 4 pole , 16 KA ,100 Amps,-01 No ( Incomming)(ii) MCB , TPN pole , 16 KA, 32 Amps -02 No(iii) MCB , SPN , 10 KA, 6 to 32 Amps -06 No(iv) Solid copper bus bar 160 Amp for 3 phase , 100 Amp for neutral(v) Digital voltmeter of size 96 x96 mm ( 0-500v) with built in selector switch(vi) Digital Ameter of size 96 x96 mm ( 0-400A) with built in selector switch including CT of suitable range. (vii) Digital Energy meter three phase( 10-60A) .(viii) Indication Lamp 22.5 mm dia LED type 240Volts AC to show three phase availability- 01 set.(ix) PCC and block Mesonry work for grouting of panel complete all as specified and directed by Engg-in-charge |
| 29 | Supply and erected ,Testing and commissioning 16 Mtr Galvanized High Mast suitable for Eight (08) No's LED Flood light 1x200 watt ( LED Floodlight carriage shall have arrangement to rotate 360 degree manually). Material for pole shaft as per IS-5986 or equivalent and aerodynamic shape and mechanically strong to face wind speed up to 180 Km/hrs , Material for Base plate -As per IS 2062 and Metal Protection treatment - Hot dip Galvanized as per IS 4759 or robust door opening and locking system with weather proof facilities to increase the life of internal accessories and Double Drum Winch system motorized with manual option including RCC foundation as per OEM recommendation,GI single spike of length 2 Mtrs for Lightening protection all as directed with following as under.(a ) 16 mtrs High Mast Fabricated Part-Top dia 150 mm , bottom Dia-360 mm section-2 section (section length-7.75 Mtrs ) Thickness- 4 mm base ,3 mm top. Base Plate 540 mm x 25 mm , PCD of Foundation bolts - 445 mm, Foundation Bolt dia - M30,Length of bolt - 850 mm ( 8 Nos) with template and anchor plate with following items -High Mast Section sections with base plate, lantern carriage suitable to fix 09 Nos of luminaries (2 x 250 W) symmetrical loading ,foundation accessories, |
| 30 | Item 14.03 (Contd/-) (b) Winches - Motorized with manual optionDouble Drum Winches shall be self sustaining with out need for break spring or clutch required to adjustment and lubricant system the Gear ratio shall be 50 :1 . The Winch shall be salt lubricating system by means of an oil winch and lubricant recommended.(c ) Steel Wire RopeSteel wire rope dia 6 mm shall be fabricated 'Marine Grade\\"-AISI Stainless Steel 316 of 7/19 of construction, 2 wire Rope system .thimbles and terminal combustible material .Steel Wire Rope Shall be factory cut terminated and pre-rigged for case for installation.(d) Mast Head AssemblyThe pulley shall be large diameter appropriate to the multy core flexible cable being used . They shall be of non-corrosive and run of self lubricant bearing with stainless steel spindle. arrangement shall be provided the Electric Cable and steel wire rope are separated before passing over the respect pulleys grooves . The complete chassis shall be hot dip galvanized after fabrication. |
| 31 | Item 14.03 (Contd/-) (e) Lantern CarriageThe lantern carriage shall be of durable steel tube designed to act as electric conduit . It shall be fitted at junction box mounting strips and two segments joints by bolted flange to permit removal from the erected must. Material of lantern carriage 40 NB ERW class B - M.S. pipe and dia of carriage ring 600 mm (ID).Load carrying capacity 9 luminaries, Symmetrically.(f) Cable and Cable ConnectionMuiti core flexible round/flat power cable shall be provided terminating in the base compartment of the Mast fitted with plug or socket and all mast cable shall be connected to a weatherproof junction box on the lantern ring equipt with suitable PVC glands. |
| 32 | Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof IP-65 protection CPRI approved, factory fabricated, cubical panel free standing type, made out of 3.00 mm thick CRCA sheet with locking arragement , factory made powder coated as approved colour, copper bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 160 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 60 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accomodate the following items including supply and fix following items and all as specified and directed by Engr-in-Charge. (For street lights and High Mast) |
| 33 | Item 14.06 (Contd/-)(a) Incoming- MCCB 63 Amps four pole 16 KA -01 Nos (a) Outgoing- MCB 32 Amps four pole 10 KA -02 Nos (b) Copper bus bar 160 Amp 3 phage and neutral -01 Nos (c) Astronomical Timer Switch (Digital Type),Legrend Cat No- Astrorex - 01 No(d ) Contractor 40 Amps four pole - 01 Nos(e) Indicating Lamp set of three - 01 Nos(f) Ammeter Digital type -01 Nos(g) Voltmeter digital type -01 Nos(h) Push button control starter for motorized winch 01 No |
| 34 | Supply and fixing of Lithium base Energy efficient integrated Solar street light of 30/32 watt in Aluminium Die casting body / FRP body , corrosion resistance,integrated PV panel Automatic dusk to input voltage 12.8V with suitable battery ,Driver efficiency .85%,PV module itself will be used to sense the ambient light to switch ON/OFF the Lamp, inbuilt MPPT charge controller, IP65,both PIR and fixed dimming available,4500 lumens (at full brightness) with grater than 150 lumen per watt,5700ANSI, cool white(5500K-6500K),CRI.70,moptical used, Metal core PCB,Low voltage cutoff ,high power LED,wide beam Angle(120 degree) LED Life 50000 hrs, weight less than 15 kg with Green/Red indicator swith with suitable battery rating 12.8V-BIS standard and of complete specified & directed.Protections: Short circuit, overload,Reserve polarity and battery protection.Firm should provide vital parametres Test report from NABL accredited lab and should be of made in India with CE & ROHS complaint. |
| 35 | Supply, install, test and commissioning factory made THERMOPLASTIC CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of minimum size 205 x 255 x 112 mm depth with cable entry size of 10-25 sqmm with terminal. |
| 36 | S&F street light GI bracket of 1.2 mtr long made out of 32 mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts bolts & washers complete necessary fixing arrangements on pole as directed. |
| 37 | S&F of automatic street light switch using Infrared Sensor based NATURE SWITCH for automatic switching of street lights. Nature switch operation switch operation should be based on Natural light Lux level. Required illuminance level for Switching ON is<= 30 lux and for switching OFF>=10 lux. The sensor should also have part night operation facility of min 4 hours to max 12 hours. The sensor along with suitable Power contactors, incoming-outgoing MCB's and Auto manual(Sensor By-pass) selection option should be enclosed in apole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, termite proof and FR grade SMC Junction box conforming to IP54. For three phase load of 5KW (Swadeep--02EC-5kW3P) with: 3 Nos contactors, 3 nos incoming MCB's & 3 nos outgoing MCB's of 20-25 Amps each & circuit wiring (copper) of min 10 sqmm etc.complete all as specified & directed. |
| 38 | Supply and fix PCC cable route indicator pesestal type of size 30cmx30cmx10 cm made out of RCC with 10 mm dia rod circular above the GL 60 CM & below GL 30 CM with PCC (1:2:4) type B1 above GL, PCC ( 1:4:8) in foundation below ground level duly engraved LT cable-MES all directed by Engg- in-charge. |
| 39 | PROVISIONAL LUMP SUMProvide provisional lump sum for Court yard shed as listed below:-(a) Construction of Court yard shed with tubular sections like trusses, purlins, Girders, ralis with 6mm thick plain, multicavity galvanised sheet (coloured) in roof covering, fixed with and including aluminium fillets at joints and aluminium angles at the end, fixed with screws and standard fittings, fixtures and accessories complete all as specified and as per manufacturer's instructions all as specified and directed. Note (i) celing height shall be 4.90 M. (b) Provisional lump sum shall be expended wholly or in parts as directed by GE/AGE(I). The works (Except excavation and earth work) under provisional lump sum shall be measured and paid for at applicable rates in MES SSR-2020 Part-II subject ot percentage (+ or - denomination) computed under last column of this schedule above/ below the lump sum price as inserted by the MES. Please Enable Macros to View BoQ information |