| 1 | Taking down carefully copper/aluminum point wiring (Light fan socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators socket, light fittings etc removing materials for taking credit and making good disturbed surfaces of wall, floor, etc., complete all as specified and directed. |
| 2 | M&L Point wiring using FRLSH grade PVC insulated, unsheathed, stranded copper conductor of size 1.5 Sqmm and one run of 1.5 Sqmm FRLSH grade PVC insulated unsheathed stranded copper conductor as earth continuity wire to be drawn in and including non metallic rigid PVC conduit concealed in wall including MS sheet metal switch / terminal box 1.2 mm thick upto (200x300)mm size box and beyond that not less than 1.63mm thick with Hylam sheet cover 3.00mm thick including cutting and chassing the wall as per site requirement and making good disturbed surface of walls, complete all as specified and directed for :- One light point controlled by one switch |
| 3 | All as per item No. 2 above but one 5 Amps switch socket combination on independent board. |
| 4 | All as per item No. 2 above but One 5 Amp Socket on same board. |
| 5 | All as per item No. 2 above but for 15/16 Amps switch socket out let point by using 4 Sqmm FRLSH grade, PVC insulated, stranded copper, conductor and 4 Sqmm FRLSH grade PVC insulated, stranded copper conductor as earth continuity conductor. |
| 6 | M&L Point wiring using FRLSH grade PVC insulated, unsheathed, stranded copper conductor of size 1.5 Sqmm and one run of 1.5 Sqmm FRLSH grade PVC insulated unsheathed stranded copper conductor as earth continuity wire to be drawn in and including PVC casing capping of suitable size incuding MS sheet metal switch / terminal box 1.2 mm thick upto (200x300)mm size box and beyond that not less than 1.63mm thick with Hylam sheet cover 3.00mm thick and making good disturbed surface to walls, complete all as specified and directed for :- one light/fan point controlled by one switch. |
| 7 | All as per item No. 6 above but one 5 Amps switch socket combination on independent board. |
| 8 | All as per item No. 6 above butone 5 Amps switch socket combination on same board. |
| 9 | All as per item No. 6 above but for 15/16 Amps switch socket out let point by using 2 runs of 4 Sqmm FRLSH grade, PVC insulated, stranded copper, conductor and 4 Sqmm FRLSH grade PVC insulated, stranded copper conductor as earth continuity conductor. |
| 10 | All as per item No. 6 above here-in-before but drawn in through existing concealed conduit for the following :- one light/Fan point controlled by one switch. |
| 11 | All as per item No. 10 above butone 5 Amps switch socket combination on independent board. |
| 12 | All as per item No. 10 above but one 5 Amps switch socket combination on same board. |
| 13 | All as per item No. 10 above here-n-before but point wiring through existing concealed conduit using 2 runs of 4 sqmm PVC insulated copper wire FRLSH grade, 1100 volt grade and one run of 4 sqmm PVC insulated copper wire FRLSH as earth continuity conductor. |
| 14 | S&F in repair including connection of switch piano, flush button, type single pole one way 5 Amps, complete all as specified and directed. |
| 15 | S&F in repair including connection of switch socket combination 5 Amps 2 in 1 flush type, complete all as specified and directed. |
| 16 | S&F in repair including connection of switch socket combination 2 in 1, 3 pin, 5 and 15 Amps flush type, complete all as specified and directed. |
| 17 | S&F in repair ceiling rose, polycarbonate three terminals, complete all as specified and directed. |
| 18 | S&F in repair Electronic fan regulator, stepped type 120/280V complete all as directed by Engineer-in-Charge. |
| 19 | Supply only Modular switch 1 way 6A, 1 module, complete all as directed by Engineer-in-Charge. |
| 20 | Supply only Modular switch 1 way 10A, 1 module, complete all as directed by Engineer-in-Charge. |
| 21 | Supply only Modular switch 1 way 16A, 1 module, complete all as directed by Engineer-in-Charge. |
| 22 | Supply only Modular Bell push 6A 1 module, complete all as directed by Engineer-in-Charge. |
| 23 | Supply only bell, AC, 230 volts, single pole, complete all as directed by Engineer-in-Charge. |
| 24 | Supply only Socket, 6A - 2/3 pin combined 2 module, complete all as directed by Engineer-in-Charge. |
| 25 | Supply only ocket 6A/16A - 2/3 pin combined 2 module, complete all as directed by Engineer-in-Charge. |
| 26 | Supply only Fan step regulator, 120W - 2 module, complete all as directed by Engineer-in-Charge. |
| 27 | Supply only Switch socket Combination 16A, 6 pin, 3 module, complete all as directed by Engineer-in-Charge. |
| 28 | S & F Switch socket outlet 3 pin 6 amp flush type, complete all as directed by Engineer-in-Charge. |
| 29 | S & F Switch socket outlet 3 pin, 16 amp, flush type, complete all as directed by Engineer-in-Charge. |
| 30 | S & F Switch socket outlet multipurpose 3 pin, 16 am and one pin, 6 amp controlled by one switch, complete all as directed by Engineer-in-Charge. |
| 31 | Taking down Sub main /Sub circuit wiring of any type and size including conduit / casing capping / batten wiring, complete all as directed by Engineer-in-Charge. |
| 32 | M&L Submain wiring using three runs of FRLSH grade PVC insulated unsheathed, stranded, copper conductor cable of size 4 Sqmm to be drawn in and including PVC conduit 25mm dia. (Note: Three runs of 4 Sqmm copper wire shall be measured as one unit.), complete all as directed by Engineer-in-Charge. |
| 33 | All as per item No. 32 above here in before but 3 runs of 6 sqmm. |
| 34 | All as per item No. 32 above, but using 4 runs of 6 Sqmm and two run of 6 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, copper wire to be drawn in and inclusing PVC conduit medium grade of suitable size, complete all as directed by Engineer-in-Charge.(Note : Four runs of 6 Sqmm copper wire with two run of 6 Sqmm copper wire shall be measured as one unit.) |
| 35 | All as per item No. 34 above, but using 4 runs of 10 Sqmm and two run of 10 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, copper wire. |
| 36 | All as per item No. 34 above, but using 4 runs of 16 Sqmm and 01 run of 16 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, copper wire. |
| 37 | M&L and fixed in repair Submain wiring using two runs of FRLSH grade PVC insulated unsheathed, stranded, copper conductor cable and one run of earth wire size 4 Sqmm to be drawn in and including PVC casing caping with suitable size according to wire size. (Note: Three runs of 4 Sqmm copper wire shall be measured as one unit), complete all as directed by Engineer-in-Charge. |
| 38 | All as per item No. 37 above here in before but 2x6.0 sqmm + 1 x 6.0 sqmm earth wire. |
| 39 | Supply and fix in repair Vertical TPN MCCB DB 8 way with 200 Amps rated busbar, double door type including provision for fixing MCCB 4 pole 100 Amps, 25 KA complete including taking down old DB and making disturbed surafce good to match the existing surface, complete all as specified and directed. |
| 40 | S & F in repair MCB DB made of sheet steel phosphatised powder coated with bus bar, neutral link, earth bar and din rail, double door type, TPN 4 way 240v, fixed in wall including making good disturbed surfaces including taking down old unserviceable, complete all as specified and directed. |
| 41 | All as per in Item No. 40 here-in-before but of SPN 8 way, 240Volts double door. |
| 42 | All as per in Item No. 40 here-in-before but of SPN 12 way, 240Volts double door. |
| 43 | S & F in repair MCCB 4 pole, with fixed thermal & magnetic release of breaking capacity 16 kA, 415 Volts, 100 Amps, complete all as specified and directed. |
| 44 | All as per item No. 43 above but of capacity 63 Amps, 4 Pole, 16 KA. |
| 45 | S & F in repair MCB SPN 40-63 Amps rating 240, volt, 'C' series, 10 kA, complete all as specified and directed. |
| 46 | S & F in repair, MCB TPN, 415 V, 50Hz, 10kA, 'C' series, 63 Amps series, complete all as specified and directed. |
| 47 | S & F in repair, MCB TP, 415 V, 50Hz, 10kA, 'C' series, 25 to 63 Amps series, complete all as specified and directed. |
| 48 | S & F in repair MCB SP, 6 to 32 Amps, 240 volt, 'B' Series, 10 kA, complete all as specified and directed. |
| 49 | Supply and fixing in repair LED lights fitting 1x 16W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete all as specified and directed. |
| 50 | Supply and fixing in repair LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 51 | Supply & fix in repair LED luminaire 600 mm x 600mm 35/36 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver holder & LED lamp suitable for roof ceiling including connection up with driver three core flexible copper conductor case of suitable size, complete all as specified and directed. |
| 52 | Supply and fixing in repair round shape 6/9/10 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 53 | Supply and fixing in repair round shape 12 watt 221 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 54 | Supply and fixing in repair round shape 15 watt 222 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed. |
| 55 | S&F in repair Sheet metal enclosure single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB SP of 20 Amps, complete all as specified and directed. |
| 56 | Supply and fix in repair exhaust fan, made of sturdy Engineering plastic AC single Phase 230V of size 300 mm sweep with blades and frame and louvers, complete all as specified and directed by Engr in Charge. |
| 57 | Supply and fix in repair exhaust fan, made of sturdy Engineering plastic AC single Phase 230V of size 250 mm sweep with blades and frame and louvers, complete all as specified and directed by Engr in Charge. |
| 58 | M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6 mm buried directly in ground connected to galvanized earth lead strip of size 25 mm x 4 mm by means of bolts, nuts, check nuts and washers of galvanized iron including 40mm dia light grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layers of 15 cm compacted thickness all around the electrode with concrete earth pit with PCC type C1 , 1:3:6 (using 20 mm graded stone aggregate), 50mm thick precast RCC type B1, (1:2:4)(using 20 mm graded stone aggregate) pit cover reinforced with 8mm dia deformed bar and suitable handle made of 10mm dia round bar including galvanised strip of size 25mm x 4mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance not exc 50 mtr and necessary connection and testing complete all as shown in electrical plate No.3 of SSR Part-I, 2009 and all as directed including taking down old unserviceable one. (Note : GI strip upto 7.5 m length shall be deemed to include in the cost of above item. |
| 59 | S & F in repair Earthing conductor with GI strip of size (25 x 4) mm, complete all as directed by Engineer-in-Charge. |
| 60 | M&L for day to day E/M complaint and one electrician and one helper must be report daily except sunday and holiday to the JE E/M office at 0900 am to 1700 hrs to collect their assigned complaint and execute the compaint at the site, material will issued above mentioned items from supply only and for emergency compliant, the contractor must sending an electrician and their helper at any time or on any day, upon being summoned by the AGE E/M and JE E/M. If the complaint is not attend to within one hour, a fine of Rs 500/- will be levied on each complaint, complete all as specified and directed by Engr-in-Charge. |
| 61 | Disconnecting electrically and dismantling of ceiling fans of any make capacity and type, washing thoroughly of bearing /bush, fan blades and body of fan by kerosene /petrol etc and greasing for smooth functioning. Replacement of worn out/defective unserviceable parts (where ever necessary), reassembling the same including provision of three core flexible copper wire 1.5m long, including one coat of synthetic enamel paint (first quality) with super glossy finish to fan body and blades refixing the same to its original position including testing complete all as directed by Engineer-in-Charge. (NOTE : Replacement of worn out/ defective/unserviceable parts, flexible copper wire and rewinding shall be measured and paid separately under relevant items of these schedule). |
| 62 | All as per item No. 61 here-in-before but for Exhaust fans of any size and make. |
| 63 | All as per item No. 61 here-in-before but for air circulator fans/wall mounting fans of any size and make. |
| 64 | M&L Rewinding the motor of AC ceiling fan of any make and size (1200/1400mm) with super enamelled copper wire of adequate size/gauge including all insulation materials, varnishing etc, complete all as directed by Engineer-in-Charge. |
| 65 | All as per item No. 64 here-in-before but for exhaust fans of 300/380mm sweep of any make. |
| 66 | All as per item No. 64 here-in-before but for air circulators/wall mounting fans of any make and size. |
| 67 | Supply only Ball bearing of suitable size for any type/make of ceiling fan. |
| 68 | All as per item No. 64 here-in-before but for Exhaust fans of any type/size/make. |
| 69 | All as per item No. 64 here-in-before but for air circulators/ wall mounting fans of any type/size/make. |
| 70 | Supply only capacitor 220 volts, 2.5 mfd suitable for ceiling fan, Make : SARADA/ TIBOCON/ UNIVERSAL. |
| 71 | Supply only capacitor 220 volts,4 mfd suitable for ceiling fan, Make : SARADA/ TIBOCON/ UNIVERSAL. |
| 72 | S&F in repair Hanging clamp for ceiling fan of adequate size including rubber reel, nuts, bolts and washers etc complete including taking down old unserviceable one, all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |