| 1 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole etc in hard/dense soil |
| 2 | All as per item No. 1 above but excavation depth exceeding 1.5 metre and not exceeding 3.0 metre. |
| 3 | Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil all as directed. |
| 4 | Removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point all as directed. |
| 5 | Supply and laying double walled corrugated HDPE Pipes of size 90 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of LT cables complete all as specified and directed. |
| 6 | Supply and laying double walled corrugated HDPE Pipes of size 110 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of LT cables complete all as specified and directed. |
| 7 | Supply and laying double walled corrugated HDPE Pipes of size 63 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of LT cables complete all as specified and directed. |
| 8 | Supply and laying double walled corrugated HDPE Pipes of size 75 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of LT cables complete all as specified and directed. |
| 9 | Supply and fix in repair GI Pipe Light grade with all connected accessories of sizes 100 mm dia completed as directed for cable protection |
| 10 | M&L for taking down XLPE cable any size/type including cable cover,GI Pipe light grade etc complete all as specified and directed.Note : Excavation and eartyh work measured and paid seperately |
| 11 | Supply and laying,jointing & testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor,1100 volt grade laid in trenches,ducts,drawn through pipes across the road/path/along poles/floors/equipment etc of size 240 sq mm 3.5 core. |
| 12 | All as per item srl item No. 09 here-in-before but of size 95 sqmm 3.5 core |
| 13 | All as per item srl item No.09 here-in-before but of size 35 sqmm 3.5 core |
| 14 | All as per item srl item No.09 here-in-before but of size 25 sqmm 4 core |
| 15 | Cutting of existing road not exc 1.5 mtr in depth and not exceeding 0.45 mtr wide including black top sub base and WBM, well ramming in layers with watering after laying of GI pipe under road making good in all respect to match with the existing surface all as directed by E-in-charge. |
| 16 | S&F in repairs cable straight through joint 35 to 95 Sqmm 3.5 core XLPE 1.1 KV LT Cable heat shrinkable complete including necessary excavation and earth work all as specified and directed. |
| 17 | S&F in repairs cable straight through joint 70 to 95 Sqmm 3.5 core XLPE 1.1 KV LT Cable heat shrinkable complete including necessary excavation and earth work all as specified and directed. |
| 18 | S&F in repairs cable straight through joint 120 to 300 Sqmm 3.5 core XLPE 1.1 KV LT Cable heat shrinkable complete including necessary excavation and earth work all as specified and directed. |
| 19 | S&F in repairs cable end termination joint 95 to 180 Sqmm 3.5 core XLPE 1.1 KV LT Cable heat shrinkable complete including necessary excavation and earth work all as specified and directed. |
| 20 | M & L for replacement of earthing continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earting etc as required 25x4 mm galvanised iron strip for replacing earth continuity conductor of LT panels /bus bar panels etc complete all as specified and directed.. |
| 21 | M&L for removing LT over head conductor from the insulator where ever required and restretching the same without any kink/bend upto permissible sag,binding it on insulator by means of binding wire and testing the LT overhead line after completion as directed.(Note: Three/four runs of LT overhead conductor will be measured and paid as one length ) |
| 22 | M&L for repairing coping of pole with Cement concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate in coping padestal to poles including provision of necessary form work finishing the exposed surface even and smooth in nominal mix cement morter complete all as specified. |
| 23 | M&L for repairing foundation/support of steel tubular pole with Cement concrete 1:3:6 type C-1 using 20 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in nominal mix cement mortar complete all as specified. |
| 24 | Cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in nominal mix cement mortar complete all as specified. |
| 25 | S&F in repair Aluminium conductor, steel reinforced, of size 6/2.11 to 6/3.00 mm (Squirrel to Ferret) straining properly on insulators with and including aluminium tape/winding wire, clamps & jumpers etc. complete all as specified.Note : 3% for sag shall be added in measurement . |
| 26 | S&F in repair Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections medium grade channel 75x40mm including nuts, bolts, washers, welding, bending (cold or hot), drilling holes for bolts, bent to any shape or size as directed and inclusive of one primer coat of red oxide, one under coat of zinc oxide and one finishing coat of aluminium paint complete all as specified. |
| 27 | Supply and fix in replacing LT Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle, two gavanised iron washers and one galvanised iron nut, 50mmheight, 65mm dia for 550 volts complete all as specified and directed. |
| 28 | Supply and fix in replacing Shackle Type, Porcelain, vitreous, white, brown or green insulator working voltage 1100 volt, height 75 mm and dia 90mm including galvanised mild steel straps, washers, insulator bolts, washers and nuts, of size |
| 29 | M&L for replacing Stay assembly complete with accessories as shown in electrical plate No. 1 ,diameter of stay rod 16mm complete including loop type insulator, stay clamps, all as specified and directed at site.Note:- Earthwork and PCC measured and paid Separately. |
| 30 | Material and labour for replacement of Digital type 3 phase voltmeter of capcity 0-500 V with selector switch complete all as specified and directed. |
| 31 | Material and labour for replacement of Digital type 3 phase ammeter of capcity 0-300 A with selector switch and CTs complete all as specified and directed. |
| 32 | Material and labour for replacement of Neon indicator lamp RYB set of three complete all as specified and directed. |
| 33 | M & L for changing the locks and refixing the doors of LT panels by welding and painting the outer surface of panel complete all as specified and directed |
| 34 | M & L for changing the locks and repairing of PCC foundation including refixing the doors of LT panels by welding and painting the outer surface of panel complete all as specified and directedNote :- PCC for foundation measured and piad separately |
| 35 | S&F in replacement of existing unserviceable changeover any size & capacity with ON load changeover 4 pole 400 Amps front handle operated along with SS enclosure including minor additional/alternation as required at site for fixing and connecting up of changeover all as directed by Engr-in-Charge. |
| 36 | S&F in replacement of existing unserviceable MCCB any size/capacity with MCCB 4 pole 400 Amps 36KA Thermal magnetic and Microprocessor release with thermal magnetic setting type incl providing suitable thimbles/extended terminal with nuts,bolts and washers etc. all as directed by Engr-in-Charge. |
| 37 | S&F in replacement of existing unserviceable MCCB any size/capacity with MCCB 4 pole 250 Amps 36KA Thermal magnetic setting type incl providing suitable thimbles/extended terminal with nuts,bolts and washers etc. all as directed by Engr-in-Charge |
| 38 | S&F in replacement of existing unserviceable MCCB any size/capacity with MCCB 4 pole 160 Amps 36 KA Thermal magnetic setting type incl providing suitable thimbles/extended terminal with nuts,bolts and washers etc. all as directed by Engr-in-Charge. |
| 39 | S&F in replacement of existing unserviceable MCCB any size/capacity with MCCB 4 pole 125 Amps 16KA Thermal magnetic setting type incl providing suitable thimbles/extended terminal with nuts,bolts and washers etc. all as directed by Engr-in-Charge. |
| 40 | S&F in replacement of existing unserviceable MCCB any size/capacity with MCCB 4 pole 63 Amps 16KA Thermal magnetic setting type incl providing suitable thimbles/extended terminal with nuts,bolts and washers etc. all as directed by Engr-in-Charge. |
| 41 | S&F in replacement of existing unserviceable changeover any size & capacity with On load changeover 4 pole 100 Amps with side handle operated including minor additional/alternation as required at site for fixing and connecting up of changeover all as directed by Engr-in-Charge. |
| 42 | S&F in replacement danger notice plate of 1.6 mm thick mild steel sheet,vitreous enamelled white with letters,figures and conventional skul and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved size 20x15 cm for Low tension line 415 V for LT poles /sub stn complete all as specified . |
| 43 | Supply and fixing in replacement of G I tubing 40 mm dia light grade galvanised with all fittting and in replacement on wall ceiling or laid in floors complete all as specified and direceted at site . |
| 44 | M&L for replacing 3 core copper flexible cable 2.5 sqmm PVC un-sheathed FRLS complete all as specified and directed . |
| 45 | M&L for painting of steel tubular pole upto 09 mtr length incl MS clamp , bracket, cross arms with two coat of alumnium paint after preparation of old painted surface and applying metallic primer , providing 03 nos alternative strip of 30 cm wide with black and yellow super quality enamel paint above embedded level and writing pole nos with 02 inch wide letter complete all as specified and directed.Note for item No 43 : Necessary electric shutt down will be taken from the Dpt before commencing the work . |
| 46 | M&L in replacing LT line seperator made of PVC 4 line complete with screws, bolts , nuts all as specified and direted. |
| 47 | M&L for replacing aluminium lugs/themble 300 sqmm |
| 48 | M&L for replacing aluminium lugs/themble 240 sqmm |
| 49 | M&L for replacing aluminium lugs/themble 185 sqmm |
| 50 | M&L for replacing aluminium lugs/themble 120 sqmm |
| 51 | M&L for replacing aluminium lugs/themble 95 to 70 sqmm |
| 52 | M&L for replacing aluminium lugs/themble 50 to 16 sqmm |
| 53 | Supply installing, testing and commissioning of Bus bar junction box panel outdoor of size 0.75x0.6x0.3 Mtr kiosk type factory made of angle iron 65mmx 65mmx 6mm on all side welded to 3.15 mm thick CRCA sheet steel for outer compartment and 2.0 mm thick for inner compartment with openable shutteron both sides ( front and rear) , having locking arrangement totally enclosed weather proof outdoor spray painted internally and externally with two coats of synthetic enamel paint over a coat of primer suitable for 440 volts, 3 phase, 4 wire, 50 Hz with Aluminium bas bar of capacity 400 Amps AC supply, electrically connected as per norms and fitted with following accessories all as specified and directed by the Engr-in Charge. (Note:- Bus bar junction box shall be mounted on PCC 1:2:4 type B-1 with 20 mm graded stone aggregate foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC block shall be deemed to be included in the unit rate quoted for the item .Note:- Drg of bus bar junction box panel shall got approved before execution at site. INCOMMER/OUT GOINGIncoming MCCB, 415V, 4 pole, 200 Amps, 36 KA -01 nosIndicator Lamp-01 Set (Set of three) |
| 54 | Taking out Air circuit breaker of capacity 800 A, 430 volts,3 ph, 50 Hz, 100 KA of any make and type from the cubical panel, for repairs/overhauling and servicing including replacement of wornout parts comprising the following works. Make - Schneider electric (a) Removing the complete fixed contacts, moving contacts, cleaninig the contacts,removing the fittings and fixing back to the breakers after adjusting the pressure(b) Checking spring tension relay of the breaker, lubricate and align properly for smooth and perfect operation(c) check and service the operating mechanism closing mechanism, and tripping mechanism including spring pressure, position etc(d) checking, setting of the movement of the trolly of breaker lubricate it adjust the stopper bolt/lever for proper functioning of the breaker(e) check the auxilliary switch, shunt trip assembly, closing / Trip solenoid, limit switch and complete contol wiring of the breaker and repair the same for effective functioning of the breaker(f)Testing of IR value with the help of meggar and commissioning the LT Air circuit breaker all as specified and as directed by Engr-in-chargeNote:- ACB spares shall be measured and paid seperatly under relevent item. |
| 55 | Supply only the following parts to the Air circuit breaker of cap 800 A , 3 phase, 430 volts, 100 KA all as per exsisting make and type |
| 56 | (a) Moving contact |
| 57 | (b) fixed contact |
| 58 | (c ) Arc Shield |
| 59 | (d) Auxiliary switch |
| 60 | (e) latch switch assly |
| 61 | (f) Closing soleniod |
| 62 | (g) loading Spring |
| 63 | Supply and erection in replacement of truely vertical position steel tubular swaged pole complete with cast iron base plate finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.0 mtr long) including painting with two coats of aluminium paint over one coat of red oxide primer, with black and white strips 30 cm each starting with black strip upto 1.5 mtr complete all as specified and as directed.Note: - Earthwork and PCC measured and Paid Separately |
| 64 | Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 3 of SSR Part I of 2009.00 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric weight not less than 4 Kg / Sqm), funnel with wire mesh, I watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 25x4 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified. |
| 65 | Deduct Credit for Demolished/Dismantled material Rs (-) 71,045.00 (Minus) as listed in Schedule 'A' Part-II (Credit Schedule)Note : Tenderers will not quote against this item being a tentative amount, to be considered to arrive at the 'Contract Sum'. Please Enable Macros to View BoQ information |