Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | INTERNAL ELECTRIFICATION WORKS :- SUB-HEAD - Internal Wiring |
| 2 | Wiring point for light with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit concealed in the wall and partly concealed laid in slab complete with 14 SWG copper earth continuity wire,GP Box , piano type switch & ceiling rose/ angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respect, as directed including matching colour wash. PS-138(C) |
| 3 | Wiring point for two way with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit concealed in the wall and partly concealed laid in slab complete with 14 SWG copper earth continuity wire,GP Box , piano type switch & ceiling rose/ angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respect, as directed including matching colour wash. PS-139(C) |
| 4 | Wiring point for fan/ fresh air fan with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit concealed in the wall and partly concealed laid in slab complete with 14 SWG copper earth continuity wire,GP Box , piano type switch & ceiling rose/ angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respect, as directed including matching colour wash. PS-140(C) |
| 5 | Wiring point for Plug point with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit concealed in the wall and partly concealed laid in slab complete with 14 SWG copper earth continuity wire,GP Box , piano type switch & ceiling rose/ angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respect, PS-141(C) |
| 6 | Wiring point for Call Bell Point with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit concealed in the wall and partly concealed laid in slab complete with 14 SWG copper earth continuity wire,GP Box , piano type switch & ceiling rose/ angle/batten holder on 3 mm thick phenolic laminated backelite sheet etc., complete in all respect, PS-142(C) |
| 7 | Supply and fixing of power plug with 20A/250 volt flush type modular switch and 5 pin 20A/250V flush type universal socket in concealed M.S. box including supply of all material laour T&P etc. required for proper completion of work |
| 8 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 10 | Addition when modular type switches etc. are used in place of piano type switches etc. in various wiring points. Add for light / fan points with modular type switch in place of piano type switch. |
| 11 | Addition when modular type switches etc. are used in place of piano type switches etc. in various wiring points. :- Add for 2 way light point with modular switches in place of piano type switches. |
| 12 | Addition when modular type switches etc. are used in place of piano type switches etc. in various wiring points. :- Add for plug point with modular switch & socket in place of piano type switch & socket. |
| 13 | Addition when modular type switches etc. are used in place of piano type switches etc. in various wiring points. :- Add for HPMV/Exhaust fan point with modular type switch in place of piano type switch. |
| 14 | Addition when modular type switches etc. are used in place of piano type switches etc. in various wiring points. :- Add for Call bell point with modular type bell push in place of piano type bell push. |
| 15 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.:-Telephone socket outlet |
| 16 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.:-TV antenna socket outlet |
| 17 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.:-Bell push |
| 18 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.:-CAT -6 / DATA outlet |
| 19 | Supply and fixing of electronic fan dimmer(Modular) 300/400 watt, ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work. |
| 20 | Supply and fixing hexagonal/Round G.P.fan box of approved make made up of 1.0 mm thick ISI Marked G.P.sheet spot welded Four to Eight holes of 25.4 mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5 mm G.P. Sheet made upper & lower cover duly screwed fitted with 300 mm round zink coted M.S Bar X 12 mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material, labour, T&P etc. required for proper completion of the work. |
| 21 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 22 | Supply and fixing of G.P. Modular switch box for 1 / 2 Module of approved make made up of 1.0 mm thick ISI Marked G.P.sheet including adjestable Nakka and holes plugged with PVC Nylon Caps . Two or more holes for pipe entry of 25.4 mm on upper and lower sides of the box. Holes should be semi-shuttered type and fitted with heavy brass Earth Piller duly screwed & brand name should be embossed. Box flushed in wall including cutting of brick work, fixing it to the level with cement sand mortar, including matching colour wash with s/o all materials, labour and T&P required for proper completion of work as directed at site by the Engineer in charge. |
| 23 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 1 or 2 Module |
| 24 | Supply and wiring of submain with FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in Heavy gauge PVC conduit partly laid in slab alongwith with reinforcement before concreting and partly concealed in wall with FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable as earth continuity wire drawin in conduit, complete in all respects |
| 25 | Supply and wiring of submain with two number 2.5 sq.mm. FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 20 mm dia heavy duty (2mm thick) PVC conduit with 1 number 1.5 sq. mm. FRLSH PVC insulated 1100 V grade multistrand single core copper conductor as earth continuity wire. complete in all respect. |
| 26 | 2 X 4 sq. mm + 1 X 2.5 sq. mm earth wire in 20 mm dia heavy duty (2mm thick) PVC conduit |
| 27 | 2 X 6 sq. mm + 1 X 4 sq. mm earth wire in 25 mm dia heavy duty (2mm thick) PVC conduit |
| 28 | 4 X 6 sq. mm + 2 X 4 sq. mm earth wire in 32 mm dia heavy duty (2mm thick) PVC conduit |
| 29 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire in 32 mm dia heavy duty (2mm thick) PVC conduit |
| 30 | 4 X 16 sq. mm + 2 X 10 sq. mm earth wire in 40 mm dia heavy duty (2mm thick) PVC conduit |
| 31 | Conduit for ELV services :- Supply and fixing and concealing of 20 mm dia. 2mm thick PVC conduit pipe with ISI mark embossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin / adhesive to make the complete piping rigid, plastering with cement sand mortar finished to the level with matching colour wash including cost of all material labour and T&P etc required for proper completion of the work as per directions and to the satisfaction of Engineer in charge. |
| 32 | Conduit for ELV services :- Supply and fixing and concealing of 25 mm dia 2 mm thick PVC conduit Pipe with ISI mark embossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin / adhesive to make the complete piping rigid, plastering with cement sand mortar finished to the level with matching colour wash including cost of all material labour and T&P etc required for proper completion of the work as per directions and to the satisfaction of Engineer in charge. |
| 33 | Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface / recessed steel / PVC conduite as required :- 1 run of cable |
| 34 | Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface / recessed steel / PVC conduite as required :- 2 run of cable |
| 35 | Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface / recessed steel / PVC conduite as required :- 3 run of cable |
| 36 | Supply and fixing and concealing of 20 mm dia. 2mm thick PVC conduit pipe with ISI mark embossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin / adhesive to make the complete piping rigid, plastering with cement sand mortar finished to the level with matching colour wash including cost of all material labour and T&P etc required for proper completion of the work as per directions and to the satisfaction of Engineer in charge. PS-148(A) |
| 37 | Supply and fixing and concealing of 25 mm dia 2 mm thick PVC conduit Pipe with ISI mark embossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin / adhesive to make the complete piping rigid, plastering with cement sand mortar finished to the level with matching colour wash including cost of all material labour and T&P etc required for proper completion of the work as per directions and to the satisfaction of Engineer in charge.PS-149(A) |
| 38 | SUB-HEAD - Switchgears & DBs |
| 39 | S&F surface/flush mounting 8ways SPN distribution board with additional metal door without MCB complete in all respect, as directed by Engineer in charge. CAT A |
| 40 | S & F surface/Flush mounting 12 ways SPN distribution board with additional metal door without MCB complete in all respect, as Direct by Engineer in Charge. - CAT A |
| 41 | S & F surface/Flush mounting 6ways TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer in charge. - CAT A |
| 42 | S & F surface/Flush mounting 8ways TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer in charge. - CAT A |
| 43 | S & F surface/Flush mounting 12ways TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge. - CAT A |
| 44 | S&F of 6 Amp to 32 Amp. SP MCB (10 KA) C Curve - CAT A |
| 45 | S&F of 40 Amp. DP MCB (10 KA) C Curve - CAT A |
| 46 | S&F of 63 Amp. DP MCB (10 KA)- CAT A |
| 47 | S&F of 6 Amp. to 32 Amp. 4 pole MCB (10 KA) C Curve - CAT A |
| 48 | S&F of 40 Amp. 4 pole MCB (10 KA) - CAT A |
| 49 | S&F of 63 Amp. 4 pole MCB(10 KA) C Curve - CAT A |
| 50 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.:- 25 Amps (DP) |
| 51 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.:- 40 Amps (DP) |
| 52 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.:- 63 Amps (DP) |
| 53 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.:- 40 Amps (FP) |
| 54 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.:- 63 Amps (FP) |
| 55 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel at least 2 mm thick, vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 56 | SITC of KV Thermoplastic Circuit Breaker Boxes IP-65 with Metric knock outs for Cables entry with 3Nos IP:66 Glands. |
| 57 | SUBHEAD- Hot Dipped Galvanized Iron Cable Tray |
| 58 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.:- 150 mm width X 50 mm depth X 1.6 mm thickness |
| 59 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.:- 300 mm width X 50 mm depth X 1.6 mm thickness |
| 60 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.:- 450 mm width X 50 mm depth X 2.0 mm thickness |
| 61 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. :- 150 mm width X 50 mm depth X 1.6 mm thickness |
| 62 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. :- 300 mm width X 50 mm depth X 1.6 mm thickness |
| 63 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. :- 450 mm width X 50 mm depth X 2.0 mm thickness |
| 64 | Supplying and installing following size of perforated hot dipped galvanised iron cable tray \\"tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with g.i. suspenders including g.i. bolts & nuts, etc. as required.:-150 mm width X 50 mm depth X 1.6 mm thickness |
| 65 | Supplying and installing following size of perforated hot dipped galvanised iron cable tray \\"tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with g.i. suspenders including g.i. bolts & nuts, etc. as required.:- 300 mm width X 50 mm depth X 1.6 mm thickness |
| 66 | Supplying and installing following size of perforated hot dipped galvanised iron cable tray \\"tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with g.i. suspenders including g.i. bolts & nuts, etc. as required.:- 450 mm width X 50 mm depth X 2.0 mm thickness |
| 67 | Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray \\"Reducer\\" (galvanization not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. :- 150 mm width X 50 mm depth X 1.6 mm thickness |
| 68 | Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray \\"Reducer\\" (galvanization not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. :- 300 mm width X 50 mm depth X 1.6 mm thickness |
| 69 | Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray \\"Reducer\\" (galvanization not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. :- 450 mm width X 50 mm depth X 2.0 mm thickness |
| 70 | Supply & Fixing of openable top Cover floor Junction Boxes made from 2mm thick pre-galvanised GI sheets for bottom & sides & 3mm thick GI top Cover complete with rubber gasketing beneath the top Cover. The Junction Boxes shall be suitable to accommodate GI floor raceways as specified above, necessary civil work as described in earlier item to be included here too. - 150 x 150 x 40 mm |
| 71 | SUBHEAD- Light Fixtures and Fittings |
| 72 | Supply,Installation, Testing and Commissioning of 42W Reces 600 X 600 LED Luminaire with housing made up of CRCA for efficient dissipation and diffuser made up of High quality polycstyrene opal diffuser to enhance the aesthic of the fixture and to provide glare free uniform light distribution, Powered by an independent output electronic LED driver (SMPS based constant current supply) with Output Short circuit protection, Surge Voltage protection & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 42W and System Efficacy not less than 120 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<=10%. LED Average life L70B50: 50000 hours.Operating temperature: -10 °C to +40°C , Operating voltage range: 140 V - 270 V,. Luminaire Should conform to IP40 Classification. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80 for led source, Driver and Fixture to be BIS certified. |
| 73 | Supply,Installation, Testing and Commissioning of ceiling recessed downlight made up of Die Cast Aluminium/Aluminium for general lighting application that runs on 230-240VAC .Fixture should equipped with COB LED Wattage of the fixture should be 20W. System Efficacy 100Lm/W, THD<10%, CRI>80, PF>0.9 Fixture should have delivered lumen output of 2000lm min.Fixture should have CCT of 5700K. Fixture should be IP20 rated min.Fixture should have control options of on-off. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80 for led source, Driver and Fixture to be BIS certified . |
| 74 | Supply,Installation, Testing and Commissioning of 12W Surface DownLight Luminaire with housing heatsink made up of pressure die-cast Aluminium for efficient heat dissipation and diffuser made up of High quality polycarbonate diffuser to enhance the aesthic of the fixture and to provide glare free uniform light distribution, Powered by an independent, isolated, output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 12W and System Efficacy not less than 110 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<=10%. LED Average life L70B50: 50000 hours.Operating temperature: -10 °C to +45 °C , Operating voltage range: 140 V - 270 V,. Luminaire Should conform to IP40 Classification. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80 for led source, Driver and Fixture to be BIS certified. |
| 75 | Supply and fixing of water tight oblong 10 Watt LED bulkhead luminaire with driver set confirming to IP 65 and above Protection . complete in all respect. CAT-AAA PS-1417 |
| 76 | Supply,Installation, Testing and Commissioning of Lumiline Plus 36W LED batten luminaires with housing made of Aluminum Extrusion for thermal management with an anodized finish. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free symmetric light distribution. Luminaires should be with min 130 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000 Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant current Potted driver offering THDi<15% , compliance, Output Short-circuit protection, Surge Voltage protection, and other reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 2.5kV surge protection. Luminaires manufacturer to have an in-house NABL-accredited Laboratory for testing Photometric parameters. |
| 77 | Supply,Installation, Testing and Commissioning of 25w Surface/suspended linear 4ft luminaire(50mm width) made of Aluminum extruded housing in white powder coated finish and snap fit plastic moulded end caps, suitable for standalone and continuous row mounting for endless line of light, High efficiency long life LED package in integral module with lumen efficacy >100 Lm/W and viewing angle of 120° to ensure better uniformity.Powered by an integral isolated low THD electronic LED driver ( SMPS based constant current supply) with output short circuit protection, surge protection. Lumen Output of 2500 lumens.CRI >80, Color temperature 5700K, THD <10% and PF >0.90,IP20,IK03.Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ; Internal Surge Protection:3.5 KV; Protection : Reverse Polarity, Open & Short Circuit. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE. |
| 78 | Supply,Installation, Testing and Commissioning of 15W Recess DownLight Luminaire with housing heatsink made up of Aluminium Alloy for efficient heat dissipation and diffuser made up of High quality polycarbonate diffuser to enhance the aesthic of the fixture and to provide glare free uniform light distribution, Powered by an independent, isolated, output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 15W and System Efficacy not less than 110 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<=10%. LED Average life L70B50: 50000 hours.Operating temperature: -10 °C to +45 °C , Operating voltage range: 140 V - 270 V,. Luminaire Should conform to IP40 Classification. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80 for led source, Driver and Fixture to be BIS certified. |
| 79 | Supply,Installation, Testing and Commissioning of 40W LED batten luminaires with housing made up of scratch resistant unbreakable polycarbonate in grey finish cable gland is used for maintaining ingress protection. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall deliver excellent illumination & visual comfort with CRI >= 80, High transmittance Opal Polycarbonate diffuser for glare-free symmetric light distribution. Luminaires should be with 110 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000 Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant current Potted driver offering THDi<10% , IP66 protection and impact resistance of IK07.Operating temperature: -10°C to + 40°C , Output Short-circuit protection, Surge Voltage protection, and other reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 4kV surge protection. Luminaires manufacturer to have an in-house NABL-accredited Laboratory for testing Photometric parameters. |
| 80 | Supply,Installation, Testing and Commissioning of 10W LED batten luminaires with housing made of Aluminium Extrusion for thermal management. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free symmetric light distribution. Luminaires should be with min 110 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000 Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant current Potted driver offering THDi<=10% , compliance, Output Short-circuit protection, Surge Voltage protection, and other reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 2.5kV surge protection. Luminaires manufacturer to have an in-house NABL-accredited Laboratory for testing Photometric parameters. |
| 81 | Supply and installation of Strip Light eq. to Philips cat No. 31308 LED Strip 5m Cool/Warm White including driver and all accessories as required.Fixture to be suitable for outdoor as well. |
| 82 | Supply, Installation, Testing and Commissioning of 10W LED batten 2' long with high end diffuser for uniform distribution of light complete with inbuilt electronic driver & installation accessories etc as required for making system functional. (Mirror light) |
| 83 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. PS-705 |
| 84 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. PS-718 |
| 85 | SUB HEAD - LIFT |
| 86 | Design, Fabrication, Supply, Installation, Testing & Commissioning of 1360Kgs @1.5mps .9 mtr rise in Simplex Control; G+1 , 2 stop & 2 opening; SS Hairline Grade‐304 Car with 2‐Panel, Horizontal sliding, Automatic Power operated centre opening Glass Doors of 1000mm (Width) X 2400mm (Height), Dual door opening ssystem and Counterweight Safety,including Interface to Building Monitoring System (BMS) as per technical datasheet (Elevator Schedule of requirement) & specification & work shall be carried out as per direction of Engineer In Charge. |
| 87 | SUBHEAD -ADDRESSABLE TYPE FIRE ALARM & PUBLIC ADDRESS SYSTEM |
| 88 | Supply, Installation, Testing & Commissioning of Microprocessor based Analogue Addressable Type Fire Alarm Control Panel Two Loop Expandable upto Eight Loop. The Fire Alarm Panel shall hae built in Network card interface, Voice Evacuation System Interface, and IP Port for 3D Graphics Workstation or BMS Integration. Each SLC Loop is capable of supporting 240 Addressable Devices. Option for sub-addressing to optimize the number of devices in each loop. The Current capability shall be 200mA in standby and 400mA in alarm. Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each with built-in sync protocol. Group bypass with built-in false alarm prevention technology. Supports 3 configuration files with “hot swap” support. Built-in Walk Test operation. The system can be configured without taking the panel offline. The System shall have 10000 Events log. The System shall have an option for 3D Event Management Interface to display facilities organized by building, floor, and device. |
| 89 | The Panel shall have inbuilt port for Printer and Annunciator. The System shall have sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, The panel complies with latest Fire codes and standards, UL Listed & FM Approved. (The System cost shall be included of all necessary cards, modules, enclosure, CPU and associated acccessories to complete the system design. All components including enclosures shall be UL Listed.) (Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) The Control panel shall have 100% hot redundancy for CPU (or able to work in Degrade Mode). Each Loop card shall have its own integral processor providing survivability on loss of any other component. SLC Should provide full response on loss of other system processor. Each loop of fire alarm panel shall have 10-15% spare addressable units. The Panel should have Built-in Ethernet Port for Webserver, BACnet and 3D Color Graphics Software. 1 Loop Panel shall be Expandable upto 8 Loops. |
| 90 | Supply, Installation, Testing & Commissioning of Analogue Addressable Multisensor equipped with a Bidirectional short circuit isolator having three sensors One Optical and Dual Heat Sensor (Static and ROR both). Two Tri-Color LEDs FOR 360° Visible for Normal, Fault and alarm condition, The addressing shall be by means of both Soft addressing or Hard Addressing like dip switches or decade switches or suitable address cards or through the hand-held device programmer. The Remote output can be controlled by the Fire Alarm Control Panel. The Advanced software algorithms for smoke detection. Anti-Tamper feature provides additional security to all devices. Protect against nuisance alarms caused by dust, insects or other debris. Magnet test option helps with commissioning and maintenance. Alongwith a breakable flat tab in the centre of the base can be cut and inserted in the base outer edge, then a label can can be used to identify the device. The Detectors shall be UL268, 7th Edition/ULC S529 Rev 4 standards & FM Approved. (Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 91 | Supply, Installation, Testing & Commissioning of Analogue Addressable Tri-Mode Heat Detectors equipped with a Bidirectional short circuit isolator that continuously monitors the environmental temperature to report high heat conditions and communicates with the panel using a fully digital protocol. Three operational modes of heat detection 57°C (135°F) & 79°C (175°F) – Fixed Heat Detection & 57°C (135°F) – Rate of Rise and to be possible to configure the detector to work in any of the mode. Two Tri-Color LEDs FOR 360° Visible for Normal, Fault and alarm condition, The addressing shall be by means of both Soft addressing or Hard Addressing like dip switches or decade switches or suitable address cards or through the hand-held device programmer |
| 92 | . The Remote output can be controlled by the Fire Alarm Control Panel. The advanced software algorithms for smoke detection. Anti-Tamper feature provides additional security to all devices. Protect against nuisance alarms caused by dust, insects or other debris. Magnet test option helps with commissioning and maintenance. Alongwith a breakable flat tab in the centre of the base can be cut and inserted in the base outer edge, then a label can can be used to identify the device. The Detectors shall be UL268, 7th Edition/ULC S529 Rev 4 standards & FM Approved. (Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 93 | Supply, installion, testing and commissioning of Dual Action Addressable Manual Pull Station. It shall have Red Light Emitting Diode (LED) for the Alarm indicator and an Amber/Yellow LED for the Fault indicator. The Pull Station uses raised symbols and icons instead of printed text that makes them universally recognized. The Pull Station shall be constructed of High Quality Polycarbonate Resin Thermoplastic “LEXAN” that supports high temperatures without deforming. The Pull Station shall have a translucent plastic panel at the center enabling the visibility of an internal LED & the LED should be visible even when the Pull Station is closed with Junction Box and other mounting accessories for proper installation. The Pull Station should have provision for a Metallic Key lock for Easy reset. The Pull Station Shall be UL Listed & FM Approved.(Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 94 | Supply, Installation, Testing & Commissioning of The Horn/Strobe with Advanced LED Technology which offer an audible/visual solution that delivers exceptional energy efficiency in a compact design. The LED Horn/Strobe provide a lower current draw which allows for more devices on a NAC circuit while reducing the number of external power supplies required. The LED Horn/Strobe offer a wide range of audible/visual settings in a single compact device. The audible settings include Temporal, Continuous, March Time and 20 BPM tones that can each be set for Low or High volume settings. The candela settings can be field-configured for 15, 15/75, 30, 75, 110, 185 cd. The candela setting is displayed through the front window for easy identification.The LED Horn/Strobe shall be UL Listed.(Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 95 | Supply, Installation, Testing & Commissioning of the Output Module controls speakers & Notification Appliances. The module have a panel controlled LED indicator. The LED flashes during normal operation and stays ON steadily when the device is in alarm condition. Supports group activation capability for fast reaction time. Can handle Class A or Class B device wiring. No external EOL required for class A operation. The Module shall be UL Listed & FM Approved. (Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 96 | Supply, installion, testing and commissioning of The Dual Input Module provides two (2) independent contact monitoring circuits only utilizing one (1) address on the SLC loop. It can be used for alarm, supervisory, or monitor type applications. The module has a panel controlled LED indicator. The LED flashes during normal operation and stays ON steadily when the device is in alarm condition. The Module shall be UL Listed & FM Approved. (Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 97 | Supply, installion, testing and commissioning of the Ceiling Mount Speaker assembly consists of a single-piece, 6 W dual cone loudspeaker and frame, with a 100 V, matching transformer, with circular metal grille, clamps, multiple taps for 6w/ 3w /1.5w.(Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 98 | Supply, installion, testing and commissioning of the240 Watts Mixer Amplifier with Two Zone output, USB drive and SD card for MP3 playback, Built-in FM tuner with preset memories, 100V/Telephone input with priority and VOX, Microphone inputs with standard XLR connector, Professional Public Address units with modern state‑of‑the‑art features, Provide crisp call or clear music is as easy as turning on the radio, 4 microphone / line balanced inputs, plus music source input, with outputs available on 100 volt line.(Make:-Advanced/Mircom/Secutron/Honeywell-Gamewell.) |
| 99 | Supply and laying of 2c x 1.5 sq.mm Fire Survival Circuit Integrity Armoured Cable 600/1000 Volt rated with class-2 Copper conductor having cross linkable Low Smoke Zero Halogen insulation as per BS EN50363 and Low Smoke Zero Halogen (LSZH) inner & outer sheath. The cable should meet fire performance circuit integrity test as per BS EN50200 PH-120 & BS6387 CWZ (950 Deg. C for 3 hours). The cable should be LPCB certified to BS EN50200 (PH-120 & BS6387 CWZ. Outer sheath should be in Red colour having ANTI-RODENT LSZH properties. (Make:-AFW/FrTek/TYCO. |
| 100 | SUBHEAD - CCTV SYSTEM |
| 101 | Supply, Installation, Testing and Commissioning of STQC Certified 5 MP or higher Vandal Resistant IR Dome Camera, 5 MP (2592 x 1944) Resolution or better, Motorized Vari-focal Lens (f = 3.6 - 10 mm), Aperture F 1.8 - 2.8, Min. Illumination Color 0.2 lux @ F 1.8, B / W : 0 lux (IR LED ON), Dynamic Range 120 dB (True WDR), IR Cut Filter with auto switch, IR Distance (LEDs) : 50 Meter, Two way audio with built-in Mic and 1/1 Audio In/ Out Ports, 1/1 Alarm in / out, Exposure, White Balance, Self-Adjusting/ Manual Video Mode (Sharpness, Contrast, Colors, Brightness Control), Video Motion Detection, Active Tampering Alarm, Trip Zone, Video Compression: H.265, H.264 (MP), M-JPEG, IP Camera Protocol: ONVIF Profile S, G & T, Quadruple: Video Streaming, Trigger Event: Motion Detection, Alarm in, Audio detection, Tampering, Trip Zone, Event Notification Remote: S / W, Email (with Image), Micro SD / SDHC / SDXC, Smart Failover (Up to 512GB), Analytics events based on AI engine (Person, Vehicle), Intrusion, Line Crossing, IK10 Vandal Proof Casing, IP67 Outdoor Ready, 3-axis mechanical design for installation, Power Source: 12VDC, PoE, Operating Temperature: - 30°C to 60°C, Operating Humidity: 0% ~ 90%, Certification: BIS with ER / UL, STQC (At the time of supply), FCC, CE approval, , MAC Address: Proposed IP cameras must be registered in the same name of the OEM. The IP Camera OEM must confirm that the MAC address of the surveillance cameras; OUI must be in the name of the OEM. etc all complete Approved Make: CP PLUS/ Mobotix / IDIS / Axis / Avigilon / Sony |
| 102 | Supply, Installation, Testing and Commissioning of 5 MP or higher Vandal - Resistant IR Bullet Camera with Heater, 5 MP (2592 x 1944) Resolution or better, Motorized Vari-focal Lens (f = 3.6 - 10 mm), Aperture F1.8 - 2.8, Min. Illumination Color: 0.2 lux @ F 1.8, B / W : 0 Lux (IR LED ON), Dynamic Range: 120 dB (True WDR), IR cut filter with auto switch, IR Distance (LEDs): 60 Meter, Two Way audio with built-in Mic and 1/1 Audio In/ Out Ports, 1/1 Alarm in / out, Exposure: White Balance, Self Adjusting/ Mnaual, Video Mode (Sharpness, Contrast, Colors, Brightness Control), Video Motion Detection, Active Tampering Alarm, Trip Zone, Video Compression: H.265, H.264 (MP), M-JPEG, IP Camera Protocol: ONVIF Profile S, G & T, Quadruple Video Streaming, Trigger Event: Motion Detection, Alarm in, Audio detection, Tampering, Trip Zone, Event Notification Remote: S/W, Email (with Image), Micro SD / SDHC / SDXC, Smart Failover (Up to 512 GB), Analytics events based on AI engine (Person, Vehicle), Intrusion, Loitering, Line Crossing, IK10 Vandal Proof Casing, IP67 Outdoor Ready, 3-axis mechanical design for installation, Power Source: 12VDC, PoE IEEE 802.3af (Class 3), Operating Temperature - 30°C ~ 60°C, Operating Humidity 0% ~ 90%, Certification: BIS with ER/UL, STQC (At the time of supply), FCC, CE approval, , MAC Address: proposed IP cameras must be registered in the same name of the OEM. The IP Camera OEM must confirm that the MAC address of the surveillance cameras; OUI must be in the name of the OEM. etc all complete Approved Make: CP PLUS/ Mobotix / IDIS / Axis / Avigilon / Sony |
| 103 | Supply, Installation, Testing and Commissioning of 32 IP Channel Network Video Recorder, H.265 4K Recorder, , Embedded Linux, Total incoming throughput 370 Mbps or higher, Supported Camera on ONVIF Latest Protocol, 2 HDMI Ouputs and 2 VGI, Recording Resolution up to 12 MP (Depending on IP Camera), H.265, H.264 Video Compression, Recording Mode: Time-lapse, Event, Pre-event, Panic; Trigger Event: (Object Detection, Intrusion, Loitering, Line Crossing, Face Detection), AI by NVR: Minimum 2 Channel face detection and recognition with up to 20 face databases and 20,000 face images, minimum 4 Channel perimeter protection, 8 Channel Smart Motion Detection. , Motion, Trip-zone, Tampering, Video Loss, Audio Detection, Alarm In, Network Alarm, Text-in, System etc. Display Resolution: 4K UHD (3840X2160) Resolution, Allow control of PTZ cameras to authorized users and be used to maneuver a PTZ camera using Built-in GUI PTZ control, , Privacy Mask, Color Control (Brightness, Contrast, Saturation, Hue), event monitoring, Audio Codec Format: G.711, G.726, Audio Data Size: 64 Kbps (per channel), Two-way (Bidirectional Audio, Maximum Live Display Speed: Up to 960 ips, Live Digital Zoom: x2 ~ x12, Search Mode: Time-lapse, Event Log, Text-in, Thumbnail, Metadata, HDD: 8 SATA with upto 20TB HDD support per slot, 1x eSATA port, RAID 0/1/5/6/10 Supported, Event Notification, Email, , Push Notification, Two-way Audio, 2 USB 2.0, 2 USB 3.0, 1 RS232, 1 RS485 port, Built-in/ external 16 channel PoE Switch, FCC, BIS/ UL, CE, Certified etc all complete Approved Make: CP PLUS/ Mobotix / IDIS / Axis / Avigilon / Sony |
| 104 | Supply, Installation, Testing and Commissioning of Survilliance Class hard disk of 6 TB HDD etc all complete Approved Make: WD / Seagate / Toshiba |
| 105 | Supply, Installation, Testing and Commissioning of ONVIF Compliant S&G VMS , Compatible with linux OS , VMS should have An interface to define layouts and pre-set cameras in multiple view mode , Able to switch between different view pages and devices , Zoom in/ Zoom out digitally by mouse scroll wheel ,Live view with stream 1 in full screen mode or stream 2 in multi-view screen mode (Bitrate adjustable) etc as required to complete the system etc all complete Approved Make: CP PLUS/ Mobotix / IDIS / Axis / Avigilon / Sony |
| 106 | Supply, Installation, Testing and Commissioning of 55\\" Smart Android 4K UHD Professional Display, 24x7 Operation, 440 nits Brightness, Smart Android OS, 4K UHD Resolution, Screen Mirroring through, Airplay/Chromecast, Direct LED, 16 Gb storage, Wi-Fi, 178 Degree Viewing Angle, Landscape / Portrait / Tilt Installation, IP / RS232C Control, 10W+10W Speakers, 4 HDMI 2.0, 2 USB, Power Scheduling, 1200:1 Contrast Ratio, Color Gamut (DCI- P3) 92%, HDMI Auto Wake up. 4K HDR Visual Experience through 4K HDR Processor X1, 4K X-Reality PRO, Triluminos PRO, Motionflow XR, HDR10 / HLG / Dolby Vision etc complete Approved Make: Sony / Christie / NEC / LG. |
| 107 | Supply, Installation, Testing and Commissioning of Workstation with Intel Processor I7 or Better, 32GB Memory, 400 GB SSD for OS, 1TB HDD for Local Storage, Gigabit Ethernet, Display Card 4 GB, Windows Operating System (64bit) with Keyboard, Mouse and 21\\" Monitor display etc complete Approved Make: HP / Dell / Lenovo |
| 108 | Supply, Installation, Testing and Commissioning of Category 6 UTP Cable - LSZH, High-Speed Gigabit Ethernet UTP 250 MHz Class E Cables for Cat 6 Consists of 23AWG Solid Bare Electrolytic Grade Copper Conductors, HDPE Insulated Twisted 4 Pair, RipCord, and LSZH Outer Jacket, Gigabit Ethernet (1000 Base-T), UL Listed, RoHS Certified in existing concealed/surface conduits / Raceways complete 305 Mtr. Roll, including Penta Scanning for per Copper connectitvity with other raleted testing and services (as per actual) as per specification etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 109 | SITC of 19” Rack Mount, 12 Port Multi Mode LIU Panel, preloaded with a pigtails, Splice tray & necessary fiber management accessories etc all complete. as per specification etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 110 | SITC of SC-LC MM Fiber Patch Cords ( 3 Mtr), LSZH jacket, meets IEC-60332-1 (LSZH) flame rating for standard safety compliant as per specification etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 111 | SITC of SC MM Pigtail (1.0 Meter), LSZH jacket, meets IEC-60332 (LSZH) flame rating for standard safety compliant. as per specification etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 112 | SITC of 6 Core Multi Mode Outdoor Fiber Optic Cable, High Link Fiber Optic, Armoured, Multi loose Tube, Outdoor Cable, Gel filled, CSM FRP, Single Sheath Black HDPE, OM4, ROHS Certified with OTDR Scanning for OFC per core connectitvity and uplink test for Point to Point with other raleted testing and services (as per actual) as per specification etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 113 | Rack Mountable Layer 2 Distribution Network Switch (for IP CCTV) with POE+ with Min 24 X 10/100/1000 Base-T POE ports with 2 X 1G and 2 X 1/10G (Min) SFP+ ports upgradable to 4 x 10G SFP+ ports with min POE budget of 380 W or better with Fibre transreciever module etc. all complete Approved Make: Cisco / Juniper / HP / Alcatel Lucent |
| 114 | Supply, installation, testing & commissioning of IP55 Outdoor Junction Box For Field Devices at camera side. JB must be of appropriate size to house different components as per CCTV system design confirming. |
| 115 | SITC of 10/100/1000 port Multi mode optical media converter or fibetr transreciver as required at site etc. all complete Approved Make: Cisco / Juniper / HP / Alcatel Lucent |
| 116 | SITC of 4 Port Industrial Grade Switch for Perimeter Camera, Advanced Industrial PoE capabilities with support for HPoE (60 W), IEEE 1588v2 PTP support, Operates at a wider temperature range, withstands greater shock, vibrations, surge and EMI/EMC variance, 4 RJ-45 10/100/1000 Base-T PoE+ ports out of which 2 ports are 60W PoE capable, 2 100/1000 Base-X SFP ports, RS-232 Console (RJ45) all required accessories etc. all complete Approved Make: Cisco / Juniper / HP / Alcatel Lucent |
| 117 | 24U (W 600mm/ D 600mm) Floor mount with front glass door, back steel door and side panels, Accessories of rack With lock & key for all side panels & door, Fan Housing Unit with 4 fans, Cable manager 4U Horizontal x 8, Cantilever tray, AC main Channel 06 points 5 Amp (PDU) ,Earthing Kit, Mounting Hardware (Pack of 10) as per specification etc. all complete Approved Make: Valrack / Netrack / CPMG / President/ APW/Poweride/Derwiser |
| 118 | SUBHEAD - ACCESS CONTROL SYSTEM |
| 119 | Supply, Installation, Testing and Commissioning of Multi Modal Face Recognition cum Fingerprint, Smart Card & Password based Reader, 5\\" Touch Screen LCD, Android OS, 2GB RAM, 16GB ROM, 256 bit encrypted algorithm to protect important information such as personal info transmitted, Support TLS standard security communication protocols, Live Face Detection with anti-spoofing against 2D photograph, mobile selfie and video, Fake Fingerprint Detection Technology, 50,000 Face Storage capacity (1:N), 50,000 Fingers (1:N) / 50,000 Fingers (1:1), 500000 Log capacity, storage, 20,000 Image logs, Onboard Dual Camera, supports Face authentication & verification from up to 3 meters, Communication protocols like TCP/IP, Wiegand Out / IN, RS 485, SD Card, Anti Pass back (Local / Global), Blacklist Employee Management, User wise authentication modes; Built in Lock Control; Mask Detection & Alert (configurable); Thermal Module integration for Body Temperature Detection (Optional), Up to 25,000 lux illumination, UL Listed Power Supply, CE, FCC, RoHS, BIS, certifications etc. suitable for mounting on metal surface/metal frames/ wooden frames / wall / flap barriers or as required based on site conditions including all accessories complete as per specifications. Approved Makes: Secureeye / Essl / Timewatch / HID/ Honeywell/ Smart-I |
| 120 | Supply, Installation, testing and commissioning of Double leaf EM Lock with 1200LBS (600 LBS each) , Collinear Load Test 560 kg,1200 lbs, Operated Voltage 12 / 24 / 48 V DC (optional), MOV Provides Reverse Current Protection, Suitable For Wooden Door, Glass Door, Metal Door, Fireproof Door, Anti-Residual Magnetism Designed High Strength Material, Anodized Aluminum Housing, Design with no Mechanical Bolt, CE Certified capacity etc all complete Approved Makes: Secureeye / Essl / Timewatch / HID/ Honeywell / Smart-I |
| 121 | Supply, Installation, testing and commissioning of Emergency Push Button NO NC Based Stainless Steel, for manual door release etc all complete Approved Makes: Secureeye / Essl / Timewatch / HID/ Honeywell/ Smart-I |
| 122 | Supply, Installation, testing and commissioning of ZL Bracket for 600lbs EM Lock etc all complete Approved Makes: Secureeye / Essl / Timewatch / HID/ Honeywell / Smart-I |
| 123 | Supply, Installation, testing and commissioning of 8 core 1.0mm Cable. Approved Makes: POLYCAB/FINOLEX/BELDEN |
| 124 | Supply, Installation, Testing and Commissioning of POWER SUPPLY UNIT 12V/ 2 AMP |
| 125 | Supply, Installation, Testing and Commissioning of ACCESS CONTROL SOFTWARE FOR PC As per the details enclosed (Entreprise Version). |
| 126 | SUBHEAD -IP-PBX System |
| 127 | Supply of 24 Button IP Digital Telephone Type 1 Senior Executive Phone having 4.3 Inch Tiltable Backlit LCD display, min 10 lines x 40 characters per line LCD display with adjustable angle, Separate Visual Message Wait Indicator Lamp with multicolour option, Minimum 36 flexible programmable keys with dual colour LED, Dial Pad, 4 soft keys, 4 Way Navigational Keys, 20 Fixed DSS function keys, Full Two Way Duplex speaker phone, RJ9 Headset Port, Analog adaptor for ringer and modem support, Wide Size Incoming Lamp with multi colour support, Adjustable Handset and Monitor speaker volume, Add-on support of 20 Key DSS support having Dual colour LED without consuming any additional digital port, ROHS Compliant etc.As per tender specs and should be from Same OEM, Phone must be TEC-ER & EMI EMC Approved & OEM must be registered on Telecom trusted portal & product must be class-I local suppplier with 50% Local content etc. all complete Approved Make: Alcatel Lucent / Unify / NEC / Cisco / Coral/Panasonic |
| 128 | SITC of 12 Button IP Digital Telephone Type 2 Phone having 2.8 Inch Tiltable Backlit LCD display, 4 lines x 16 characters per line LCD display with adjustable angle, Separate Visual Message Wait Indicator Lamp with multicolour option, Minimum 20 flexible programmable keys with dual colour LED, Backlit Dial Pad, 4 soft keys, 4 Way Navigational Keys, 8 Fixed function keys, Full Two Way Duplex speaker phone, RJ9 Headset Port, Analog port adaptor for ringer and modem support, Wide Size Incoming Lamp with multi colour support, Adjustable Handset and Monitor speaker volume, Add-on 8 Key DSS support having Dual colour LED without consuming any additional digital port, ROHS Compliant etc.As per tender specs and should be from Same OEM, Phone must be TEC-ER & EMI EMC Approved & OEM must be registered on Telecom trusted portal & product must be class-I local suppplier with 50% Local content etc. all completeApproved Make: Alcatel Lucent / Unify / NEC / Cisco/Coral/Panasonic. |
| 129 | Supply, Installation, Testing and Commissioning of 6 Button Digital Telephone Type 2 Digital Phone having 3 Inch Tiltable Backlit LCD display, 4 lines x 6 characters per line LCD display with adjustable angle, Separate Visual Message Wait Indicator Lamp with multicolour option, Minimum 6 flexible programmable keys with dual colour LED, Backlit Dial Pad, 4 soft keys, 4 Way Navigational Keys, Fixed function keys, Full Two Way Duplex speaker phone, RJ9 Headset Port, Analog port adaptor for ringer and modem support, Wide Size Incoming Lamp with 7 colour support, Adjustable Handset and Monitor speaker volume, As per tender specs and should be from Same OEM etc. all complete Approved Make: Alcatel Lucent / Unify / NEC / Cisco/ Tadiran/Coral/Panasonic |
| 130 | Supply, Installation, Testing and Commissioning of, TEC-GR Type I, II & III approved IMS IP-PBX System, SIP Compliant, 19\\" 2U Rack Mount design, standalone system port capacity upto 2000 Ports (IP + Analog) and further expandable upto ports over SIP Standard networking, 250 Ch. VOIP resource, in-skin 10 port MCU for integrating VC equipments, 10 port web based video conference bridge further expandable upto 32 Ports, 64 ports voice logger, Seamless 4G/5G communication with wired comunication including BLF on Digital/IP Phone of mobile ringing etc and upto 90,000 call buffer support and equipped with:CO Trunk Line : 8 Nos Nos.PRI (30 Channel)- 1 Nos.IP/ SIP Extension License- 250 Nos.Digital Extension- 32 Nos.OEM must be registered on Telecom trusted portal & product must be class-I local suppplier with 65% Local content etc. all complete.Approved Make: Alcatel Lucent / Unify / NEC / Cisco / Coral / Panasonic. |
| 131 | Supply, Installation, Testing and Commissioning of Rack Mountable Layer 2 Distribution Network Switch, 24 X 1G RJ-45 PoE+ Ports with 380W power budget, 2 x 1G/10G SFP+ Ports and 2 x 1G SFP/Base-T Combo Ports upgradable to 2 x 1/10G SFP+ Ports, Internal Power Supply, Upto 4 Switches or more Virtual Chassis/ Stacking Option, Switching Capacity and forwarding Rate: 128 Gbps or better and 68 Mpps or better, Static Routing, MSTP, RSTP, PVST+,IPv6 Tunneling, LACP, LAG, IGMPv3, DHCP, DHCP82,DHCP Relay for IPv4/IPv6,Multiple microcode image support with fallback recovery, ARP,SDN support through Restful API and openflow 1.3.1, Loopback IP address support for management per service, Policy- and port- based mirroring, Remote port mirroring, sFlow v5 and Remote Monitoring (RMON), Unidirectional Link Detection (UDLD),Digital Diagnostic Monitoring (DDM), LLDP-MED, NTP,MVRP, SNMP, sflow or equivalent with SFP Module should be of same make as switch,etc. all complete Approved Make: Cisco / Juniper / HP / Alcatel Lucent/ Tadiran / Coral / Panasonic |
| 132 | Supply, Installation, Testing and Commissioning of 24 port Cat 6 patch panels available with block of four equipped with tool less IO, Rack Mountable. 19\\" Modular Patch Panel, loaded CAT6 U/UTP 24port LCS2 rack mountable to be compatible in 4nos of 6 X RJ 45 Tool less connector U/UTP unit in a block etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 133 | Supply, Installation, Testing and Commissioning of CAT6 UTP Patch Cord- 1 mtr-in Blue colour etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon/ Derwiser/ Legrand |
| 134 | Supply, Installation, Testing and Commissioning of Floor Standing Network Rack - 42U / 600w / 800d, with Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs. etc. all complete Approved Make: Valrack / CPMG / Netrack/ Derwiser/ Legrand/Poweride |
| 135 | Supply, Installation, Testing and Commissioning of 24 port Cat 6 patch panels available with block of four equipped with tool less IO, Rack Mountable. 19\\" Modular Patch Panel, loaded CAT6 U/UTP 24port LCS2 rack mountable to be compatible in 4nos of 6 X RJ 45 Tool less connector U/UTP unit in a block etc. all complete Approved Make: Belden / 3C3 / Commscope / Siemon Derwiser/ Legrand/Poweride |
| 136 | Supply and Receving,storing,installation,testing & commissioning of 2 Mtr Cat 6 patch cord with 23 AWG suitable for Gigabit connection, it should be suitable to maintain the bending radius as per relevant code. |
| 137 | Supply and Receving,storing,installation,testing & commissioning of Cat 6, SFP Sswitching capacityh 24 port loaded rack mountable Patch Panel. The panel should be fully unshielded. |
| 138 | Supply, Installation, Testing and Commissioning of fully loaded Networking Floor Standing Rack of 28U along with PDU (With surge protection), cable manager, fan etc for Switches, Servers & other accessories etc, complete as required.(At each Floor) |
| 139 | Supply, Installation, Testing and Commissioning of fully loaded Networking Floor Standing Rack of 42U along with PDU (With surge protection), cable manager, fan etc for Switches, Servers & other accessories etc, complete as required.(FOR Server) |
| 140 | Providing Instaltion, testing commisioning Penta testing, Documentation & Certification of Cat6. |
| 141 | OFC Backbone Connectivity |
| 142 | Supply and Receving,storing,installation,testing & commissioning of 6 Core OM3 Outdoor Armoured PE OFC |
| 143 | Supply and Receving,storing,installation,testing & commissioning of Fiber Optic Drawer 24 LC duplex Multimode - LIU Loaded |
| 144 | Supply and Receving,storing,installation,testing & commissioning of LC Pigtails MM 50/125mn 1 Mtr |
| 145 | Supply and Receving,storing,installation,testing & commissioning of SC/LC Duplex Patch Cords OM3 - 3 mtr |
| 146 | Supply and Receving,storing,installation,testing & commissioning of LC/LC Duplex Patch Cord OM3 - 3 mtr |
| 147 | Providing & Fixing of Digital ISDN Key Telephone System in capacity of 02 CO 100 digital Extensions expandable up to 250 extension ,six number digital key telephone and 80 nos caller id phone with 200 pair MDF box.With the following Exclusive Features besides the Standard: Inbuilt CLI on KTS&PBTInbuilt Battery ChargerInbuilt Music on HoldInbuilt Unsupervised ConferenceInbuilt External Call ForwardingInbuilt 8 IP ResourcesHybrid Extensions(Analog/Digital)Inbuilt Voice Mail/AutoattendantInbuilt 4 Party Web Based Video ConfLic(Lan) |
| 148 | Supply, installation, testing, commissioning & configuration of Core Switch : Layer 3 Switch with 24x 1G/10G SFP+ Ports , additional 4x1/10G SFP/SFP+ ports and 2x 40G/100G QSFP+ Port from Day 1. 1x 40 G Passive Direct attached Copper cable (DAC) cable 1m , 16x 10G Short reach ,8x 10 GLong Reach with Hot-swappable Redundant Power Supply and Fans , 3 Years Next Business Day (NBD) Warranty (Make- D-Link/Netgear/HP Aruba |
| 149 | SUBHEAD -Boom Barrier System |
| 150 | Supply, Installation, Testing and Commissioning of Automatic Electromechanical Boom Barrier Suitable road width upto 6 meter for intensive applications, high speed with 6 second opening / closing time with Anti corrosive high strength MS 7 tank powder coated housing with dual colour, IP 67 Protection etc.(for Gate Entry / Exit) Safety sensors to be provided for preventing any accidental damage while closing, MCBF-5 Million cycle, Drive Unit: Heavy Duty Gear Motor. Intelligence: The barrier shall use a suitable AC Drivefor smooth functioning of the equipment. Possibility for integration via standard user interfaces. Power: 230+/- 10% VAC, 50 Hz. Power Consumption: Max 60 Watt, Operating Temperature: -20 Deg to 60 Deg C, Certifications: ISO- 9001:2015, IS0 -14001:2015 , CE, RoHS Certified, IP-67 Certification , Environmental test certified, Input Tolerance test Certified, Surge protection test certified from govt accredited lab from Government accredited lab Valid lab test reports to be submitted with technical bid, Housing dimension - 355mm x 245 mm x 1080 mm etc all complete Approved Make: Speedgatz / Synergy Access / Kaba |
| 151 | Supply, Installation, testing and commissioning of i5 Infrared Beam Set, Infrared-Safe beam sensor consisting of transmitter and receiver for preventing accidental damage to vehicles etc all complete Approved Make: Speedgatz / Synergy Access / Kaba |
| 152 | Supply, Installation, testing and commissioning of Mounting Post for PE Sensor with canopy on top etc all complete Approved Make: Speedgatz / Synergy Access / Kaba |
| 153 | Supply, Installation, testing and commissioning of HELIX Receiver, Integrated inside the control panel, Two Channelsetc all complete Approved Make: Speedgatz / Synergy Access / Kaba |
| 154 | Transmitter, Silicone 2 Buttonetc , Wirelessly to be operated from a distance of approx 20 mtrs with clear sightall complete Approved Make: Speedgatz / Synergy Access / Kaba |
| 155 | Supply, Installation, Testing and Commissioning of 2MP Box Camera with IR Housing and Lens for Number Plate recognition, image Sensor 1/2\\" CMOS, Max. Resolution 1920 x 1080, Auto Back Focus, Min. Illumination Color Mode : 0.02 lux @F1.5, BW Mode : 0.002lux @F1.5, Dynamic Range 120dB (True WDR), Electronic Shutter Speed Auto / Manual , Anti-Flicker, Slow Shutter, Day and Night Yes (ICR), De-fog, Privacy Masking 8 Zones, Intelligent Video Motion Detection, Active Tampering Alarm, Trip Zone, Network, Video Compression H.265, H.264 (MP), M-JPEG, Intelligent Codec, Audio Compression ADPCM 16K, G.726, G.711 u-Law, G.711 a-Law, Two-way Audio -Yes, DirectIP 2.0, ONVIF, Max. Frame Rate 30ips : 1920 x 1080(WDR), Network Protocols - DirectIP 2.0 Protocol, mDNS, uPNP, SNMPv2, Security Digest authentication, Password Protection, User access log, IP Filtering, IEEE802.1x(EAP-TLS), Chained Fingerprint, SSL Encryption, HTTPS Encryption, Edge Storage micro SD/SDHC/SDXC, Smart Failover (Up to 512GB) Alarm and Event, Trigger Event Motion Detection, Alarm in, Audio detection, Tampering, Trip Zone, Event Notification Remote S/W, Email (with Image), Audio In / Out 1(Built In MIC)+1 / 1, Alarm In / Out 2/2, Serial Interface. RS485, Environmental Vandal Proof Casing Outdoor Ready- Operating Temperature-10°C ~ +50°C (+14°F ~ +122°F), Operating Humidity 0% ~ 90%, Electrical Power Source 12VDC, PoE IEEE 802.3af (Class 2), PoE, IEEE 802.3af(Class 2), 5W, Approval FCC, CE, KC, UL |
| 156 | Supply, Installation, Testing and Commissioning of 2MP Varifocal Bullet Camera for Driver Image, Image Sensor 1/2.8\\" CMOS, Max. Resolution 1920 x 1080, Lens Type Motorized Vari-focal, Focal Length 2.8 ~ 12mm, Aperture F1.4 ~ F2.8, Dynamic Range 120dB (True WDR), Electronic Shutter Speed Auto / Manual , Anti-Flicker, Slow Shutter , Day and Night Yes (ICR), IR Distance (LEDs) 30 m , White Balance, Self-Adjusting Video Mode (Sharpness, Contrast, Colors, Brightness Control, Backlight Compensation BLC, Mirroring / Pivot Horizontal / Vertical / Pivot, De-fog, Privacy Masking 8 Zones, Intelligent Video Motion Detection, Active Tampering Alarm, Trip Zone, Video Compression H.265, H.264 (MP), M-JPEG trate Control H.265 - CBR / VBR, H.264 - CBR / VBR, Audio Compression - ADPCM 16K, G.726, G.711 u-Law, G.711 a-Law, Two-way Audio Yes, IP Camera Protocol DirectIP 2.0, ONVIF Profile S/T, Max. Frame Rate 30ips : 1920 x 1080(WDR), Network Protocols DirectIP 2.0 Protocol, IPv4, IPv6, RTP/RTSP/TCP, RTP/RTSP/HTTP/TCP, RTP/UDP RTSP/TCP, HTTP, HTTPS, FTP, SNTP, SMTP, FEN, mDNS, Upnp, SNMPv2, Security Digest authentication, Password Protection, User access log, IP Filtering, IEEE802.1x(EAP-TLS), Chained Fingerprint, SSL Encryption, HTTPS Encryption, Edge Storage micro SD/SDHC/SDXC, Smart Failover (Up to 512GB), Alarm and Event Trigger Event Motion Detection, Alarm in, Audio detection, Tampering, Trip Zone, Audio Alarm Yes, Audio In / Out 1 / 1, Alarm In / Out 1 / 1, Environmental Vandal Proof Casing, IK10, Outdoor Ready IP67, Operating Temperature -20°C ~ +55°C (-4°F ~ +131°F), Operating Humidity 0% ~ 90%, Electrical Power Source 12VDC, PoE, IEEE 802.3af(Class 3), Approval FCC, CE, KC etc all complete. Approved Make: Mobotix / IDIS / Axis / Avigilon / Sony |
| 157 | Supply, Installation, Testing and Commissioning of ANPR Software per channel etc all complete Approved Make: Mobotix / IDIS / Axis / Avigilon / Sony |
| 158 | Supply, Installation, Testing and Commissioning of 4Chhannel Network Video Recorder for ANPR data recording without Storage, Video Inputs 4 IP channels, Max. Incoming Throughput 160Mbps, Supported Camera DirectIP™, AXIS, PANASONIC, ONVIF, Video Outputs 1 HDMI, 1 VGA, Display Resolution HDMI : 3840x2160, 1920 x 1200 , 1920 x 1080, VGA : 1920 x 1200 , 1920 x 1080, Max. Throughput 70Mbps, 120ips@UHD, Recording Resolution Up to 12MP , Video Compression H.265, H.264, Recording Mode Time-Lapse, Event, Pre-Event, Panic, Trigger Event IDLA(Object Detection, Intrusion, Loitering, Line Crossing, Face Detection), BI(Exceed Occupancy Limit, Social Distancing, Mask Rule Violation, Queue, Congestion), Motion, Trip-zone, Tampering, Video Loss, Audio Detection, Alarm In, Network Alarm, Text-in, System, Playback Performance 4ch synchronous playback, 4ch 4K playback, Storage HDD SATA x 2, eSATA x 1, PSE Power PoE(IEEE 802.3at class 4) supported 4 ports, 30W, Event Notification Email (attach clip (.cbf) .MP4), Callback to Remote S/W, Push notification, Two-way Audio Yes, Interface Audio In / Out Local(NVR) : - / 1RCA + 1HDMI, IP Camera : 4 / 4 , Alarm In / Out Local(NVR) : 4 / 1, Alarm Reset In - Serial Interface RS232 (Terminal Block), USB USB 2.0 x 1, USB 3.0 x 1, Operating System Embedded Linux, Environmental Operating Temperature 0°C to 40°C (32℉ ~ 104℉),Operating Humidity 0% ~ 90% etc all complete Approved Make: Mobotix / IDIS / Axis / Avigilon / Sony |
| 159 | 2MP IR 35X Network IR PTZ Camera with minimum specifications as: Sensor Size: 1/2.7\\" CMOS, Progressive Scan; Effective Pixels: (1920 × 1080); Lens: 6.5 mm ~ 200 mm,(+/- 10% on each side), IR LED (Distance : 350m), 36X optical zoom, DC-Auto IRIS lens with Auto ICR (Infrared Cut Filter); Frames: 30 FPS at 2MP; Min. Illumination: 0.001 lux @ F1.6 (color); Electronic Shutter: 1/30-/10,000;Min. Illumination: Color : 0.001 lux @ F1.36 Analytics: Video Motion Detection, Active Tampering Alarm, Trip Zone,Line crossing detectionAlarm in, Audio detection, Tampering;Electronic Image Stabilization; 8 Privacy Mask; Security: HTTPS, SSL,TLS , Network Protoclos:IPv4, IPv6, RTP/RTSP/TCP, RTP/RTSP/HTTP/TCP, RTP/UDP RTSP/TCP, HTTP, HTTPS, FTP, SNTP, SMTP,mDNS, uPNP; Alarm I/O support: 1 In/ 1 Out; Two-way Audio Support: Audio In /Out:1/1;Audio Compression: G.726,G.711;Edge Storage: Micro SD/SDHC/SDXC upto 256GB Card,smart failover;Power: AC24V, High POE, Heater; Environmental Protection: IP66, IK10; Operating temp range : –40°C to 60°C; ONVIF: ONVIF Profile S/G/T; Security Certification:CE/FCC/BIS/, NDAA Compliant;MTBF(Mean Time Between Failure):125000Hrs at 40Degree; Complete with Brackets suitable for wall / pole mounting as per site conditions. Vendor to consider and quote all necessary additional accessories required to make the system functional etc all complete Approved Make: Mobotix / IDIS / Axis / Avigilon / Sony |
| 160 | 9U (W 600mm/ D 600mm) wall mount with front glass door, Accessories of rack With lock & key for all side panels & door, Fan Housing Unit with fans, Cable manager (PDU), Mounting Hardware (Pack of 10) as per specification etc. all complete Approved Make: Valrack / Netrack / CPMG / President/ APW/Poweride/Derwiser |
| 161 | SUB HEAD - AIR CONDITIONING / VRV/VRFSystem |
| 162 | Supply, Installation, testing and commissioning of AIR COOLED & INVERTER BASED VARIABLE REFRIGERANT VOLUME / VARIABLE REFRIGERANT FLOW MODULAR TYPE AIR CONDITIONING SYSTEM with R410A suitable for 415 ± 10% , 50 Hz. The unit shall consist of indoor units and external condensing units and other accessaries as listed below complete in all respects as under: |
| 163 | Outdoor Unit :- Supply, Installation, testing and commissioning of Modular type outdoor units equipped with Heating and Cooling mode highly efficient inverter type scroll compressor(s) with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated. Outdoor units shall have environmet friendly refrigerant R-410A.The C.O.P shall be confirmed by vendor at full and part load at ambient temperature..Complete with M.S mounting stand of approved design for outdoor unit.Nitogen Flushing before gas charging.Pressure testing should be done after installation.Anti corrosive coating should be done at site. |
| 164 | 60 HP |
| 165 | 54 HP |
| 166 | 32 HP |
| 167 | 30 HP |
| 168 | 22 HP |
| 169 | Indoor Units :- Supply,Installation, testing and commissioning of both interconnected with copper refrigerant & drain pipe of required length, insulation, full charge of refrigerant gas and oil, M.S. base frame duly primered & painted, supports etc. complete as per specifications and drawings. SITC of Air Cooled VRV/VRF Cassette type Indoor units equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, electronic expansion valve, outer cabinet, insulation, pipe connections,control and power panel with corded remote control etc. Unit mounted air purification system with Advanced Oxidation Plasma Hydroxyl cells comprising of UVC lamp 254 NM (no ozone) on nanoX coating metallic compound of five metals targeted on Alumninum matrix cell duly enclosed by a poly casing tube, with the capability to produce ionized Hydroxyl oxidizers using plasmoX along with Antimicrobial coating EPA Approved. The unit shall have inbuilt multipin ion generator pins (+- ions 10^6). The cell will have built in LED indication system stating the operation of the system. The power / control cabling between the Pentagon units and the power source / controls shall be included in the cost. The wattage of the lamp shall not be less than 13 watts for CFM upto 1200 CFM and 21 watts upto 5000 CFM. The system shall be capable of reducing microbial bacteria, virus and spores , VoC’, odors and particulates matter. The equipment shall have to CE, ISO 13485, ROHS with 2014/35/EU Low Voltage Directive as well have ICMR approved lab/ CSIR certiffication for COVID-19 certififcation with a kill rate of greater than 99% within 45 mins. The product shall have Green Pro certification. The specific certifications shall be submitted along with the technical submital. The pentagon cells should be selected by considering a load factor calculation for each specific area where the equipment is to be installed. The Cells Should be complete with Transformers, control cabling and Plug Top & necessary power cable. The units shall be 100 percent manufcaturered in India. Vendor to comply all Tender Specifications. etc. of various capacities as per specifications and drawings |
| 170 | 4.55 TR |
| 171 | 3.18 TR |
| 172 | 2.01 TR |
| 173 | 0.8 TR |
| 174 | Fresh air unit (for VRV): :- Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Treated Ftesh AIr unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., Unit mounted air purification system with Advanced Oxidation Plasma Hydroxyl cells comprising of UVC lamp 254 NM (no ozone) on nanoX coating metallic compound of five metals targeted on Alumninum matrix cell duly enclosed by a poly casing tube, with the capability to produce ionized Hydroxyl oxidizers using plasmoX along with Antimicrobial coating EPA Approved. The unit shall have inbuilt multipin ion generator pins (+- ions 10^6). The cell will have built in LED indication system stating the operation of the system. The power / control cabling between the Pentagon units and the power source / controls shall be included in the cost. The wattage of the lamp shall not be less than 13 watts for CFM upto 1200 CFM and 21 watts upto 5000 CFM. The system shall be capable of reducing microbial bacteria, virus and spores , VoC’, odors and particulates matter. The equipment shall have to CE, ISO 13485, ROHS with 2014/35/EU Low Voltage Directive as well have ICMR approved lab/ CSIR certiffication for COVID-19 certififcation with a kill rate of greater than 99% within 45 mins. The product shall have Green Pro certification. The specific certifications shall be submitted along with the technical submital. The pentagon cells should be selected by considering a load factor calculation for each specific area where the equipment is to be installed. The Cells Should be complete with Transformers, control cabling and Plug Top & necessary power cable. The units shall be 100 percent manufcaturered in India. Vendor to comply all Tender Specifications. etc. of various capacities as per specifications and drawings |
| 175 | 1377 CFM |
| 176 | 1024 CFM |
| 177 | 741 CFM |
| 178 | Installation & Allied Works : - Y-joints & header etc above complete as per specification and drawings. |
| 179 | Supply,Installation, testing and commissioning of Centralised Analog remote controllers for operation & status monitoring of VRV/VRF indoor units |
| 180 | Refrigerant Piping (For inside the Building) :- Supply,installation,testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) , Class 'O', k value-0.035 w/mk minimum, Density not less than 55 Kg/cu.m closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps |
| 181 | 41.3 mm O.D. (insulation : 19 mm) |
| 182 | 34.9 mm O.D. (insulation : 19 mm) |
| 183 | 28.6 mm O.D. (insulation : 19 mm) |
| 184 | 22.2 mm O.D. (insulation : 13 mm) |
| 185 | 19.1 mm O.D. (insulation : 13 mm) |
| 186 | 15.9 mm O.D. (insulation : 13 mm) |
| 187 | 12.7 mm O.D. (insulation : 13 mm) |
| 188 | 9.5 mm O.D. (insulation : 13 mm) |
| 189 | 6.4 mm O.D. (insulation : 13 mm) |
| 190 | Refrigerant Piping: (For Outside the Building :- Supply,installation,testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) , Class 'O', k value-0.035 w/mk minimum, Density not less than 55 Kg/cu.m closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping to be coated with two layers of glass clothe dipped in lag coating for mechanical protection against sun light. |
| 191 | 41.3 mm O.D. (insulation : 19 mm) |
| 192 | 34.9 mm O.D. (insulation : 19 mm) |
| 193 | 28.6 mm O.D. (insulation : 19 mm) |
| 194 | 22.2 mm O.D. (insulation : 13 mm) |
| 195 | 19.1 mm O.D. (insulation : 13 mm) |
| 196 | 15.9 mm O.D. (insulation : 13 mm) |
| 197 | 12.7 mm O.D. (insulation : 13 mm) |
| 198 | 9.5 mm O.D. (insulation : 13 mm) |
| 199 | Plastic Propeller Fans :- Supply, installation, testing and commissioning of propeller exhaust fans of various capacities as given below suitable for 240 volts, 50 Hz, single phase AC supply complete with gravity louvers & speed regulator etc with modular type single phase motor starter up to 6A (Rating shall be as per motor) including 3\\" x 3\\" x 2.5\\" G.I. Box with modular, modular cover plate, conduiting and wiring from starter to fan etc as required at site. :- 200 DIA (12mm static pressure, single phase) |
| 200 | Inline Fans :- Supplying, Installing, Testing and Commissioning of Inline fans complete with motor, supporting frame, gravity louvres,etc. as per drawings and specifications. @ 15mm Static. |
| 201 | 900 CFM Inline Fan |
| 202 | 600 CFM Inline Fan |
| 203 | 550 CFM Inline Fan |
| 204 | 500 CFM Inline Fan |
| 205 | 300 CFM Inline Fan |
| 206 | 200 CFM Inline Fan |
| 207 | 150 CFM Inline Fan |
| 208 | SMOKE EXTRACTION FAN :- Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS MS with powder double coated / High duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE-3 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class \\"F\\" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc.The fans shall be as per specifications & tender drawing of following capacity:-Thickness of the casing shall not be less than: For Dia (300 to 650) mm – 2mm, Dia (700 to 1140) mm – 3 mm, Dia (1200 to 1400) mm – 4mm & Dia 1600 – 5 mm.Multi piece casing is not accepted. Manufacturer shall furnish AMCA Test Certificate for air performance along with fire test certificate (Latest) for each fan sourced from that particular factory. :- 16500 CFM |
| 209 | Factory Fabricated Double Skin Scrubber :- Supply, installation, testing and commissioning of factory fabricated Double Skinned Scrubber unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized /pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G tainless steel. The Scrubber shall be complete with spray arrangement with metallic viscous filter & face velocity across the section shall be limited to 152 MPM. The scrubber shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves, viscous filters. The scrubber panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. St Pressure, Fan & Fan motor KW given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Suitable rating Air Scrubber Starter Panel shall be supplied along with each Unit. The scrubber shall conform to specication given in the tender & shall be of following capacity :- 6000 CFM, 3.7 Kw Fan Motor, 50 mm St. Pressure, Monoblock Pump For Kitchen |
| 210 | Factory Fabricated Double Skin Airwasher :- Supply, installation, testing and commissioning of factory fabricated Double Skinned Air-washer unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G stainless steel.Suitable rating Air Washer Starter Panel shall be supplied along with each Unit. :- The Air-washer shall be complete with fill of depth 200 mm & face velocity across the fill shall be limited to 152 MPM. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The airwasher panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The Airwasher shall conform to specication given in the tender & shall be of following capacity. St Pressure, Fan & Fan motor KW given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity.:- 5200 CFM, 3.0 Kw Fan Motor, 50 mm St. Pressure, Monoblock Pump |
| 211 | Ducting :- Supply, fabrication, installation, balancing and commissioning of factory/ site fabricated GI sheet metal Rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings of following gauges as per SMACNA standard:- : G.I. Sheet Metal Ducting (Rectangular) |
| 212 | Thickness 24 G sheet |
| 213 | Thickness 22 G sheet |
| 214 | Thickness 20 G sheet |
| 215 | Thickness 18 G sheet |
| 216 | Duct Insulation-Supply, installation, testing of thermal insulation of supply air ducting with closed cell Nitrile Rubber with prelaminated Aluminium foil on one side having a low stable k value of 0.035 k.cal/hr.m at 10.C and minimum density of 40-55 ± 3 kg/cum.The R.value should be as per ECBC Code.:- 19 mm |
| 217 | Duct Acoustic Lining-Supply & Installation of Acoustic insulation GI Supply air ducts. Acoustic material shall be 15 mm thick open cell elastomeric foam class '1,UL-94HF. The density shall be 180 kg.m3 with thermal conductivity of 0.042 W/ m Deg K.Material shall have anti-bacterial and anti-fungal properties The insulation shall be as per technical specification and drawings etc, All joints to be sealed with anti condensation tapes. :- 15 mm |
| 218 | Grilles/Diffusers: :- Supply,installation, testing and commissioning supply and return air grilles/ diffusers as per specifications and drawings including fixing frame of G.I./wooden in false ceiling/walls. |
| 219 | Aluminium supply air grill with VCD |
| 220 | Aluminium return air grill without VCD |
| 221 | Fresh / Exhaust air louvers with bird screen & damper |
| 222 | Drain Piping : Supply,installation,testing and commissioning of rigid PVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber class ‘O’ . Providng and fixing pipes with all necessary fittings, supports and insulation. |
| 223 | 25 MM |
| 224 | 32 MM |
| 225 | 40 MM |
| 226 | Control & Transmission Wiring :- Supply,installation,testing and commisioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable 25 MM PVC conduits between indoor and out door unit & outdoor units to central remotes controllers. |
| 227 | TOILET ODOR CONTROL SYSTEM :- Supply, installation, testing and commissioning of wall mounted HygieneOX unit which is advance oxidation with nanoX & plasmOX based system. Advance oxidation plasma using unique wave-length photon special metal catalyst layer with the capability to generate Hydroxyl to eliminate contamination in the conditioned space. The system shall have an independent centrifugal fan and on/ off switch. The equipment shall be enclosed in PU coated material for durability and better aesthetics. The units should be designed after undertaking a load factor calculation for each specific area where the equipment is to be installed. The load shall clearly state the number of units required. The system shall be capable of eleminating bad odors, VoC's as well as bacteria, virus, spores and particulates matter. Contaminated Air will be Sucked from one Side and Decontaminated Air will come out from other side. The equipment shall have to GreenPro,CE,ISO 13485,TUV,ROHS with 2014/35/EU Low voltage directive along with FDA compliance certifications. The system shall have a microbiological testing report against Bacteriophage (MS-2 FDA) surrogate SARS Cov-2 with a minimum efficiency of 99 percent along with a Virology report from CCMB lab with a minimum efficiency of 99 percent against SARS Cov-2 within 45 minutes. :- UPTO 500 |
| 228 | Air Curtains :- Supply, installation, testing and commissioning of Galvanized steel housing with baked powder coat finish of air curtains at all open exists as mentioned in drawings and should be as per specification and drawings sizes are as follows.:- a) 7.8 feet length, 21-23 m/s |
| 229 | BMS WORK STATION |
| 230 | Supply, installation, testing and commissioning of BMS Computer System: i7 Processor, latest generation, 2.5GHz, 4MB Cache with 16 GB RAM, & 1 TB SSD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise or latest, Web server software, DVD-ROM Drive (with RAM), 100/1000 Mbps NIC for Network connection and anti virus software as per Tender Specifications. Accessories included 50 Inch LED Screen, Optical Mouse & Key Pad, Windows Licensed software compatible with the above BMS System configuration complete as required. |
| 231 | Supply, installation, testing and commissioning of Laserjet A4 Black and White printer |
| 232 | Supply, installation, testing and commissioning of 24 Port Layer 2 switch, with SFP Module, rack mountable& other termination accessories (Like Pigtails / LIUs / Convertors / Patch Cord, Etc) complete as required. |
| 233 | Application Software :- Supply, installation, testing and commissioning of the following window based graphical software for IBMS system with 1 No. Client for Operator workstation. The Software shall have 3D & HD vector dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility, Native 64 Bit System, Multi-Monitor Support-( Max 4 Nos), Multi-language support, BTL, UL, EN Certified System, BACnet Profile B-AWS (Advanced workstation) as per the BTL Listing, dot net platform, Certified OPC DA Server by OPC Foundation, Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The Software shall comply to international standards and strive to deliver products that meet security standards such as ISA/IEC 62443, UL2900, ISO/IEC 27001, ISO/IEC62443 and OWASP. Cybersecurity audit trail, 4-eye principle, Seamless integration of certificates within customer IT infrastructure, Microsoft’s active directory-based authentication, Use of network infrastructure that supports physical network or VLAN segmentation, Placing the web server in a “demilitarized zone” (DMZ), End-to-end encryption, from client to server, End-to-end encryption between servers, Certificate-based data exchange, Encrypted backupsSupply, installation, testing and commissioning of True IP Based DDC Standalone 32 Bit Intelligent, inbuilt web browser, peer to peer communication, interoperable DDC as per the specification. The compact controller shall have inbuilt 2-port Ethernet switch, WLAN interface and Cloud Connectivity. The controller shall have min 12 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules. The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. The controller shall be freely programmable and have System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories). It should have one integration port inbuilt and port for POT for local interface. (Make Seimens / Honnywell). The above shall be housed in vandal proof, lockable & secure MS Cabinets to be supplied along with all necessary switchgear protections as required. Number of controllers shall have spare capacity of 15% for future expansion. |
| 234 | DDC for Electrical System HT/LT Panels |
| 235 | DDC for Fire Fighting system along with tanks |
| 236 | DDC for Plumbing pumps and tanks |
| 237 | Supply, installation, testing and commissioning of True IP Based BTL & UL Listed for third party integration. The controller shall have 2-port Ethernet switch, WLAN interface and Cloud Connectivity. It should have BTL label (BACnet communications passed the BTL test) and consisting of Dual microprocessor with Storage capacity of 1 GByte RAM. It should support Real Time clock upto 7 Days. It should Support of the major communication protocols: BACnet/IP, BACnet MS/TP, Modbus IP and Modbus RTU upto 500 points. (Note - Integrator shall be of same DDC make only.)Integration of VRV/VRF on Bacnet/IP or Modbus over RS485 Integration of UPS on Modbus/IP or SNMP Integration of DG Sets on Modbus over RS485 Integration of KWH Meters Modbus over RS485 Integration of HT Power Meter on Modbus over RS485 Integration of Lifts on Modbus over RS485 Integration of FAS & PA on Bacnet/IP or OPC or Modbus/IP Integration of CCTV on Industry standard Open Protocol Field instruments (Make Seimens / Honnywell) Supplying, installing, testing and commissioning of the following sensors / transducers / transmitters. (A) VRV / (B) LIFTS / (C) FIRE ALARM SYSTEM / (D) ENERGY METERS / (E) TRANSFORMERS / (F) DG. |
| 238 | Outside Temperature & RH Sensor along with IP65 radiation shield for outdoor protection Measuring Accuracy at At 15…35 °C 0…100 % r.h.: ±2 % r.h |
| 239 | Flameproof Level Switch |
| 240 | Water pressure sensor |
| 241 | Differential pressure switch |
| 242 | Bi Level Switch |
| 243 | IAQ Monitoring Sensor |
| 244 | Cabling and Conduiting |
| 245 | Supply and laying of 2 Core 1.0 Sqmm Annealed Tinned Copper, Twisted pair, Shielded unarmoured cable for signal and power as per specifications |
| 246 | Supply and laying of Cat-6 unarmoured cable with required jacks and points |
| 247 | Supply and laying of MS Conduit 25 mm Size with all accessories |
| 248 | Supply and laying of GI Flexible 25 mm |
| 249 | (WET RISER SYSTEM - PUMPING EQUIPMENTS) |
| 250 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 2850 lpm at 70 m Head. |
| 251 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump). Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 15 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2850 lpm at 70 m Head |
| 252 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump). Horizontal type, multistage, centrifugal, split casing pump of cast iron body & steel Stainless impeller with stainless steel shaft, mechanical seal complete. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S. fabricated Common base plate, coupling, coupling guard, pressure switch , pressure gauge , vibration eliminator pads , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 70 m Head |
| 253 | Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shadeas required. . |
| 254 | Providing, installation, testing and commissioning of stainless steel Ystrainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange :- 80 mm dia |
| 255 | Providing, installation, testing and commissioning of stainless steel Ystrainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange :- 150 mm dia |
| 256 | Providing, installation, testing and commissioning of stainless steel Ystrainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange :- 250 mm dia |
| 257 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :-250 mm dia |
| 258 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :-200 mm dia |
| 259 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :-150 mm dia |
| 260 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :-80 mm dia |
| 261 | Providing and fixing of Rubber Flexible Coupling with Control Unit PN:16 including Matching flanges & fastner. :- 150 mm dia |
| 262 | Providing and fixing of Rubber Flexible Coupling with Control Unit PN:16 including Matching flanges & fastner. :- 80 mm dia |
| 263 | SUB HEAD -(HYDRANTS SYSTEM) |
| 264 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required . Single headed Stainless steel |
| 265 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel |
| 266 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304) |
| 267 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: Stainless Steel (Grade 304) |
| 268 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipments on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. :- 30 m |
| 269 | Supplying, installation, testing and commissioning of weather proof M.S cabinet size 900 mm wide x 2100 mm height x 600mm deep fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following.Gunmetal single headed Hydrant valve - 1 No. Fire Hoses 63mm, 15 M long with accessories - 2 Nos. Short branch - 1 No. First Aid hose Reel - 1 No. Fire Extinguisher - 2 Nos. Fireman's Axe - 1 No. Pressure Gauge - 1 No. The cabinet shall be painted with one coat of primer and 2 coats of synthetic enamel paint of approved shade. |
| 270 | Providing, installation, testing and commissioning weather proof lockable cabinet of size not less than 0.90 x 0.60 x 0.30 mtr made out of M.S. sheet 2mm thick having central opening and 6 mm thick glazed glass doors (Two nos.) suitably marked on the outside with the letters \\"FIRE HOSE\\" including necessary locking arrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade as required as per specifications. |
| 271 | Supplying, installation, testing and commissioning of fire brigade connection of cast iron body with gun metal male & female instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :- 2 way - 100 mm dia M.S. Pipe |
| 272 | Supplying, installation, testing and commissioning of fire brigade connection of cast iron body with gun metal male & female instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : - 4 way - 150 mm dia M.S. Pipe |
| 273 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 274 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 275 | Providing and fixing standard fire man's axe with heavily insulated rubber handle complete as required. |
| 276 | SUB HEAD - (PIPING, VALVES AND ACCESSORIES) |
| 277 | MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 278 | 25 mm dia |
| 279 | 32 mm dia |
| 280 | 40 mm dia |
| 281 | 50 mm dia |
| 282 | 65 mm dia |
| 283 | 80 mm dia |
| 284 | 100 mm dia |
| 285 | 150 mm dia |
| 286 | 200 mm dia (wall thickness 6.3 mm) |
| 287 | 250 mm dia (wall thickness 6.3 mm) |
| 288 | Providing, laying, jointing, testing & commissioning of heavy class M.S. pipes conforming to IS: 1239/3589 complete with fittings including trenching ,refilling and wraping coating etc.(external work) including all fittings and accessories like tees, elbows, flanged joints, rubber insertion, nuts, bolts or cutting and welding joints. Providing thrust block at distance specified as per specifications. (Pipe shall be provided with anti corrosive protective treatment with coal tar/asphalt tape confirming to IS: 10221 standard complete as per specification). All work complete as per specification and as directed by Engineer-In-Charge. (All the fitting i.e. tee /elbow etc. for Valve connections etc. will be flanged joints). 150 mm dia |
| 289 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories. :- Pendent/Upright sprinkler |
| 290 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 291 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mmNPT female thread with reducer, nipple, 2 side brackets, center bracket, stock bar of following sizes complete as required :- 1500mm |
| 292 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. :- 150 mm dia |
| 293 | Providing, fixing, testing & commissioning inspectors test assembly complete with, test valve, sight glass sectional drain valve, union with corrosion resistant orifice all complete strictly as per drawing. |
| 294 | Providing, Installation, Testing and Commissioning of Gun Metal / Bronze Ball Valves screwed ends of following sizes as required. (PN-1.6) :- 25 mm dia |
| 295 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required ::- 80 mm dia |
| 296 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required ::- 150 mm dia |
| 297 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :-80 mm dia |
| 298 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :-150 mm dia |
| 299 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :-200 mm dia |
| 300 | Providing and fixing single acting air valve with screwed inlet 25 mm dia. |
| 301 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronzeworkingpartscomprisingofwatermotor alarm, bronze seat clapper, clapper arm and hydraulically drivenmechanical gong bell to sound continuousalarmwhen thewet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve completewith drainvalveandbypass, test control box, ball valves, MSpipeof requiredsize, flanges,orificeplate,gasket etc of follwing sizes as required :- 150mm dia |
| 302 | SUB HEAD - (FIRE EXTINGUISHERS) |
| 303 | Providing and fixing ABC Powder type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guase internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with re enamel paint and fixed to wall with brackets complete with inernal charge. 6 kg capacity cylinder |
| 304 | Supply, installation, testing and commissioning fire extinguisher of carbon dioxide type consisting of brand new high pressure steel cylinder bearing IS: 7285 mark and having the approval of controller of explosives Nagpur, wheel type valve bearing IS:3224 mark internal discharge tube, 1 meter long high pressure discharge hose, non conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed conforming IS : 15683:2006 :- 4.5kg capacity cylinder |
| 305 | Providing and fixing Kitchen fire extinguisher (K-Type) Fire extinguishers Suitable for Kitchen fire in Industrial, hospital, malls, Schools, College Etc. IS : 15683 latest revision manufacturer and of CRCA sheet in welded construction, finish with epoxy polyster powder coated complete with brass forged ball valve, gun metal cap and nozzle, including initial filled and wall suspension bracket (suitable for fighting in class 'A', B & 'C' that is wood, textile, flammable liquid, electric and gases. :- 4.0kg capacity cylinder |
| 306 | Supply, installation, testing and commissioning of Clean agent Fire Extinguisher mfd to IS:15683 with BIS mark, Brass forged squeeze lever discharge valve (CE MARKED WITH NRV), fitted with pressure indicating guage (CE MARK - 3N APPROVED) with direct nozzle, wall mounting bracket & screw, duly charged . FIRE RATING 1A, 8B :- 5.0kg capacity cylinder |
| 307 | Supply, installation, testing and commissioning of ISI marked Fire and wall suspension bracket fire Extinguisher, Trolley mounted carbon-dioxide type capacity 25 Kg. conforming to IS: 2878 Flat base including valve, discharge hose of not less than 10mm dia 1m long complete in all respects including wheeled trolley, carrying handle and initial fill with CO2 gas as per IS: 307-1996 filled to a filling ratio of not more than 0.667. |
| 308 | Supply, installation, testing and commissioning in position approved make fire bucket of 24 gauge, galvanized steel, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on bottom dome with letters ‘FIRE’ in black and gold with all mounting bracket and screws. |
| 309 | Supply, installation, testing and commissioning of fire Bucket Stand including sheet metal (16 gauge) shade for 5 buckets. Platform and associated civil works complete. |
| 310 | SUB HEAD - (ELECTRICAL PANEL) Fire Fighting Main Panel |
| 311 | Incoming :- 800A, 50kA 4 Pole MCCB, Ics=100% Icu rating / Digital Voltmeter 0-500V with selector switch / Digita. l Ammeter (0-800 A) with selector swtich & CTs etc. / LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps / Set of Copper Bus Bar 300A. OUTGOING :- ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 312 | Main Fire Pump |
| 313 | 250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2sets |
| 314 | Jockey Pump |
| 315 | 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2sets |
| 316 | DIESEL ENGINE CONTROL |
| 317 | Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode. / Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication. / Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter. / All standard relays and accessories for automatic operation of diesel engine. |
| 318 | System Controller |
| 319 | Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 320 | Fire panel as above |
| 321 | EXTERNAL ELECTRIFICATION |
| 322 | SUBHEAD- COMPACT SUBSTATION-630KVA |
| 323 | Supplying, assembling, erecting, connecting, testing and commissioning of 11 KV Compact Secondary Sub Station outdoor type designed for natural cooling having type tested equipment comprising distribution transformers, SF6 insulated compact switchgear having metal enclosed robotically sealed/welded stainless steel tank , low voltage switchboard, interconnection between HT switchgear & Transformer using single core cables and Transformer to LT switchgear using Al bus bars/Cables factory built / ready for connection type,other associated equipment etc including necessary foundation and earth work etc. without oil pits complete as required conforming to detailed specification laid down in the tender documents. The enclosure shall have modular construction using 2mm thick CRCA and 4 mm thick got dipped CRCA sheets for base and shall be painted with polyurethane paint from the exterior.The enclosure for LT switchgear & HT switchgear shall be provided with IP54 ingress protection. The transformer compartment will have IP34 ingress protection. Note- HT & LT Switchgear should be same make. The transformer used shall be specially designed for low losses (As per IS:-1180 level-01) and shall be hermetically sealed oil immersed & with corrugated tank, oil level indicator, hermetic protection realy, pressure relief device, gas filling valve, oil temprature indicator, multi function relay (DGPT Device) etc. as required Complete in all respect.The earthing shall be suitable for 18.3KA fault current.The varoius combinations of CSS shall be as per details below including necessary foundation and earth work etc |
| 324 | HT Switchgear Section |
| 325 | 11KV 3 Way RMU( CCT2) type Compact switchgear unit having 2 No. Isolater load break switches and 1 No SF 6 circuit breaker enclosed in robotically laser welded non-extensible type stainless steel SF6 enclosure with Self powered relay (IDMTL O/C + E/F ) as HT switchgear as per the requirement detailed in the tender documents/SLD. Copper bus bars of 800 A capacity for HT 11 KV network. |
| 326 | Transformer Section |
| 327 | 11KV/415V,630KVA, hermetically sealed oil immersed Transformer suitable for CSS as per detailed specifications, with Automatic on load tap changer & RTCC .Remote tap changer circuit (RTCC) panel with all associated accessories as per schedules and specifications.Taps on HV for HV variation : +5 to - 15 % in the steps of 1.25 with AVR. |
| 328 | LV Switchgear Section |
| 329 | LT section comprising the following & as shown in the drawing:- 1000Amps 415V, 4P, 50Hz, 50KA Manual operated drawout type Air Circuit Breaker (ACB) with overload and short circuit Protection. |
| 330 | RELAYs, METERING INDICATOR & CT's |
| 331 | On/Off Indication lamps with 6A control MCB as per fault requirement. / R,Y,B phase Indication lamps with Control MCB as per fault requirement. / One Set of 5 Nos. indication panel each with 6A control MCB as per fault requirement with ACB. / 1 No. off delay timer for manual operation. / Phase Reversal relay. / 8 Window annunciator all compartment. / Heat shrinkable cable end terminal indoor type cable box 240/300/400 Sq. mm. Size complete all as required to connect incoming and outgoing HT cables to unitized Sub-Station and interconnection of network within the unitized Sub-Station with arc proof shoes. |
| 332 | H.T. Cable |
| 333 | Supplying of following size of Al conductor, XLPE insulated armoured and over all PVC sheathed, 11 KV (E) grade earthed cable as per technical specifications. 3 core x 185 Sq. mm |
| 334 | HT Cable laying |
| 335 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. above 120 and upto 400 |
| 336 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required. 185 Sq. mm |
| 337 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 120 sq. mm and upto 400 sq. mm |
| 338 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) In ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 250 mm dia |
| 339 | Supply & Laying of non skid Electro mat 1mtr wide and 2.5 mm thick 11KV grade IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities. |
| 340 | Supply and fixing in position the approved “Shock Treatment Charts” written in English and Local Language. These charts shall be framed in teak wood frame and covered with glass. |
| 341 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 342 | Supply and fixing position the approved single line diagram framed in 1000 x 100 mm size glass frame and installed in main LT Panel Room. |
| 343 | Supply of tool kit, first aid box with all accessories required for operation and maintainence for 415 volt & 11 kV equipment with 1 pair 11 kV rubber hand gloves of approved make. |
| 344 | SUBHEAD- DIESEL GENERATOR SETS |
| 345 | Supply, installation, testing and commissioning of Prime Duty, Diesel engine driven generating Set (Silent Type) of 625KVA capacity CPCB-IV compliance to ISO-8528-Part 1 with Genset Controller (DIEF / DeepSea / Woodward or eq) and comprising of following:- including necessary foundation and earth work etc. The DG Set emission should be as per revised CPCB-IV norms as per the latest notification MOEFCC NOTIFICATION “GSR 804(E) DATED 03.11 .2022 [F.NO. Q-15017/05/2012-CPW. |
| 346 | a) Diesel Engine |
| 347 | Engine developing minimum 625kVA Gross Engine Power at 1500 RPM rated for Prime Duty with an additional 10% overload capacity for one hour in period of twelve hours of continuous operation at standard operation conditions as per ISO 3046-1/1, ISO 15550 inclusive of all standard accessories like Silencer, After Treatment System In Front of Radiator, High Pressure Common Rail (HPCR) Fuel Injection, ECU control providing efficient performance in terms of power & fuel consumption, Electronic Governing of G3 Governing Class and with all standard accessories as per ISO:8528-5.Engine Cooling System must be designed for 50⁰C ambient |
| 348 | b) Alternator |
| 349 | Synchronous alternator 750KVA, AC 3 phase, 415 volt, 50 Hz, 1500 RPM, 0.8 lagging power factor alternator shall be in SPDP enclosure, self excited, self regulated, foot mounted with end shield. The alternator shall confirm to IS:13364/IEC 60034 – 1 suitable for tropical conditions.Alternator shall deliver full output at 50 degree C, shall have inbuilt BTD and winding temp. detector along with space heaters. Necessary spaace provision for REF protection with separate earth fault CTs shall be provided inside alternator box. |
| 350 | c) Automatic Main Failure Panel |
| 351 | DG AMF control panel with internal access to facilitate both connection and maintenance complete with 1 No 1000Amps ACB WITH COPPER BUSBAR to loads. Ammeter, Voltmeter, frequency meter, Kh meter etc. including light Set ON/OFF battery charge etc. complete in all respect with power loom between alternator & isolator panel thru CU flexible within the Genset Canopy / Acoustic Enclosure.Engine mounted instrument panel fitted with and having digital/Analog display. |
| 352 | d) Acoustic Enclosure |
| 353 | The enclosure fabricated from high grade cold rolled close annealed (CRCA) sheet and steel members lined with high density sound absorption material to reduce the sound level to 75 dBA from the original sound level measured at a distance of 1 meter away from the GenSet, under free field conditions compliance to CPCB- IV Noise limit / guidlines for Dg Set below 1000kVA / 800Kwe. Accoustic and weather proof enclosure suitable for the DG Set with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per CPCB-IV norms.The enclosure will be provided with durable industrial locking system with doors duly gas-keted etc., all complete with ARAI Type approval / certification. |
| 354 | e) Battery |
| 355 | 2x12V, 150 Ah Battery assembly with all necessary connecting leads and terminals of reputed make and stand for lead acid Maintinance free battery. Starter Motor Power must be min 8KW |
| 356 | f) Base frame |
| 357 | Skid mounting type base frame fabricated from suitable size of MS channel / CRCA Sheet providing common bed for engine & alternator directly coupled together with AVM Pads and necessary reinforcement which shall be installed on suitable RCC foundation and vibration isolation arrangement as per recommendations of manufacturer. |
| 358 | g) Testing in Works / Factory |
| 359 | The DG sets will be tested in the works of the manufacturer for 12 hours at full load including 10% over load before dispatch in the presence of the representative of client . Testing will be crried out as per CPWD's specifications. |
| 360 | h) MISC |
| 361 | Inbuilt Capacity Day tank of standard capacity . for fuel storage with level markings inside and outside canopy. After Treatment System In Front of Radiator with DEF (diesel exhaust fluid) / AdBlue storage tank of min 35L for urea dosing with proper connection etc. |
| 362 | EXHAUST PIPING |
| 363 | Supply and Fixing of MS Exhaust Pipe of dia 1x250mm class 'B' for 625KVA DG Set with rain cap. With all accessories etc., complete |
| 364 | Supply and fixing of Thermal insulation on MS Exhaust Pipe of dia 250mm class 'B' for 625 KVA DG Set with 50mm thick LRB/Rock Wool of 96 Kg density per cub mtr. Covered with wire mesh & covered with 24 gauge AI Sheet |
| 365 | Supply, testing and commissioning of Aluminium cladding for residential silencers with LRB Rockwool 50mm Thick, density 64 Kg/cu.mtr., wire mesh and 24 gauge aluminium cladding. complete as required suitable for 500 Kva DG exhaust pipe temperature upto 450°C. |
| 366 | Supply and installation of SS Flexible Bellows, 8\\" dia. (250 mm NB), complete with counter flanges, heat resistant gaskets, nuts-bolts-washers etc., complete as required. |
| 367 | Providing & fixing for MS support structure for exhaust fume pipes from DG Sets (Exhaust pipe to be measured and paid for separately) along horizontal and vertical runs upto the height (as per CPCB norms) including cutting, welding etc and applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by client/Architect. The design of the support structure shall be done by the contractor and shall be as per CPCB norms approved , also to get the approval from the consultant before execution etc. as required. |
| 368 | Provide & fixing fuel piping with pipe supports, bends, flanges packing, hardware's and painting from main storage tank to day oil tank and day oil tank to DG Set of following sizes :- 25 mm dia Heavy duty (Class C ) MS Pipe |
| 369 | VALVES |
| 370 | Supply & fixing the following valves of approved make complete with flanges, bolts nuts and gaskets etc., :- 25mm dia gate valve |
| 371 | Supply & fixing of 990 Litre (14 SWG thick) fuel oil service tank with oil level indicator with level gauge scale, inlet/outlet connection valve, air vent, pedestal for mounting etc., including 02 Nos if hand fuel transfer pumps |
| 372 | Obtaining necessary approvals from the chief electrical inspectorate, if required for electrical safety for 1X 625kVA Genset. |
| 373 | SUBHEAD- 10KVA UPS Please Enable Macros to View BoQ information |
| 374 | SUBHEAD- 10KVA UPS Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail