| 1 | Supply / replacement of 200Amp TPN switch with HRC fuses in the existing panel i/c removal of existing faulty switch, fixing of new switch, connection , testing etc. as complete as reqd.(Havells/ HPL) |
| 2 | Supply / replacement of 63Amp TPN switch with HRC fuses in the existing panel i/c removal of existing faulty switch, fixing of new switch, connection , testing etc. as complete as reqd.(Havells/ HPL) |
| 3 | Supply and Fixing of 63Amp Kit kat type on the existing meter board for incommer supply including dismantlling of damaged / burnt switch from panel / feeder piller etc complete as required |
| 4 | Supply and replacement of 200Amp copper neutral link on the existing meter board for incommer supply including dismantlling of damaged / burnt neutral link from meter board etc complete as required |
| 5 | Supplying and Crimping of aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.( a ) 240 sq mm cable |
| 6 | ( b ) 185 sq mm cable |
| 7 | ( c ) 95 sq mm cable |
| 8 | ( d ) 25sq mm cable |
| 9 | Supply and Laying and fixing of one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV grade of 3.5 x 95 sq. mm in the surface / ground etc complete as required |
| 10 | Supply and Laying and fixing of one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV grade of 4 x 25 sq. mm in the surface / ground etc complete as required |
| 11 | Painting of the existing panel in the meter room / feeder piller with the synthetic paint by two coat of red oxide and two coat of paint including cleaning the panel sheet by rubbing with sand paper |
| 12 | Dismantling of the existing burried cables in the panel and burnt switches to make free the space for connections etc complete as required |
| 13 | Dismantling and pull out of the existing damaged underground aluminium power cables including excavation and refilling of the trench etc complete as required |
| 14 | Providing and fixing of the tin shed on the existing meter room including dismantling of the existing broken and rusted tin sheds with dimantling the brick work over the existing tin shed and reconstructing the brick work on new tin shed with old bricks etc complete as required |
| 15 | Painting of the existing sub meter panels in the quarters block with the synthetic paint by two coat of red oxide and two coat of paint including cleaning the panel sheet by rubbing with sand paper |
| 16 | Supply and fixing of single phase 230 volt AC supply electronic kWh Energy Meter of rating 10 - 40A, Class 1.0, 240V, 50Hz, LCD type display with Transparent Hinge i/c conections, testing etc. complete as required (Make: HPL or SS make) |
| 17 | Supplying & Fixing of following rating 240/415 volt MCB of single/four pole in the existing MCB DB complete with connection, testing and commissioning etc. as required. ( a ) 6A - 32 Amp. 'C' series SPMCB |
| 18 | ( b ) 40Amp Double Pole MCB |
| 19 | Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit or in sub metering system etc complete as required.( a) 1 X 6 sq.mm as additional wire |
| 20 | ( b ) 1 X 10 sq.mm as additional wire |
| 21 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 22 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. Please Enable Macros to View BoQ information |