| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. a) Group -C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required |
| 3 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 6 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 7 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 8 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 9 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 10 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 12 way , Double Door |
| 12 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single Pole |
| 13 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 40 A |
| 14 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 63 A |
| 15 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 16 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 17 | Supplying of T5, 36W LED Batten Make Crompton LDLSRNX36-CDL/NW/WW, 36W or its equivalent etc., as required. |
| 18 | Supplying of 15W LED Lamp Make Havells CLASSY LED 15W B22 CDL 3 STAR Order Code LHLDEUEEML8R015 or its equivalent etc., as required. |
| 19 | Supplying of10W Bulk Head Fitting similar to Make Crompton Model BLKD-XELLO-10W-CDL/WW, 10W or its equivalent etc., as required. |
| 20 | Supplying of AC Ceiling Fan 1200 mm Sweep (Color: Opal White, Brown) Similar to Crompton Empower ISI marked without Remote with 2 year Warranty and Without regulator i/c wiring down rod of standard length (upto 30 cm) will all accessories or its equivalent etc., as required. |
| 21 | Supplying and Fixing of Stepped Type Electronic Fan Regulator equivalent to Pressfit Glory 5 Step Regulator (Board) Coad-546070 or its equivalent, etc., as required. |
| 22 | Supplying of following size XLPE insulated heavy duty armoured aluminium conductor UG cable of 1.1 KV grade conforming to IS 7098 (Part-I) and IS No:1554 (Part-I) 1988 as applicable Make: CCI/Glooster/ Havells/ Polycab/ Finolex etc as reqd.a) 10 sq.mm x 2 Core |
| 23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Upto 35 sq. mm |
| 24 | Supplying and laying of one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I & II complete with necessary HDPE fitting for protection of 1.1 KV grade following size on wall surface as required.a) 50mm outer dia and 38 mm Inner dia (Clamping with MS Flat Clamp and Screw) |
| 25 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required a) 50 mm dia |
| 26 | Supplying and laying of one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I & II complete with necessary HDPE fitting for protection of 1.1 KV grade directly in ground at the depth of 50 cm i/c excavation and refilling in the trench etc as reqd.a) 50mm outer dia and 38 mm Inner dia |
| 27 | Supplying of following size XLPE insulated heavy duty armoured aluminium conductor UG cable of 1.1 KV grade conforming to IS 7098 (Part-I) and IS No:1554 (Part-I) 1988 as applicable Make: CCI/Glooster/ Havells/ Polycab/ Finolex etc as reqd.a) 16 sq.mm x 4.0 Core |
| 28 | Supplying and laying of one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I & II complete with necessary HDPE fitting for protection of 1.1 KV grade following size on wall surface as required.a) 63mm outer dia and 50 mm Inner dia (Clamping with MS Flat Clamp and Screw) |
| 29 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required a) 80 mm dia |
| 30 | Supplying and laying of one number double walled corrugated high density Polythylene pipe having corrugation on the outer wall and plain surface inner wall confirming to IS 14930 Part -I & II complete with necessary HDPE fitting for protection of 1.1 KV grade directly in ground at the depth of 50 cm i/c excavation and refilling in the trench etc as reqd.a) 63mm outer dia and 50 mm Inner dia |
| 31 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 32 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as requireda) 3 x 2.5 sq. mm |
| 33 | Supplying and Fixing of Street Light Assy 50 Watt (CDL), IP66 rating, Similar to Make Crompton LED Street Light Platina Item Code LDSTRX5OCDL Energy saving LED Street Light with PDC aluminium body and toughened glass and high Power LEDs and Secondary Lenses with IP66 Protection or its equivalent etc., as required. |
| 34 | Fabrication and Supplying of Street Light Pole made up of 65 mm dia 'B' Class ISI mark GI Pipe 6 Mtr long with earth stud and necessary GI reducer / coupling fixed with Street Light Bracket made up of 40mm dia 1.2 mtr long 'B' class GI Pipe ISI marked including bending the pipe to he required shape including SMC box of size 250 x 200 x 105 mm (out side) thick hinged door an locking arrangement properly mounted on 40 x 6 mm MS flat welded on the pole with DIN Channel, 10A MCB DP and 63A rating modular 4 Way connector and 300 x 300 x 6 mm thick M.S Base Plate Welded at the bottom i/c painting with one coat of metallic primer and two coats of synthetic enamel paint, as required as per the direction of the Engineer in Charge. (Foundation 70cm below G/L and 50 cm above G/L). |
| 35 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. a) Above 4.5 metre and upto 6.5 metre Please Enable Macros to View BoQ information |