| 1 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole etc in hard/dense soil |
| 2 | Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil complete all as directed. |
| 3 | Removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as directed. |
| 4 | Supply and laying double walled corrugated HDPE Pipes of size 110 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of cables complete all as specified and directed |
| 5 | Supply and laying double walled corrugated HDPE Pipes of size 40 mm dia as per IS 16205 Anti termite, Anti Rodency and Non flame propagation propety etc for protection of cables complete all as specified and directed |
| 6 | Supply and fix in repair GI Pipe Light grade with all connected accessories of sizes 100 mm dia complete all as specified & directed for cable protection |
| 7 | Taking out the UG XLPE insulated armoured /unarmoured PVC sheathed laid in trenches/ passing through GI tubing /on pole /on wall of any size and type complete all as specified and directed. |
| 8 | Supply and laying,jointing & testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor,1100 volt grade laid in trenches,ducts,drawn through pipes across the road/path/along poles/floors/equipment etc of size 300 sq mm 3.5 core. |
| 9 | All as per above srl item No. 8 here-in-before but of size of cable 150 sqmm 3.5 core |
| 10 | All as per above srl item No. 8 here-in-before but of size of cable 120 sqmm 3.5 core |
| 11 | All as per above srl item No. 8 here-in-before but of size of cable 95 sqmm 3.5 core |
| 12 | All as per above srl item No. 8 here-in-before but of size of cable 70 sqmm 3.5 core |
| 13 | All as per above srl item No. 8 here-in-before but of size of cable 50 sqmm 3.5 core |
| 14 | All as per above srl item No. 8 here-in-before but of size of cable 35 sqmm 3.5 core |
| 15 | All as per above srl item No. 8 here-in-before but of size of cable 25 sqmm 3.5 core |
| 16 | All as per above srl item No. 8 here-in-before but of size of cable 16 sqmm 4.0 core |
| 17 | All as per above srl item No. 8 here-in-before but of size of cable 10 sqmm 4.0 core |
| 18 | All as per above srl item No. 8 here-in-before but of size of cable 16 sqmm 2.0 core |
| 19 | Supply installing, testing and commissioning in replacementof LT Panel of Size 1.8 x 1.5 x 0.5 Mtr outdoor kiosk type factory made of angle iron 65mmx 65mmx 6mm on all side welded to 3.15 mm thick CRCA sheet steel for outer compartment and 2.0 mm thick for inner compartment with openable shutteron both sides ( front and rear) , having locking arrangement totally enclosed weather proof outdoor spray painted internally and externally with two coats of synthetic enamel paint over a coat of primer suitable for 440 volts, 3 phase, 4 wire, 50 Hz with Aluminium bas bar of capacity 800 Amps AC supply, electrically connected as per norms and fitted with following accessories all as specified and directed by the Engr-in Charge. (Note:- LT panel shall be mounted on PCC 1:2:4 type B-1 with 20 mm graded stone aggregate foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC block shall be deemed to be included in the unit rate quoted for the item . The panels shall be of CPRI approved Note:- Drg of panel shall got approved by GE before execution at site. INCOMMER Incoming MCCB, 415V, 4 pole, 400 Amps, 36 KA, Ics =100% IcuIndicator Lamp-01 Set (Set of three)Voltmeter 0-500 Volt , 415V , 50 Hz ,with selector switches -01 setAmmeter 0- 500 Amps with CTs, 415V 50 Hz with selector switches -01 setOUTGOINGMCCB, 415V, 4 pole, 200 Amps, 25 KA -01 No MCCB 4 pole 125 amp, 415V, 36 KA, 4 pole , 02 Nos MCCB 4 pole 63 amp, 415V, 36 KA, 4 pole , 01 Nos MCB SPN 40 Amps , 230V, 50 Hz - 01 Nos |
| 20 | Supply installing, testing and commissioning in replacement of Bus bar junction box panel of Size 0.75 x 0.6 x 0.3 Mtr outdoor kiosk type factory made of angle iron 65mmx 65mmx 6mm on all side welded to 3.15 mm thick CRCA sheet steel for outer compartment and 2.0 mm thick for inner compartment with openable shutteron both sides ( front and rear) , having locking arrangement totally enclosed weather proof outdoor spray painted internally and externally with two coats of synthetic enamel paint over a coat of primer suitable for 440 volts, 3 phase, 4 wire, 50 Hz with Aluminium bas bar of capacity 800 Amps AC supply, electrically connected as per norms and fitted with following accessories all as specified and directed by the Engr-in Charge. (Note:- Bus bar junction box shall be mounted on PCC 1:2:4 type B-1 with 20 mm graded stone aggregate foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC block shall be deemed to be included in the unit rate quoted for the item . Note:- Drg of bus bar junction box panel shall got approved by GE before execution at site. INCOMMER/OUT GOINGIncoming MCCB, 415V, 4 pole, 400 Amps, 36 KA, Ics =100% Icu -01 nosIndicator Lamp-01 Set (Set of three) |
| 21 | M & L for replacement of earthing continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/piope or fixed to poles or any other indicated situation for loop earting etc as required 25x4 mm galvanised iron strip complete all as specified & directed. |
| 22 | Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 3 of SSR Part I of 2009.00 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, I watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 25x4 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified & directed. |
| 23 | M&L for removing LT over head conductor from the insulator where ever required and restretching the same without any kink/bend upto permissible sag,binding it on insulator by means of binding wire and replacing the old jumpers with new jumpers using conductor of the required size and testing the HT/LT overhead line after completion as directed. |
| 24 | S&F in replacement of steel tubular poles complete with cast iron base plate, final taper plug, bolt, nuts & screws as specified type 410 SP-31 ( 9 mtr long ) complete all as specified and directed. Note: Excavation and PCC shall be measured and paid separately . |
| 25 | M&L for Cement concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate in coping padestal to poles including provision of necessary form work finishing the exposed surface even and smooth complete all as specified. |
| 26 | M & L for Cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar 1:3 complete all as specified. |
| 27 | M & L for Cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar 1:3 and applying two coats of white wash to the portion of PCC muffs above ground level complete all as specified. |
| 28 | S&F in repair Aluminium conductor, steel reinforced, of size 6/211 to 6/3010 mm (Squirrel to Ferret) straining properly on insulators with and including aluminium tape/winding wire, clamps & jumpers etc. complete all as specified.Note : 3% for sag shall be added in measurement . |
| 29 | S&F in repair Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending (cold or hot), drilling holes for bolts, bent to any shape or size as directed and inclusive of one primer coat of red oxide, one under coat of zinc oxide and one finishing coat of aluminium paint complete all as specified & directed |
| 30 | S&F in repair pin type porcelain vitreous/ polymer insulator 50 mm height and 65 mm dia for working pressure 550 volts including one galvanised mild steel spindle, two galvanised iron washer and one iron nut complete all as specified & directed. |
| 31 | S&F in repair shackle type porcelain vitreous/ polymer insulator 50 mm height and 65 mm dia for working pressure 550 volts including one galvanised mild steel spindle, two galvanised iron washerand one iron nut complete all as specified & directed. |
| 32 | S&F in repair stay assembly complete with accessories as shown in electrical plate No 1 and diameter of stay rod 16 mmincluding Stay Clamps and PCC (1:3:6) cocreate for foundation of stay assmbly complete all as specified and directed |
| 33 | Taking out the Air circuit breaker (ACB) of capacity 630 A, to 1000 A 415 volts,3 ph, 50 Hz of any make and type from the panel, for repairs/overhauling and servicing including replacement of wornout minor parts and refixing the same site complete all as specified and directed. |
| 34 | Supply and fixing in repair LT line separator suitable for three phase four wire water proof, weather proof, shock proof, Resistant to chemicals , robust construction easy to install low maintenance and fine uniform finish complete all as specified & directed. |
| 35 | Dismantling of old jumper and including supply and fixing of new jumper made out of ACSR conductor 6/3010 mm (ferrit) inserted inside PVC pipe complete (length not exceeding 2 mtr), including testing on completion of the job complete all as specifed and directed. |
| 36 | Deduct Credit for Demolished/Dismantled material Rs (-) 1,38,368.00 (Minus) as listed in Schedule 'A' Part-II (Credit Schedule)Note : Tenderers will not quote against this item being a tentative amount, to be considered to arrive at the 'Contract Sum'. Please Enable Macros to View BoQ information |