| 1 | SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. |
| 2 | Design and Build of tech building for E-MMS three storeyed (G+3) with permanent specifications, including RCC domestic water tank, fire fighting tank of 12600 litres in total at terrace and underground sump cum fire pump house of 50,000 litre capacity, ramp etc complete all as specified and shown on drawings. |
| 3 | Lump sum price worked out by the Contractor for “SITE CLEARANCE, EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II |
| 4 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY WORKS\\" as listed in Schedule ‘A’ Part III |
| 5 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION WORKS\\" as listed in Schedule ‘A’ Part IV |
| 6 | Lump sum price worked out by the Contractor for “ROAD, PATH AND HARDSTANDING WORKS & CULVERT\\" as listed in Schedule ‘A’ Part V |
| 7 | Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY WORKS” as listed in Schedule ‘A’ Part VI |
| 8 | Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL WORKS” as listed in Schedule ‘A’ Part VII |
| 9 | Lump sum price worked out by the Contractor for “AREA DRAINAGE WORKS ” as listed in Schedule ‘A’ Part VIII |
| 10 | Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY WORKS” as listed in Schedule ‘A’ Part IX |
| 11 | Lump sum price worked out by the Contractor for “AIR CONDITIONING WORKS” as listed in Schedule ‘A’ Part X |
| 12 | Lump sum price worked out by the Contractor for “FIRE ALARM & FIRE FIGHTING WORKS\\" as listed in Schedule ‘A’ Part XI |
| 13 | Lump sum price worked out by the Contractor for “DG SET\\" as listed in Schedule ‘A’ Part XII |
| 14 | Lump sum price worked out by the Contractor for “LIGHTENING PROTECTION WORKS\\" as listed in Schedule ‘A’ Part XIII |
| 15 | Lump sum price worked out by the Contractor for “DEMOLITION & DISMANTLING WORKS\\" as listed in Schedule ‘A’ Part XIV |
| 16 | SCHEDULE `A' PART - XV MISC ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. |
| 17 | DEMOLITION OF B/R ITEMS |
| 18 | Taking down flushing cisterns and flushing pips of any description/capacity complete all as specified and directed. |
| 19 | Taking down wash basins vitreous china any size including brackets complete all as specified and directed. |
| 20 | Internal Electric Supply |
| 21 | Supply and fixing of Modular metal flush 8 module complete all as specified and directed. |
| 22 | Supply and fixing of Modular metal flush 12 module complete all as specified and directed. |
| 23 | Supply and fixing of modular cover plate white with frame complete for 12 module complete all as specified and directed. |
| 24 | M & L for VTPN 8 way sheet steel enclouser distribution boards, double door factory made 3 phase 415 volts, 100 A MCCB as incomer and 24 single phase outgoing copper bus bar of suitable size and PVC insulated to the out going circuits,complete all as specified and directed. |
| 25 | M & L for VTPN 4 way sheet steel enclouser distribution boards, double door factory made 3 phase 415 volts, 63 A MCCB as incomer and 12 single phase outgoing copper bus bar of suitable size and PVC insulated to the out going circuits,complete all as specified and directed. |
| 26 | S & F surge protection device intigreated type 2+3 SPN in small module width voltage protection level 1.5 KV complete all as specified and directed.(includng all accessories) |
| 27 | Taking down the TPN DBs any type by necessary cutting, chasses including disconnection of incoming and out going cable etc complete all as specified and directed. |
| 28 | Taking down the SPN DBs by necessary cutting, chasses including disconnection of incoming and out going cable etc ccomplete all as specified and directed. |
| 29 | Taking down the MCBs/MCCBs any type by necessary cutting, chasses including disconnection of incoming and out going cable etc complete all as specified and directed. |
| 30 | Dismantling Tube Light fitting single / double rod/ Ceiling light fitting any type and wattage or CFL fitting of any type and bulk head fitting of any type or wattage complete all as specified and directed. |
| 31 | Disconnecting and taking down unserviceable cable of size 10 Sqmm/ 16 Sqmm/ 25 Sqmm/50 Sqmm from pole/main switch board complete all as specified and directed. |
| 32 | Taking out carefully earthing set complete of any type including earthing wire/strip complete all as specified and directed. |
| 33 | External Electric Supply |
| 34 | Supply, Installation, testing and commissioning of distribution net work, 11 Kv outdoor Compact Sub Station totally factory assembled (non walk in type) consisting of 1 way RMU type, 1 No. 11KV/433V, 315 KVA with oil type transformer, 1 set of LT device as under:-(A) MV COMPARTMENT - 11 KV, 630A, 25KA/1Sec indoor type non-extensible, SF6 gas insulated LBS with sealed pressure system criterion in accordance with the IEC 60298, 62271- 202 IAX category IAC AFL. The Switchgear includes the following HV cubicles:- 01 No Load Break Switch with self powered relay for protection of transormer. Rated for voltage 12KV, rated current for lbs feeder and ring main feeder,630A, rated short time current-25KA for 1 sec. Rated voltage should be - 12 KV, Rated power frequenecy voltage- 28 KV, Rated lightening with stand voltage- 75KV, Rated short time making current- 50 KA, Ambient temp (o deg C to +40 deg C), Rated internal arc rating - 20KA for 1 sec for tank and cable box category IAC-AFL. protection CTs rated for 30/ 1 amp, class-10P10 accuracy, 2.5 VA burdan for ckt breaker. |
| 35 | (B)TRANSFORMER (Oil type) Three phase, Standard : IS:2026, IS 1180, Vector group : Dyn11, Rating : 315KVA, Cooling system: ONAN, Winding : Copper, Magnetic core: Prime grade of M4 or better, High voltage: 11KV-50Hz, System highest voltage: 12kV at the HV side, H.V power frequency (KV rms): 28kV, H.V Impulse withstand voltage (KV peak) : 75kVp, The losses of transformer should be as per IS 1180 part I eff level-2 norms, transformer shall be designed for 110% continous overfluxing withstand capability, Temprature rise as per IS1180, OTI & WTI, Pressure valve (without auxiliary contacts), skids, earthing terminal, lifting lugs, rating plate, Dehydrating breather. |
| 36 | (C) LV COMPARTMENT - The LV compartment with degree of protection IP54 designed for a 50 degree C ambientt temprature. The panel is modular, dead front, freestanding, floor mounted and comprises the following equipement:- 433 V air insulated copper busbar having capacity 1000A, 50Hz,50kA withstand fault level capacity, (a) Incomer - 4 Pole, 630A, Thermal magnetic MCCB with O/c, S/C protection. Ics-50 KA, with Double make & Double break type.(b) Outgoing-320A,4P, Thermal magnetic MCCB with Double make & Double break type 36 kA- 1nos, 200A, 4P,Thermal Magnetic MCCB with Double make & Double break type, 25 KA- 2 no,160A,4P,Thermal Magnetic MCCB with Double make & Double break type, 25 KA- 1 no, 250A, TP,Thermal Magnetic MCCB with Double make & Double break type, 25 KA- 1 no, 63A,4P,MCB,10kA - 1 no, 20A,4P,MCB,10kA - 1 no.(c) APFC Panel-Incomer 1 no MCCB TP Pole 250A ICs=50kA ,Thermal magnetic with Double make and Double break roto mechanism, Intelligent APFC relay with 100 kVAr MPP Heavy duty capacitor with suitable rating of contactors & short circuit protection device for each banking of capacitor should be 5X1 no, 10X2 no,25 x 2 No, 50X1no. |
| 37 | (D) OUTDOOR ENCLOSURE :the enclouser shall be made of 2.0mm thick galvanized sheet steel tropicallsed to meet indian weather condition including all partition sheets and doors.the base shall be 4.00mm thick hot dip galvanized sheet steel to ensure rigidity for easy transport and installation. The entire package substation shall be factory assemble & factory fitted. The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment IP34 degree of protection for Transformer compartment. The enclosure to be tested for internal Arc fault test to the tune of atleast 20KA for 1 second adhering to as per latest IEC 62271-202. The enclosure exterior shall be powder coated. The compartmernt ilumination lamp with door operated switch shall be provided for MV & LV compartment. the enclosure , RMU, LV breaker should be of same make for better coordination and services. |
| 38 | Supply of 11 KV extensible outdoor duty (IP 54 enclosure) SF6 gas insulated 3 way motor operated Ring main unit comprising of 1 No 630 AMPs Vacuum circuit Breaker as incomer and 2 Nos 630 AMPs load break switch as outgoing, cable termination from the front, breaking capcity 21 KA/3sec (internal Arc classification AFLR 21KA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in robotically welded stainless steel tank having IP67 Degree of protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed.The outer enclosure shall IP 54 protection, it should be Top Opening Canopy type.temp and climate sensor,earth switch with its own making capacity independent of breaker with own snap action mechanism, power relay shall be for 3 o/c + 1E/F(idmt type) self powered.other details: nominal system voltage- 11kv, voltage regulation on supply side- ±10%, corresponding highest system voltage- 12kv, freq- 50 Hz with ± 3% tolerance, transient condn- -20% or +10% combined variation of voltage and freq, no of phase: 3 phase, neutral earthing- solidly earthed, fault level(min) - 21/3 KA/Sec, lightning impulse withstand voltage(kVp)- 75, one min dry/wet poder frequency withstand voltage primary(KV rms)- 28KV, rated dynamic withstand current( KAp)- 52.5KA, |
| 39 | no of short circuit operations at rated circuit current of 21KA for breaker- 50 nos, earth switch with its own making capacity indpendent of breaker with own snap action mechanism for fast closing independent of operator action(E2 class). Applicable standards for this RMU scope of work- IEC 62271-200, The RMUs shall confirm to the latest applicable , IE 62271-200, IEC 62271-200, All live parts, bus bars, shall preferably be enclosed in non-magnetic and non-ferrite grade stainless steel tank grade SS304 of min 2.5 mm thickness , the RMU shall be type tested for internal arc test of 21KA/1sec AFLR with bottom exhaust for safety of personnel for both tank as well as cable compartment as per IEC62271-200, the outer encloser shall have IP55 protection for complete switchgears, however it should be top opening canopy & indoor RMU placed inside outdoor enclosure should not be acceptable, the protection relay shall be for 3 O/C + 1E/F( IDMT TYPE) self powered numerical protection relay with low and high set of over current and earth fault, MODBUS,communication along with RS 485 port/ USB port, internal arc classification should be with bottom exhaust only, RMUs should be manufactured, inspected and invoiced from the OEM factory, temp & climate change sensor in each panel, wireless & self powered temp sensor should be mounted in busbar, breaker chamber and the same data should display on the panel.Note: - RMU and LV breaker shall be of same make. |
| 40 | Supply and fixing LED building security light fitting 25 watt 230V AC outdoor type aluminium material, IP65 ,complete all as specified and directed by Engr- In- Charge. |
| 41 | Supply and Fix UPS for 30 min back up three phase AC supply, output 415 V + 1% of capacity 10 KVA complete all as specified and directed. |
| 42 | Dismantling existing old unserviceable LT panel complete all as specified and directed by Engr- In- Charge. |
| 43 | Taking down the old MCCBs any type by necessary cutting, chasses including disconnection of incoming and out going cable etc complete all as specified and directed by Engr- In- Charge. |
| 44 | Disconnecting and taking down unserviceable cable of size 50/95 Sqmm from pole/main switch board complete all as specified and directed by Engr- In- Charge. |
| 45 | Taking out carefully earthing set complete of any type including earthing wire/stripcomplete all as specified and directed by Engr- In- Charge. |
| 46 | External water supply |
| 47 | Supply and lay pipe ductile Iron (DI), \\" medium class\\" including fitting of size 100 mm dia complete all specified and directed. |
| 48 | M&L construction of valve chamber of size 900x900x1200mm (internal size) suitable for valves with PCC 1:4:8 type D 2 for foundation and brick masonry wall in cement mortar 1:6 PCC 1:3:6 type C 1 for coping rendering in CM (1:4) 15mm thick including Provn of mild steel sheet cover 3.0mm thick on 40x40x6mm angle iron frame work with two coats of synthetic enamel black paint over a coat of red oxide primer and locking arrangement including necessary excavation earth work in any type of soil complete all as specified and directed. |
| 49 | Supply and fix centrifugal, mono block pumping set of capacity 5 HP upto 36 mtr head, with a discharge rate of 480 LPM electric driven, 415V 50Hz inclusive of Star delta starter and PCC foundation complete all as specified and directed. |
| 50 | Supply and fix CI foot valve confirming to IS 4038 of size 50mm dia complete all as specified and directed. |
| 51 | Supply and fix CI reflux valve with by pass arrangement complete of size 50mm dia complete all as specified and directed. |
| 52 | Supply and fix MS strainer Y type of size 50mm dia complete all as specified and directed. |
| 53 | AIR CONDITIONING WORK |
| 54 | Dismantling and re- fixing of air cooled split air conditioner, electric driven, single phase of capacity 1.5 TR all as specified and directed.( AC's are submitted to MES storeyard and will be refixed according to user requirements) |
| 55 | Supply and fixing of copper pipe line of size 1/2\\" for Suction line of 1.5 Tr split AC complete with insulation and connecting accessories complete all as specified and directed. |
| 56 | Supply and fixing of copper pipe line of size 5/8\\" for Suction line of 2.0 Tr split AC complete with insulation and connecting accessories complete all as specified and directed. |
| 57 | Supply and fixing of copper pipe line of size 1/4\\" for Liquid line of 1.5 & 2.0 TR split AC complete with insulation and connecting accessories complete all as specified and directed. |
| 58 | Supply and fixing of Metal stand for outdoor unit of split AC with connecting accessories complete all as specified and directed. |
| 59 | S & F PVC drain pipe for split AC including of connection with existing drain pipe and fixing on wall complete all as specified and directed. |
| 60 | FIRE FIGHTING & DETECTION ALARM |
| 61 | Supply and fix MS flanged pipe 100 mm , NB heavy duty for multi stories building duly painted with 2 coats of synthetic enamel paint a over coat of zinc chromate primer complete all as specified and directed. |
| 62 | Supply & fix hose reel of 20 mm dia and 30 m length conforming to IS 5132 complete all as specified and directed. |
| 63 | Supply & fix branch pipe and nozzle for 20 mm dia hose reel conforming to IS 8090 complete all as specified and directed. |
| 64 | Supply and fix of Talk back system complete all as specified and directed by Engr- In Charge. |
| 65 | Supplying, installing, testing & commissioning of 2x 1.5 sq mm unarmoured PVC insulated FRLS copper conductor cable complete all as specified and directed. |
| 66 | M& L for self luminous sign's board for ' Fire Exit ' fixed on each floor |
| 67 | M & L for self luminous sign's board in case of Fire 'Use Stair case, Do Not Use Lift' |
| 68 | Supply installtion testing and commissioning of Active Repeater Panel with Annunciation repeaters : Supply of Panel with 320 Alpha numeric Characters on LCD display/ or Touch Screen LCD sitting as Network Node on the Main Network Peer-Peer Topology , shall be able to work with all functionality of Main Panel having Reset / Alarm Silence and Acknowledgement Buttons . On the Active Repeater over Serial Interface or Network there shall be Annuciation Panels as well for all Control stations. Individual Active Repeater shall be able to take care of upto minimum 16 nos Annunciation LCD Indicator Panels . Approval Standards : VdS / EN |
| 69 | Supply and fix MS flanged pipe 25 mm , NB heavy duty for multi stories building duly painted with 2 coats of synthetic enamel paint a over coat of zinc chromate primer complete all as specified and directed. |
| 70 | Supply and fix reflux valve (NRV) with by pass arrengement of size 100mm dia complete all as specified and directed. |
| 71 | Supply and fix strainer Y type of size 100mm dia complete all as specified and directed. |
| 72 | Supply and fix MS flanged pipe 150 mm , NB heavy duty for multi stories building duly painted with 2 coats of synthetic enamel paint a over coat of zinc chromate primer complete all as specified and directed. |
| 73 | Supply and fix Air relese valve 25mm dia , bronze open discharge screwed spring loaded complete all as specified and directed. |
| 74 | Supply and fix Pressure relese valve 25mm dia , bronze open discharge screwed spring loaded complete all as specified and directed. |
| 75 | Supply and fix rubber expansion bellow for fire pump complete with flanged at both end with nout bolt complete all as secified and directed. |
| 76 | Supply, install and testing of fire supression system clean agent type of capacity 05 Kg , including clean agent cylinder, automatic control unit and tubing complete set all as specified and directed.( all supression systems will be connected to all panels and server cabinates) |
| 77 | Supply , install ,test & commission of LT Panel of suitable size of indoor, Cubicle type, factory fabricated out of MS Sheet of 2.0 mm thick dust, vermin proof, weather proof, IP-54 Grade of protection, fabricated on 50x50x5 mm thick MS angle iron frame both side opening and locking arrangement including providing copper bus bar of capacity 100 Amps rating for 415 V 50 Hz 3 Phase system including with RYB colours and suitable adopter boxes with spreader links for connecting cables with switch terminals (Where necessary) complete with following:-. (Fire Panel) |
| 78 | INCOMING:(a) MCCB 320 Amps 4 pole 16 KA - 01 Nos (b) Voltmeter 0-500 volt - 01 Nos (c) Amperemeter 0-200 Amp - 01 Nos (d) LED Indicator Lamp set - 01 NosOUT GOING:(a ) MCB 4 pole, 30 A , 10 KA( Elect fire pump- 01 nos)(b ) MCB 4 pole, 10 A , 10 KA ( jockey pump- 01 nos & Centrifugal pump-01 Nos)-02 Nos(c ) MCB SPN 10 A, 10KA, C curve - 1 No (Room light) |
| 79 | supply, install, test, commission of 5 kg UL approved Grenoz 1230 gas as an extinguisher agent of the area coverage 3x3m at the operating pressure 8 bar with the working temp rating -30deg to +60deg; ceiling mounted clean agent all as specified and directed.(for UPS/ server room) |
| 80 | Supply and fix MS flanged pipe 63mm, NB heavy duty for multi stories building duly painted with 2 coast of synthetic enamel paint a over coat of zinc chromate primer complete all as specified and directed. |
| 81 | LIFT WORK |
| 82 | Design supply, install testing & commissioning 13 passengers lift, 884 kg, speed (1-1.5)mt/sec, lift with single speed motor 415 volts, 3 phase, AC 50 Hz supply , suitable to serve G+ 03 upper floors complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, VF generator drive (closed loop),centre opening doors with door drive (electric motor driven mechanism),PM gearless machine,full collective operation,4 stops( opening on same side),one car simplex,flat coated steel belt, DC operator door,sliding stainless steel doors, Controller type LVA/ACD,(11-15mt) rise,CD61 type false ceiling,fire rating 60 mins, aluminium chequered plate flooring,pit depth-1600, overhead-4500, hoistway dim: 1800mm (W)* 2265mm (D), car dim: 1100mm (W)*2000mm (D)*2200mm (D),O2000 hall fixures, automatic rescue device (ARD) system,hall button with HPI,anti-nuisance car call protection, infrared curtain door protection,intercom, independent service( for duplex only), overload device, nudging, emergency firemens service, emergency car light unit, emergency alarm button, extra door time of lobby & parking, manual rescue op, belt inspection drive, auto fan cut off (G+ 3 Bldg Passenger cum fire lift -01 Nos ). |
| 83 | Supply , install test & commission of LT Panel of suitable size of indoor, Cubicle type, factory fabricated out of MS Sheet of 2.0 mm thick dust, vermin proof, weather proof, IP-54 Grade of protection, fabricated on 50x50x5 mm thick MS angle iron frame both side opening and locking arrangement including providing copper bus bar of capacity 100 Amps rating for 415 V 50 Hz 3 Phase system including with RYB colours and suitable adopter boxes with spreader links for connecting cables with switch terminals (Where necessary) complete with following:-. (Lift room panel ) |
| 84 | INCOMING:(a) MCB 40 Amps 4 pole 10 KA - 01 Nos(b) Voltmeter 0-500 volt - 01 Nos(c) Amperemeter 0-200 Amp - 01 Nos(d) LED Indicator lamp - 01 NosOUT GOING:(a) RCCB 4 pole, 30 A , 10 KA (Lift 13P- 01 nos)(b) MCB SPN 10 A, 10KA, C curve - 1 No (Room light)(c) MCB TPN 10 A, 10 KA (terrace pump) |
| 85 | DG SET |
| 86 | Supply, installation, testing and commissioning of diesel engine driven Gen set of 200KVA capacity, of Mahindra model H6725G4, or equivalent model of approved make, 6 cylinder, single phase liquid cooled, turbo charged developing 247 HP. This is electric start, compressed ignition, 4 stroke engine design to run continuously at 1500rpm. The diesel engine comprise of following- radiator with fan, electric starter motor with sift starting system, G2 as per ISO 8528 part 5 class governor, battery charging alternator, dry type air cleaner with service indicator, 1*12V DC battery, lube oil& fuel filter, first fill of lube oil & coolant.compact size with manual/ automatic starting system, sound proof , weather proof enclosure, low vibration, best in class fuel consumption, class G2 governing in its range, which gives better accuracy in decreasing the speed drop in transient and lowering the recovery time of the speed, low cost of service and spark, confirm to statutory govt. CPCB NORM 4+ emission & noise level norms, the enclosure is of modular construction with the provision to asemble and dismantle easily, the sheet metal components are 11 tanks pre treated and is polyester based powder coated |
| 87 | coated (inside as well as outside), all nuts-bolts, hardware are of stainless steel, battery is provided in tray inside the enclosure, doors are gaskeled with light quality EPDN gaskets to avoid leakage of sound, a special residentail silencer is provided to control exhaust noise, specially designed sound attenuators are there to control sound at air entry & exit points inside the enclosure, to make the system vibration free, engine and alternator are mounted on specially desinged anti-vibration pads mounted on base frame. the enclosure is designed and layout of the equipments is such that there is easy access to all serviceable parts, adequate ventilation is provided to meet air requirments for combustion & heat removal. Safety featurtes: high water temp, low lube pressure, emergency stop push button outside the enclosure, EGR, cold start feature(optional), standard control panel mounted inside enclosure, in built draw in type fuel tank of suitable capacity, with UV resistant powder coating , the walls of enclosure are insulated with the fire- retardant & noise absorbent foam/ rockwool so as to comply with the noise level of 75dB at a distance of 1mt, in open free field environment as per ISO 8528 part10 specified by ministry of environment & forest, fluid frains for lube and fuel. |
| 88 | Alternator: alternator suitable for continuous operation rated at 1500 RPM 415V, .85pf, 50Hz, ph. In SPDP enclosure, self excited, self regulated brush less, floor mounted. The alternator conforms to IS 4722, BS EN 60034-1 &will be suitable for tropical conditions. Acoustic enclosure: the enclosure is of modular, durable industrial locking system is provided on doors, the sheet metal components are 9 tanks pre treated and is polyester based powder coated (inside as well as outside), specially designed sound attenuators are there to control sound at air entry & exit points inside the enclosure,in built draw in type fuel tank of suitable capacity the walls of enclosure are insulated with the fire- retardant & noise absorbant foam/ rockwool so as to comply with the noise level of 75dB at dist of 1mt, in open free field environment as per ISO 8528 part10 specified by ministry of environment & forest, fluid frains for lube and fuel. DG control panel with genset controller: control panel is 16/18 gauge CRCA sheet and is powder coated for weather proof , panel consistes of Microprocessor based genset controller, MCCB , key switch, push button, led:battery charging alternator fail indication, current transformer, instrument fuses. |
| 89 | Supply , installation, testing & commission of LT Panel of suitable size out door, Cubicle type, factory fabricated out of MS Sheet of 3.0 mm thick dust, vermin proof, weather proof, IP-54 Grade of protection, fabricated on 50x50x5 mm thick MS angle iron frame both side opening and locking arrangement including providing Aluminium bus bar of capacity 500 Amps rating for 415 V 50 Hz 3 Phase system including interconnection with Solid conductor/Strips/Wires/Cables with hot shrink color coded sleeves with RYB colours and suitable adopter boxes with spreader links for connecting cables with switch terminals (Where necessary) complete with following( Main DG Panel) |
| 90 | INCOMING:(a) MCCB 320 Amps 4 pole 25 KA - 01 Nos(b) Voltmeter 0-500 volt - 01 Nos(c) Amperemeter 0-200 Amp - 01 Nos (d) LED Indicator Lamp set - 01 NosOUT GOING:(a) MCB SPN 20A, 10KA ( Fire Alarm Panel-01) -01(b) MCB TPN 40 Amps 4 pole 10 KA, C curve (Lift Room-01)(c) MCCB 63 Amps 4 pole 16 KA ( First floor server Room-01)(d) MCCB 100 Amps 4 pole 16 KA ( 2nd floor - 01, 3rd floor-01) -02 |
| 91 | Shifting of existing stand by DG set of 160 KVA to specified location including suitable steel frame with PCC foundation of suitable size and bracing bolt at new location complete all as specified and directed. |
| 92 | M & L for vertical type sheet steel enclosure distribution boards, double door factory made 3 phase, 415 volts, 4 way, with 200 amps rated copper bus bar of suitable size and PVC insulated copper jumpers from the MCCB to the out going circuits (one incoming MCCB and 12 outgoing MCBs circuits) comprising of 3 phase 4 wire of suitable rating including MCCB 63 amps, 25 KA, TP, 415 volts, 50 Hz = 01 No. and 12 Nos MCBs 40 Amps, complete all as specified and directed. |
| 93 | LIGHTENING PROTECTION |
| 94 | S&F epoxy base insulators of suitable size 40mm height for fixing GI/aluminium earth strip on wall/ceiling/floor/poles etc complete all as specified and directed by Engr-in- Charge Please Enable Macros to View BoQ information |