| 1 | (a) Day to day attending complaints & maintaining the electric supply GE NAMS Area round the clock (24 Hours) comprising the following electrical distribution net work / transformers / LT panels by contractor/his rep with fwg networks:-(i) Feeder No-1 emanating from MRS to TOP II, Appx length – 4.5 Km.(ii) Feeder No-2 emanating from MRS to NME, Appx length = 1.8 Km, LT Panels , LT overhead lines appx – 2.50 km and 01 No transformer. (iii) Feeder No 03 emanating from TOP I Sub station to Old Officer colony Feeder, Appx length = 3 Km along with 08 transformers with GOD s of different capacities , LT Panels , LT overhead lines appx – 4.5 km. (iv) Feeder No 04 emanating from TOP I Sub station to Back Feeder Appx length = 3 Km along Complete upto end point.(v) Feeder No 05 emanating from TOP II Sub station to Old Kathania Accn Appx length = 2 Km complete upto end point(vi) Feeder No 6 emanating from TOP II Sub station to Back Feeder to Army school, central school Appx length = 3.5 Km complete upto end point(vii) Feeder No 7 emanating from TOP II Sub station to units area - Approx 3.5 Km Complete upto end point.(Viii) Feeder No 8 emanating from TOP II Sub station to NOC II, Appx length = 1 Km complete upto end points(ix) Feeder No 9 emanating from TOP II Sub station to CP -6 baffle range Appx length = 4 Km complete upto end points.(x) Feeder No 10 emanating from 66 KV Sub station to New Red Colony, New Kathania & NOC-I Appx length = 2.5 Km complete upto end points. (Preodicity - round the clock) (b) Nature of work to be done (i) Maintaining the serviceability and attending break down complaints of electric supply of all the feeder including of New ASR Cantt area mentioned under Sl 1.0(i) to 1(x) here in before .(ii) Attending the complaint of external electric supply – from sub station to main board / DB of the occupant.(iii) Periodical maintenance/complaints of all the feeders mentioned here-in-before related to loose connection/no lights in the area and other faults not covered in items mentioned in BOQ here in after. |
| 2 | (iv) Complaint to be attended within 1 to 2 hrs otherwise penalty to be made at @ Rs. 500/- per complaint.(v) Complaint Register , complaint slip and log book shall be provide by the contractor wihout any extra cost paid to him and maintained by the SBA on duty/ Contractor rep present at Complaint cell in supervison of JE EM and signature of JE / Engr in charge will be taken on each complaint after completion of complaint on daily basis.(vi) All necessary tools & ladders etc to be provided by contractor without any extra cost. Note – (i) Time consuming jobs such as replacement of defective cable by extension of loop and periodical trimming of trees / branches along the over head lines shall be measured and paid separately under respective items.(ii) Before attending any complaints of external elect supply contractor or his rep shall ensure that proper shut down has been taken in physical presense on permit slip and will be lifted on the same permit by the physical reporting at Sub station with proper time and signature.(iii) No shut down given/ lifted on mobile phone. Shut down shall be given / lifted only after physical reporting of electrician at power house(iv) All safety precaution will be taken by the Contractor/his rep. incase of any physical injury / any mishappning contractor will be responsible for all the medical treatment and compansation to the individual . No extra cost paid to the contractor for the same.(v) Contractor will provide shut down permit book for taking shut down permit from the JE/ Engr-in-Charge on duty. No extra cost will be paid for the same.(vi) Contractor has to deposit all the stores in advance for attending day to day complaints and late hours complaints.(vii) Tinned copper fuse wire and self adhesive insulation tapes to be used in complaints shall be measured and paid seperately under respective items. |
| 3 | Excavation in trenches n .exc 1.5 mtr wide and not exec 1.5 mtr in depth for foundation etc or for laying pipe lines and cables and getting out as in looses/soft soil complete all as specified and directed. |
| 4 | Returning filling in including spreading leveling, watering and well ramming in layer not exe. 25 cm in soft/ loose soil, complete all as specified and directed. |
| 5 | Removing excavated material to a distance not exc 50m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed. |
| 6 | Supply,laying & fixing double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps as size of DWC pipe is 50mm outer dia and 63 mm Inner dia complete all as specified and directed. |
| 7 | All as per srl item No 5.00 here-in-before but of size 63mm outer dia and 50mm inner dia complete all as specified and directed. |
| 8 | All as per srl item No 5.00 here-in-before but of size 90mm outer dia and 76mm inner dia complete all as specified and directed. |
| 9 | M&L for in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured heavy duty electric power cable 1100 volts with stranded aluminium conductor of size 240 Sqmm 3.5 core laid in trenches or under road complete all as specified and as directed. Note: Excavation, cable protection work will be measure & paid separately. |
| 10 | All as per serial item No 8.00 here-in- before but of size 120 Sqmm 3.5 core complete all as specified and directed. |
| 11 | All as per serial item No 8.00 here-in- before but of size 95 Sqmm 3.5 core complete all as specified and directed. |
| 12 | All as per serial item No 8.00 here-in- before but of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 13 | All as per serial item No 8.00 here-in- before but of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 14 | All as per serial item No 8.00 here-in- before but of size 25 Sqmm 3.5 core complete all as specified and directed. |
| 15 | All as per serial item No 8.00 here-in- before but of size 16 Sqmm 3.5 core complete all as specified and directed. |
| 16 | Excavating and relaying cables LT loops near the poles LT Panels transformers, cutting the damages/burnt parts of cable and reconnecting its into positions complete with thimbles, nut bolts, sleaves complete all as specified and directed. |
| 17 | Excavating and relaying high tension cables loops near the poles , transformers, cutting the damages/burnt parts of cable and reconnecting its into positions complete with thimbles, nut bolts, sleaves complete all as specified and directed. |
| 18 | Replacement of pin type porcelain white, brown or green insulator including one galvanized mild steel spindle, two galvanised iron washers & one galvanised nut 100mm height, 65mm dia for working pressure 1100 volts grade complete all as specified and directed. |
| 19 | S & F in shackle type,vitreous Insulator incl one galvanised mild steel spindle, two galvanised iron washerrs and one galvanised iron nut, 100 mm height, 115 mm dia ,suitable for 1100 Volt complete all as specified and directed. |
| 20 | Supply and spraying anti vegetation chemical liquid of 1ltrs bottle mixed with water (water to be measured seperately) complete all as specified and directed. |
| 21 | Supply and fixing in replacement of male female contacts of gang operative switch made out of brass and rated capacity 200 amps ,make matching with the existing switch complete all as specified and directed . |
| 22 | M&L for CRC 226 (500 ml) grease/Liquied suitable for VCB mechanism and air break switches complete all as specified and as directed by Engr-in-Charge. |
| 23 | Taking out carefully manually by excavation of existing HT/LT cable of any size upto transfromer with loops and relaying with old retrieved cable cover complete the same after repair of cutting the damages / burnt parts of cable and reconnecting it into original positions complete with cable joints complete all as specified and directed. Note: (i) Unit rate shall include in excavation and returning filling. (ii) Cable joint shall be measrued and paid seprately. |
| 24 | Taking out carefully manually by excavation / Pulling of cable with rope of existing LT cable of size 10 Sqmm to 95 Sqmm with loops and relaying with existing DWC pipe repair/ cutting the damages / burnt parts of cable and reconnecting into original positions complete with cable joints complete all as specified and directed..Note: (i) LT Cable Joint will be measured and paid sepearetly. (ii) Unit rate shall include for excavation and returning filling. |
| 25 | Taking out carefully manually by excavation / Pulling of cable with rope of existing LT cable of size 120 Sqmm to 240 Sqmm with loops and relaying with existing DWC pipe repair/ cutting the damages / burnt parts of cable and reconnecting into original positions complete with cable joints complete all as specified and directed..Note: (i) LT Cable Joint will be measured and paid sepearetly. (ii) Unit rate shall include for excavation and returning filling. |
| 26 | Labour for cleaning away all grass vegetation, scaling shrubs bushes under growth roots and trees not exceeding 30cm girth and removing rubbish aroung LT Panel, transformer, sub stations, LT Poles, under over head lines complete all as specified and as directed. |
| 27 | S&F in replacement for heat shrinkable straight through joint for LT PVC/XLPE insulated armoured cable of size 50 Sqmm 3.5/4 core complete all as specified and as directed. |
| 28 | All as per serial item No 26.00 above but LT cable size of 95 to 120 Sqmm complete all as specified and directed. |
| 29 | All as per serial item No 26.00 above but LT cable size of 150 to 185 sqmm complete all as specified and directed. |
| 30 | All as per serial item No 26.00 above but LT cable size of 240 to 300 sqmm complete all as specified and directed. |
| 31 | M&L for replacement of LT/ HT bush Rod assembly suitable for indoor / outdoor type 315 to 630 KVA transformer complete with brass stud, brass nuts, brass cup and packing gasket complete all as specified and directed.. |
| 32 | All as per Srl item No 30.00 here-in-before but suitable for 100 to 250 KVA transformer complete all as specified and directed. |
| 33 | Supply and Fix high grade PVC LT overhead phase to phase line spacer suitable for 4 lines/wires, suitable for verticale and horizontal line complete all as specified and as directed. |
| 34 | S&F in replacement HT Jumpers wire not less than 95 Sqmm HT single core from top disc insulator to GOD and disc to disc in any lenth with complete nuts & thimbles all as required at site. |
| 35 | M&L for in replacement of aluminium cable lugs/thimbles long barrel type of suitable for XLPE armoured heavy duty electric power cable 1100 volts aluminium conductor of size 25 Sqmm 3.5/4 core bolt dia M14 including jointing/crimping and testing complete all as specified and as directed. |
| 36 | All as per serial item No 34.00 here-in- before but of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 37 | All as per serial item No 34.00 here-in- before but of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 38 | All as per serial item No 34.00 here-in- before but of size 70 Sqmm 3.5 core and bolt dia M16 complete all as specified and directed. |
| 39 | All as per serial item No 34.00 here-in- before but of size 90 Sqmm 3.5 core and bolt dia M16 complete all as specified and directed. |
| 40 | All as per serial item No 34.00 here-in- before but of size 120 Sqmm 3.5 core and bolt dia M16 complete all as specified and directed. |
| 41 | All as per serial item No 34.00 here-in- before but of size 150 Sqmm 3.5 core and bolt dia M20 complete all as specified and directed. |
| 42 | All as per serial item No 34.00 here-in- before but of size 185 Sqmm 3.5 core and bolt dia M20 complete all as specified and directed. |
| 43 | All as per serial item No 34.00 here-in- before but of size 240 Sqmm 3.5 core and bolt dia M20 complete all as specified and directed. |
| 44 | All as per serial item No 34.00 here-in- before but of size 300 Sqmm 3.5 core and bolt dia M20 complete all as specified and directed. |
| 45 | Supply and laying or fixing in replacement 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 10 Sqmm cable standard conductor cable flat or circular complete all as specified and directed. |
| 46 | Supply and laying or fixing in replacement 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 16 Sqmm cable standard conductor cable flat or circular all as complete all as specified and directed. |
| 47 | M&L for earthing complete with galvanized iron or steel plate electrode 600 mm x 600 mm x 6.00 mm thick buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized wire 4 mm dia as earthing lead by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 20 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2010 Part I and including necessary excavation and earth work in any type of soil, 20mm bore light grade GI pipe for watering, funnel, wire mesh, PCC (1:3:6) type C-1 chamber, MS cover of thickness 5mm openable type and having suitable locking arrangement and MS frame of suitable size made of angle iron 50 x 50 x 60 mm, complete all as specified. Note: (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth. |
| 48 | M&L for earthing complete with galvanized iron or steel plate electrode 600 mm x 600 mm x 6.00 mm thick buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 25x3 mm dia as earthing lead by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2010 Part I and including necessary excavation and earth work in any type of soil, 20mm bore light grade GI pipe for watering, funnel, wire mesh, PCC (1:3:6) type C-1 chamber, MS cover of thickness 5mm openable type and having suitable locking arrangement and MS frame of suitable size made of angle iron 50 x 50 x 60 mm, complete all as specified. Note: (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth. |
| 49 | S & F in replacement of MCCB four pole 100 Amps with breaking capacity 16KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed & MCCB matching with the existing slots complete all as specified and directed. |
| 50 | All as per ser item No 48.00 above but 160 Amps with breaking capacity 25 KA complete all as specified and directed. |
| 51 | S & F in replacement of MCCB four pole 250 Amps with breaking capacity 36 KA , 415 Volts, adjustable thermal & fixed magnetic release Ics=100% including making all incoming/ outgoing connections fixed & MCCB matching with the existing slots complete all as specified and directed. |
| 52 | All as per ser item No 50.00 but 315 Amps with breaking capacity 36 KA complete all as specified and directed. |
| 53 | S & F in replacement of MCCB four pole 400 Amps with breaking capacity 35/36 KA , 415 Volts, Microprocessor release Ics=100% inbuilt adjustable overload, short circuit, ground fault including, spreader terminal including all incoming/ outgoing connections fixed & MCCB matching with the existing slots complete all as specified and directed. |
| 54 | All as per ser item No 52.00 but 600 Amps with breaking capacity 36 KA complete all as specified and directed. |
| 55 | M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white , with numeric, letters in \hindi ,English and including local language and conventional skull and bones in signal red and fixed with MS Clamps , bolts and nuts of approved size for LT , 20x 15 cm complete all as specified and as directed. |
| 56 | Material & labour for painting of PCC LT poles with two coats of synthetic enamel paint in black and white strip 30 cm wide each up to 1.5 mtr height from coping including writing of pole number with white paint inside black circle of 10 cm dia complete all as specified and directed. |
| 57 | Supply and laying GI steel tubing, 80mm bore, light grade with all fittings, laid in trenches / under roads / along pole / wall for protection of Cable / GI wire / GI strip etc complete all as specified and directed. |
| 58 | Supply and laying GI steel tubing, 100mm bore, light grade with all fittings, laid in trenches / under roads / along pole / wall for protection of Cable / GI wire / GI strip etc complete all as specified and directed. |
| 59 | M&L of tinned copper fuse wire 22 SWG to 35 SWG 5 Ampere to 24 Ampere (14 sizes ), each roll weight from 125 to 150 gm , sutable for fuse wire complete all as specified and as directed. |
| 60 | M&L for medium voltage fire resistant high quality PVC self adhesive electrical insulaion tape (Red, Yellow, Blue & Black) high quality size minimum 18mm width and 7 mtr long complete use in respect of Item No 1.00 above complete all as specified & directed. |
| 61 | M&L for high voltage fire resistant, flame retardant self adhesive electrical insulaion tape suitble for 11KV (RYB), high quality self melgamate size minimum 38mm width and 09 mtr length use inrsspect of Item No 1 above complete all as specified & directed by Engr-in-charge. |
| 62 | Supply and fill up transformer oil topping up having dielectric strength not less than 60 KV at 4 mm gap conforming to IS complete all as specified and directed. |
| 63 | M&L for discharge Rod 11KV 15 feet long Rod round type FRP material, push button type locking system Top diameter 25mm and bottom diameter 45 mm single phase HV test 110KV clamp type total 3 nos section type conforming to as per IS complete all as specified and directed. |
| 64 | M&L for replacement of Existing Unserviceable LT feeder pillar box out door type double door and single shutter front open including locking arrangement system made out of MS sheet of 3.15 mm CRCA sheet of size 0.9x0.9x0.6 mtr and double door,canopy,dust proof, bottom cable entry plate and gland for cable size150/120/95/70/50/25/16/10 sqmm 3.5 core suitable MS angle iron 50x50x6 mm with aluminium busbar size 400Amps with Incoming MCCB 250 Amp 4 pole system mounted on hygroscopic insulators bus bar including suitable nut, Bolt and Washer(16 Nos) , & including powder coated paint with and providing necessary foundation/plateform of the feeder pillar legs size 40cm below the ground and 60 cm above the ground complete from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland, thimbling for old / new cables as per site requirement and proper finshing as per existing surface complete all as specified and directed by Engr- in- Charge. Note: Drawing for LT feeder piller box shall be got approved from GE before fabrication consisting of following:-(i) Incoming : MCCB 04 Pole 26 KA, 200 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 01 Nos) (ii) Aluminium bus bar suitable size 3 phase, 4 wire 400 Amp,415 V, duly insulated - set of 4(iii) Digital Volt meter 0-500V with slector switch.(iv) Digital Amp meter 0-400 amp with CT and selector switch. (v) Indicating lamp (RYB)LED Type - set of 3 |
| 65 | M & L for in replacement of Hydraulic Crimping tool kits heavy duty type capacity of 16 -400 sqmm cable lugs/terminal/connector (Aluminium & Copper) crimping with 12-14 sets of diffrent size of Hexagone type Die size including all accessories complete all as specified and directed. |
| 66 | Supply & fixing GI earth strip continuity conductor on main earthing lead fixed to Panel/pole or buried in ground or at any other situation for loop earthing extra as required (beyond 7.5 M) of GI Strip 25x3 mm complete all as specified and directed. |
| 67 | M&L for Boring of holes under road, pavement, hard standing by trenchless ultra sound technology/mannual all as per site requirment complete all as specified & directed. Please Enable Macros to View BoQ information |