| 1 | BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER, UDHAMPUR Name of Work: PROVN OF NEW TRANSFORMER AND CONNECTING NETWORK FOR CT SCANNER UNDER GE (UTILITIES) UDHAMPUR Contract No: CWE/U(U)-09/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply, laying, jointing & testing XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 11000 volts grade cross sectional area 120 Sqmm 3 core laind in trenches or passing through pipe or fixed on poles complete all as specefied and directed. |
| 3 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specefied and directed. |
| 4 | Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specefied and directed. |
| 5 | Supply & fixing switch air break gang operated, vertical type triple pole, mechanically operated, mounted on insulator and steel frame with operating machanism worked from ground level using heavy duty GI pipe, for current rating 200 Amp, outdoor type (conforming to IS specifications) HT 11 KV, triple pole with fixed contacts of phosphorous and bronze and a set of drop out HT fuse assembly, fuse carrier fitting, 12 insulator type mounted on MS channel operating rod with pad lock arrangement complete all as specified. |
| 6 | Supply, installation, Connecting, Testing and Commissioning of Oil Cooled, Copper wound (Purity of copper 99.8%). Step down \\"BIS marked & BEE star labelled transformer of capacity 400 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433 V, 3 phase 4 wire, 50 C/S oil immerse, naturally cooled externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433V with tapping at +/-2.5 %to +/5% & +/- 7.5% on HV side and to be changed by means of hand operated off load tap changing gear including first filling of new transformer oil of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland, Silica gel, breather, Oil level indicator gauge, drain out valve (oil tank), exhaust vent, air release valve, temp gauge, cast iron wheel etc comply with EEL3 with latest amdt 1,2,3 & 4 , IS 1180 2014, Following items/ Accessories included in this rate complete all as specified and directed by Engineer-in-charge. |
| 7 | Srl Item No. 5 Contd/----- (i) Name, rating & diagram plate(ii) Off circuit tap changing switch(iii) Earthling terminals(iv) Lifting lugs(v) Oil drain valve with plug(vi) Oil filter valve with plug(vii) Conservator with oil filling hole(viii) Thermometer pocket(ix) Air release plug(x) Silicagel breather(xi) Removable inspection opening(xii) Explosion vent |
| 8 | Supply and fix lightning arresters expulsion type complete with all fittings suitable for 11000 volts grade conforming to IS-3070 part-I, transmission class, discharge capacity 65 kilo amp complete all as specefied and directed. |
| 9 | Plain cement concrete (1:4:8) type D2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation ect. complete all as specified and as directed. |
| 10 | Providing, cement concrete type B-1, 1:4:8 (using 20mm graded crushed stone aggregate) as in coping of pole and strut, stay around the pole complete all as specified and as directed. |
| 11 | M&L for Steel tublar HT pole and Supply, transportation upto site of work and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and including marking alternate 05 Nos white and black strip 30cm height with two coats of synthetic enamel paint all as specified. (Excavation and earth wok and PCC for foundation, channel, clamps nuts, bolts to be measured and paid separately). |
| 12 | M&L for Material and Labour for construction of plateform for transformer 2.5m (wide)x 2.5m (long) & 1.5m (height) including moorum filling, earth work in brickwork any type of soil, brick work in CM (1:6) and PCC at top 10 cm thick (1:2:4) type B-1 and foundation with 1:4:8 type D-2, 25cm thick all as per drawing including plastering to exposed walls and white wash, providing MS channel on top of size 75x40x8mm of 1.5m length for rolling to transformer, including chain link fencing of wire mesh 150x100 size made out 4mm dia GI wire of height 1.5m fixed with the help of MS strip 25x6mm on and including MS angle iron 75x45x6mm thick 12 Nos post by the means of drilling holes at the distance of 30cm and fixed with the help of suitable nut, bolt and washer, the length of MS angle iron not less than 2.25m top of post bend to the shape of 60 degree including 03 Nos cuts for inserting barbed wire including 03 run of barbed wire and including provision of gate of size 1.5mx0.9m made out of MS angle iron 50x50x6mm and MS bar 12mm dia for meshing to the gate and locking arrangement complete all necessary for work, complete all as specified. . |
| 13 | Earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 32x6 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed.Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way.(ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC.(iii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost |
| 14 | Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4mm dia galvanized iron wire lead by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate No 3 of MES Part-I, including testing on completion including the material and labour and taking out old unserviceable earthing of the following :-(a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1.(c) Precast RCC cover with suitable handle 40 mm thick in RCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal.(g) 4 mm dia galvanised earth lead wire 7.5m.Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.(b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing. |
| 15 | Supply, Installation , testing and commissioing outdoor type, weather proof, cubicle panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 50 x 50 x 6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/ openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments:- |
| 16 | Srl Item No. 14 Contd/----- (a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 Amps for phases and neutral - 01 set .(b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos.(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos.(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job. INCOMINGMain INCOMER: 630 Amps. 4P MCCB (35 KA Rupturing cap) with Adjustable thermal & Adjustable magnetic releases-01 NoDG Set Incomer: 400 Amps. 4P MCCB (35 KA Rupturing cap) with Adjustable thermal & Adjustable magnetic releases- 01 NosOn Load change over switch 630 A-01 NoOUT GOING(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 03 Nos. |
| 17 | Mild steel work as in cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections ( flat, angle, channel) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide primer, one under coat and one finishing coat of aluminium paint, complete all as specified and directed. |
| 18 | Supply and lay DWC ( Double wall corruated ) pipe 120 x 103.5 mm conforming to IS 14930/ IS 16205 for protection of LT / HTCable of size 120 sqmm including neccesory Snap-Fit cuppler required for fixing all as specified and directed. |
| 19 | Supply and lay DWC ( Double wall corruated ) pipe 180 x 152 mm conforming to IS 14930/ IS 16205 for protection of LT / HTCable of size 500 sqmm including neccesory Snap-Fit cuppler required for fixing all as specified and directed. |
| 20 | Supply, laying, jointing & testing XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 500 Sqmm 3.5 core laind in trenches or passing through pipe or fixed on poles complete all as specefied and directed. |
| 21 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes foundations of poles/stays/pipes etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and directed. |
| 22 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed. |
| 23 | Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |