| 1 | Annexure-A (LABOUR CHARGES) |
| 2 | Chemical Earthing including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthing electrode (to be supplied by contractor), connecting the same with G.I. Strip (to be supplied by contractor) of size 35x6 mm for a minimum lenght 6 m. treatment of soil with highly condctive substance as per IS 30343 complete in all respect, result of earthing resistance to be recroded in M.B. before and after installation of earthing. The earth resistance after earthing should be less than 1 Ohm. |
| 3 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel, bracing and special type bracket etc. as per RESPO schedule and local approved drawing. |
| 4 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including proper dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil as directed complete work. |
| 5 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel & clamps as per RESPO manual. |
| 6 | Grouting of pole in size 0.45x0.45x1/9 of the support in CC ratio 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) block including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, levelling as per RESPO cnstruction manual. |
| 7 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm height from ground level including cost of cement, stone and sand etc. |
| 8 | Painting of SP-55 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint and two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 9 | Providing and fixing of Danger Board and number plate complete by providing clamps of M.S. Flat 50x6 mm and Nuts & Bolts, danger Boards of M.S. Sheet 2 mm Thick 11''x7'' size (Including cost of all material). |
| 10 | Cartage of ST pole SP-55 Poles from store centre to construction site with loading, unloading at both points and proper stacking.(Distance 0-20 Km) |
| 11 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and unloading at both ends(distance 0-20 Km) |
| 12 | Headload cartage of SP-55 Pole from road to site (distance 0-1 Km) |
| 13 | Headload cartage of small material(distance 0-1 Km) |
| 14 | Straightning of Tilted STP Poles as per direction of Engineer in charge. |
| 15 | Back Cartage of Petty Material (Distance 0-20 Km) |
| 16 | Fixing of IPC with AL. Bail for Earthing. |
| 17 | Fixing of 11 KV 90KN Tension Clamp B&IPC |
| 18 | Fixing of 11 KV Suspension Ties. |
| 19 | Fixing of 11 KV IPC for CC to CC Conductor. |
| 20 | Fixing of 11 KV IPC for CC to Bare Conductor. |
| 21 | Fixing of 11 KV Mid Span Jointing Kit. |
| 22 | Fixing of Biometalic crimping insulated lugs. |
| 23 | Back Head Load Cartage of Petty Material (Distance 0-1 Km) |
| 24 | Laying Spreading & Sagging of Covered Conductor for 11 KV. |
| 25 | Removing old conductor by opening Jumper. |
| 26 | Annexure-B (SUPPLY ITEMS)(As per UPCL Norms) |
| 27 | Supply of Holding Clamp for SP-55 with N/B |
| 28 | Supply of 11 KV IPC for Covered to Covered Conductor. |
| 29 | Supply of 11 KV IPC for Covered to Bare Conductor. |
| 30 | Supply of 11 KV mid span Jointing Kit |
| 31 | Supply of IPC with Al. BAIL for Earthing 11 KV |
| 32 | Supply of 11 KV Sus. Ties/Cable Ties for Pin Insulator |
| 33 | Supply of 11 KV Biometalic crimping insulated lugs. |
| 34 | Supply of 11 KV ACS AL-59, 104.98 Sq.mm. Covered Conductor. |
| 35 | Supply of 11 KV Polymer Pin Insulator with Pin-D |
| 36 | Supply of Disc Fitting 70 KN-D |
| 37 | Supply of 11 KV Tension Clamp with BAIL & IPC. Please Enable Macros to View BoQ information |