| 1 | Part-B |
| 2 | Supply & construction of 33 KV U/G Line 0.595 km using 3C X 400 sqmm XLPE UG cable without spare (0.535 KM IN Open Trench & 60 mtr in HDD) |
| 3 | Supply of materials for 11kV, 3Core, 400sqmm,Al, XLPE insulation armoured UG cable with accessories |
| 4 | Supply of 33kV, 3Core, 400sqmm, XLPE insulation armoured UG cable (SC rating of cable in kA- 37.7KA and SC rating of Armour in kA- 20kA) |
| 5 | Supply of straight through jointing kits Heat Shrinkable type suitable for 33kV, 3Core,400sqmm, Aluminium UG cable kits |
| 6 | Supply of outdoor termination kits Heat Shrinkable type suitable for 33kV, 3Core,400sqmm, HT UG cable kits |
| 7 | Supply of Indoor termination kits Heat Shrinkable type suitable for 33kv, 3Core, 400sqmm, HT U/G Cable kits (Touch Proof) |
| 8 | Supply of materials for High Density Polyethelene (HDPE) pipe of 200mm diameter, PE 80- PN8 for laying of 33KV UG Cable |
| 9 | Supply of 33kv RMU |
| 10 | No. of 33 kv 3 Way RMU LLV(2ISO+1BKR)+AUX.PT |
| 11 | Supply of RMU 33 KV 3WAY 630A LLV(2ISO+1BKR)+AUX.PT |
| 12 | Earthing |
| 13 | Earthing Conductor :50x6mm(2.4Kg./Mtr.)GI Flat (GI) for Equipment ,Structure etc.) |
| 14 | Pipe earthing 40mm GI Pipe |
| 15 | Erection Portion |
| 16 | Erection, Commissioning & Testing of 33KV new line by 3 core, 400 sqmm XLPE UG Cable |
| 17 | Laying, Commissioning, Testing of 33kV, 3core, 400sqmm, XLPE insulation (extruded type) UG cable by open trench method. |
| 18 | Erection of straight through jointing kits/Outdoor termination kits/Indoor termination kits Heat Shrinkable type suitable for 33kV, 3Core,400sqmm, Aluminium UG cable kits |
| 19 | Installation, Laying, Commissioning & Testing of 33kV, 3core, 400sqmm,XLPE U/G cable by HDD method with HDPE pipe (200mm dia, PN8 PE80) including supply of HDPE pipe |
| 20 | Laying of 200mm dia PE 80-PN8, HDPE pipe inside open trench. |
| 21 | Erection, Commissioning, Wiring and Testing of 33KV RMU |
| 22 | Erection of RMU 33 KV 3WAY 630A LLV(2ISO+1BKR)+AUX.PT |
| 23 | CIVIL Portion |
| 24 | Civil works with supply of all materials like cement, MS tor rod, brick, coarse & fine aggregates and labour, T&P, etc for UG Cable Trench |
| 25 | Earth work excavation of soil (1 mtr width x 1.2 mtr depth) Route Length |
| 26 | Earth work excavation of soil |
| 27 | Earth work excavation of hard rock |
| 28 | Back filling with excavated soil outside and above the trench |
| 29 | Damage of as phalt/tar road and other utilities and reconstructing to bring to its original shape after laying of cable in open trench (1mtr. width) |
| 30 | Civil works with supply of all materials like cement, MS tor rod, brick, coarse & fine aggregates and labour, T&P, etc for HT Cable Trench |
| 31 | Earth work of excavation normal soil Trench Dimension: (1.6 mtr W X 1.775 mtr D) |
| 32 | Earth work of excavation hard rock Trench Dimension: (1.6 mtr W X 1.775 mtr D) |
| 33 | Back filling with excavated soil outside and above the trench |
| 34 | PCC (1:3:6(M-10 Grade)) below trench (width 1500mm, thickness 75mm thoroughout) |
| 35 | Supply and erection of material for RCC partition slab 750mm X 100mm (M-25 grade) |
| 36 | Supply and erection of material for RCC trench, 1500mm thick (M-25 grade) |
| 37 | Supply and erection of rod, bending, cutting and binding of RCC trench (65.23 KG/cum) |
| 38 | Supply and erection of rod, bending, cutting and binding of RCC slabs (67.8 KG/cum) |
| 39 | Centring & shuttering of mass concrete |
| 40 | Structural steel work riveted ( Channel (GI)-75 mmX40mmX4.8mm), (Flat (GI)- 75mmX6mm) |
| 41 | Civil works for Prefabricated RCC Foundation with supply of all materials |
| 42 | Prefabricated RCC foundation of 33kv RMU |
| 43 | Supply of GI Fencing with gate around each RMU |
| 44 | Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation, soil treatment with bentonide powder, calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat (GI) around pipe . |
| 45 | Supply and erection of GI Pipe of dia. 150mm, Class-B (8Mtr.) |
| 46 | Supply and Erection of Cable Route Marker along the cable route at an interval of 30mtrs with civil works |
| 47 | PART-C |
| 48 | No of DP required with Isolator |
| 49 | WPB (GI) Pole160x152 (13Mtr. Long, 30.44KG/Mtr.) - DP( Total Pole Weight with Base Plate & Stiffner=395.72 KG + 10.74 KG= 406.46KG) |
| 50 | Top Channel GI 100 X 50 X 6 mm 9.56Kg./Mtr, rach chanbnel (GI) lenth 4.3 mtr., 2 nos Channel (GI) required= (2X9.56X4.3) |
| 51 | Fish Plate (GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280) |
| 52 | Insulator Support Channel (GI)75x40x4.8 mm, 7.14Kg./Mtr., each channel length 4.3 mtr 1 No's.channel require(Each 1x 4.3x 7.14) |
| 53 | Isolator Support Channel (GI)75x40x4.8 mm, 7.14Kg./Mtr., each channel length 4.3 mtr 2 No's.channel require(Each 2x 4.3x 7.14) |
| 54 | Double Pole Belting Channel (GI) 75X40X 4,8mm., 7,14KG/Mtr., each channel length 4.3 Mtr., 4nos channel required =( 7,14x4.3 x 4) |
| 55 | 50x50x6mm.GI Bracing Angle (GI), 4.5Kg,/mtr each angle (GI) length 4.927 mtr. 4nos angle (GI) required . (4.5x4.927x 4) |
| 56 | Isolator operating Down Pipe Support Channel (GI) 75x 40x 4.8 mm , 7.14 kg/mtr each channel length 0.8 mtr , 1 nos channel required= (7.14x0.8x1) |
| 57 | Down Pipe Diagonal Support Angle (GI) 4.5 Kg/mtr., each Angle (GI) length 0.34mtr., 1 nos Angle (GI) required = (1x4.5x0.340) |
| 58 | Down Pipe Base Support Angle (GI) 4.5 Kg/mtr., each Angle (GI) length 0.34mtr., 1 nos Angle (GI) required = (1x4.5x0.340) |
| 59 | Isolator Support Side Channel (GI)100x50x6 mm mm, 9.56Kg./Mtr., each channel length 0.5 mtr 2 No's.channel require(Each 2x 9.56x 0.5) |
| 60 | Danger Plate, 2 no's. |
| 61 | Back Clamp for danger Plate 25X3 mm. flat (GI), 0.59Kg/ Mtr. Flat of 0.510mtr length 2 no's = (2x0.59x0.510) |
| 62 | HT stay Clamp , 50x8mm flat (GI), 3.14kg/mtr, 0.551mtr length , 2 no's qty required (1pair) |
| 63 | HT stay set (complete) |
| 64 | HT stay insulator TYPE-C |
| 65 | 7/8 SWG stay wire (15Kg./ Set) |
| 66 | GI pipe earthing 40 mm , 3 mtr .Long |
| 67 | 50x6mm GI Flat for earthing ,2.36kg/mtr.(15mtr. For L.A ,4Mtr for Isolator Body, 2.5 Mtr For mesh formation and 2.5 mtr. For raising)=24x2.36 |
| 68 | GI Barbed wire/Anticlimbing device (3kg per support, 2 no's qty required=(2x3kg) |
| 69 | Back Clamp for anticlimbing device 25X3 mm. flat (GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 8 no's = (8x0.59x0.510) |
| 70 | Lightning Arrester(30KV,10KA) Station Class 2 |
| 71 | 33 KV 1250 Amp Double Break (Turn & Twist centre rotating) isloator without earth switch with PI Polymer |
| 72 | 33KV pin insulator polymer |
| 73 | Non metalic Ties-33KV 100SQMM CVRD AAAC |
| 74 | IPC for 100 sqmm AAA conductor (For covered conductor)-33KV |
| 75 | Spike (GI) (using 50x6mm Flat (GI) welded with 8 mm square bar) (2 nos of spike per set in each pole) |
| 76 | H W fitting (B&S)90KN(4bolted) |
| 77 | Disc insulator (B&S)90 KN polymer |
| 78 | Paddle clamp for wedge connector of 100 sqmm AAA Conductor |
| 79 | GI Nut , Bolt & Washer of different sizes (22.15 Kg each DP with Isolator) . |
| 80 | Black Paint (GIS Numbering & Zebra Stripping) |
| 81 | Yellow Colour Paint (GIS Numbering & Zebra Stripping) for Background |
| 82 | CIVIL WORK. |
| 83 | Fixing of complete 33kv line complete stay set includes 1) Turn Buckle Assembly 2) Stay rod and Stay plate 3) Stay insulator 4) Stay wire. 5) Stay clamps with nuts & bolts BA will done the excavation including excvation. supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard . Note- Excavation of earth will be done of 500x500x1500mm |
| 84 | Concreting ratio 1:1.5:3 (M-20Grade)(500mm X 500mm X 2200mm) = 0.550Cu.mtr (Per Pole) |
| 85 | Couping ratio 1:1.5:3 (M-20Grade) withdimension (500mmX500mmX450mm) = 0.1125Cu.mtr (Per Pole) |
| 86 | Provide necessary civil material for Construction of Earthing chamber, excavation & installation of including earthing pipe dia upto 100mm dia for length 3 Mtr.Scope also includes necessary nutbolt, 25 Kg Bentonide powder, connection & welding with incoming earth Flat (GI). The work to be executed as per TPCODL drawing & design.. |
| 87 | 33KV Cut Point with 180 Degree Angle |
| 88 | 33KV pin insulator polymer |
| 89 | H W fitting (B&S)90KN(4bolted) |
| 90 | Disc insulator (B&S)90 KN polymer |
| 91 | Non metalic Ties-33KV 100SQMM CVRD AAAC |
| 92 | IPC for 100 sqmm AAA conductor (For covered conductor)-33KV |
| 93 | 33KV Line Length with 40 Mtr Span |
| 94 | 100 SQMM AAAC XLPE Covered Conductor-33KV |
| 95 | 33KV Indoor air insulated VCB Panel |
| 96 | Supply, delivery, installation, testing & Commissioning of 33KV Indoor air insulated VCB Panel made out of 2.0mm thick CRCA sheet steel complete with internal wiring incorporating the following |
| 97 | Incomer: 33KV 1250A 25KA VCB (AIS) |
| 98 | Instruments: 1 set each of 4 Nos. 65-KA SP SA along with 32 AMP SP MCB backup protection for each SA |
| 99 | 3Set PT with ratio 33KV / √3/110V/ √3 with 0-36KV Voltmeter with selector switch |
| 100 | 3 Set Multi function meter with CT STC 25 KA for 1-sec - 100-50/1-1A, 5P20, 15VA |
| 101 | 3 Set Multi function Numerical Relay with CT STC 25 KA for 1-sec - 100-50/1-1A, CL 1.0, 15VA |
| 102 | Busbar: 33KV, 1250A, 50c/s, 3ph, 3w, 25.3KA for 3 sec copper Busbar |
| 103 | Outgoing: 2nos 33KV 630A 25KA VCB (AIS) |
| 104 | Complete duly factory wired as per SLD |
| 105 | 1250 KVA, 33/0.433 KV Outdoor type Transformer |
| 106 | Design, Supply, delivery, installation, testing & Commissioning of 1250KVA, 33/0.433 KV, 3phase, 50Hz Copper wound outdoor type transformer, natural oil cooled (ONAN) to be manufactured as per IS: 1180(part-1)/2014(level-2) complete with standard fittings and accessories and MOG, buchholz relay, WTI, OTI duly wired upto the marshalling box and on-load-tap changer(OLTC) ranging from -5% to +15% in steps of 2.5%, RTCC Panel with AVR. The Transformer shall have the cable end box at both 33KV side and 433V side as per the detail technical specification & the direction of Engineer-in-charge. |
| 107 | N.B: The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed. Please Enable Macros to View BoQ information |