| 1 | Supply and fix ERW MS pipe heavy duty 150mm Dia including socket/ joint including taking down old unserviceable MS pipe of any type and size complete all as specified and directed. |
| 2 | Excavation in trenches n.exc 1.5 M wide and n. exc 1.5 M depth and getting out in hard/ dense soil .complete all as specified and directed by Engr-in-Charge |
| 3 | Returning, filling in including spreading levelling, watering and well ramming in layers n.exc.25cm thick. complete all as specified and directed by Engr-in-Charge |
| 4 | Removing excavated material to a distance n.exc 50 M and depositing where directed at a level n.exc 1.5 M above the starting point complete all as specified and directed by Engr-in-Charge |
| 5 | Cutting CI/ MS pipes and reducing to required length before fixing complete all as specified and directed by Engr-in-Charge |
| 6 | Cutting CI/ MS pipes and reducing to required length before fixing in position for insertion of new tees, bends etc complete all as specified and directed by Engr-in-Charge |
| 7 | Dismantling joints of flanged pipes in position, including removing old rubber or fibre board gaskets, bolts, nuts. Etc complete all as specified and directed by Engr-in-Charge |
| 8 | Supply and fix Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. \\"Y\\" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs complete all as specified and directed by Engr-in-Charge |
| 9 | Supply and fixing gate valve 50 mm complete all as specified and directed by Engr-in-Charge |
| 10 | Supply and fixing ball valve 50 mm complete all as specified and directed by Engr-in-Charge |
| 11 | Supply and fixing Stainer for Suction Dia 150 mm in size complete all as specified and directed by Engr-in-Charge |
| 12 | Supply and fixing non return valve PN- 1.6, 100 mm Dia both ends flanged heavy duty including packing materials, nut bolts washer etc and testing complete all as specified and directed by Engr-in-Charge. |
| 13 | All as per item No.12 but bore size of 50 mm complete all as specified and directed. |
| 14 | Supply and fixing Sluice valve 150 mm PN- 1.6 both ends flanged heavy duty including packing materials, nut bolts washer etc and testing complete all as specified and directed by Engr-in-Charge |
| 15 | All as per item No.14 but bore size of 100 mm complete all as specified and directed. |
| 16 | All as per item No.14 but bore size of 80 mm complete all as specified and directed. |
| 17 | Supply & Fixing pressure gauge 4'' dial 0-14kg/cm² rating as per sample complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply, Installation, Testing & Commissioning of fire hydrant landing Valve Type A (single head outlet) of 63mm Dia size complete all as specified and directed by Engr-in-Charge |
| 19 | Supply & Fixing Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard including taking down old unserviceable complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply & Fixing CP Hose 15 Mtr length, 63mm Dia complete all as specified and directed by Engr-in-Charge. |
| 21 | Supply & fix Butterfly Valve conforming to IS of size 150mm Dia including taking down old unserviceable valve complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply & fix Fire brigade inlet connection 2way conforming to IS including taking down old unserviceable complete all as specified and directed by Engr-in-Charge |
| 23 | Supply & fix Pressure switch Universal type 8'' dial 0-14kg/cm² rating as per sample complete all as specified and directed by Engr-in-Charge. |
| 24 | Supply & fix Flow switch 150 mm Dia as per sample complete all as specified and directed by Engr-in-Charge. |
| 25 | Supply & fix Detectors complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical base with self built intelligence as per IS: 11360 complete all as specified and directed by Engr-in-Charge |
| 26 | Supply & fix Detectors complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination Photoelectric /Optical base with self built intelligence as per IS: 11360 complete all as specified and directed by Engr-in-Charge |
| 27 | Supply & fix Addressable electronic sounder cum strobe complete all as specified and directed by Engr-in-Charge |
| 28 | Supply & fix Addressable manual call point resettable type complete all as specified and directed by Engr-in-Charge |
| 29 | Supply and fix 415V 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB with connection testing and commissioning complete all as specified and directed by Engr-in-Charge |
| 30 | (a) TP 25 To 63 AMP |
| 31 | (b) TPN 16 To 32 AMP |
| 32 | (c) TPN 40 To 100 AMP |
| 33 | Supply and fix MCCB 3 Pole , 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA with connection testing and commissioning complete all as specified and directed. |
| 34 | Material and labour for earthing with copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less 'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm Dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed by Engr-in-Charge |
| 35 | Taking down old unserviceable stainer, valves, pressure gauge, landing hydrant valve, MS hose boxes, pressure switches, CP hoses, flow switch and fire brigade inlet of any type and size complete all as specified and directed by Engr-in-Charge |
| 36 | Taking down old unserviceable MCB/ MCCB of any type and size complete all as specified and directed by Engr-in-Charge |
| 37 | Taking down old unserviceable detectors, sounders and manual call points of any type and size complete all as specified and directed by Engr-in-Charge |
| 38 | Taking out sluice valves refacing, regrinding and replacing spindle, gate and locking checknut including packing gland of sluice valve of size 150/ 200 mm Dia bore and refixing complete all as specified and directed. |
| 39 | Servicing and repair of 4 Loop addressable fire alarm control panel , calibrating, checking and testing for operation, repairing for spare parts required complete all as specified and directed. |
| 40 | Material & Labour for cleaning of Diesel tank of capacity 900 litres by drying tank and cleaning by vacuum cleaner complete all as specified and directed. |
| 41 | Material & Labour for checking, cleaning and testing of fire/ smoke and heat detectors by artificial means to check the serviceability of detectors of total 135 Nos complete all as specified and directed. Please Enable Macros to View BoQ information |
| 42 | Material & Labour for checking, cleaning and testing of fire/ smoke and heat detectors by artificial means to check the serviceability of detectors of total 135 Nos complete all as specified and directed. Please Enable Macros to View BoQ information |