| 1 | Supply, Installation, Testing of IT related Items & other associated activities as per tender technical specifications |
| 2 | Shifting and installation of Racks, Servers & other IT Networking equipment in Centralised Server Room from existing location in same floor and maximum distance is 50Meters. |
| 3 | Shifting & Installation of Racks in new Centralized Server Room(Total 7Nos of racks having size of racks is 42U Height and 800mm width X 1000 MM Depth). |
| 4 | Shifting & Installation of Servers in new Centralized Server Room(Total no of physical servers) |
| 5 | Shifting & installation of other IT equipment (like Routers, Switches, Firewall, UPS etc.). |
| 6 | Supply & installation of Passive components (like LIU Patch Panel, Pigtails, Cable Manager, UTP Connectors, OFC Couplers and other passive items to complete the work). |
| 7 | Supply & laying/installation of CAT6A UTP Cable, OFC Cable & Cable Tray. |
| 8 | Supply of 2 Boxes of CAT 6A UTP Cables (1 Box=305 mtr.) and laying & termination of cables upto new Centralized Server Room as per site requirement. |
| 9 | Supply of 100 m of 24 Core Armoured Optical Fibre (Single Mode) and laying & termination of cables upto new Centralized Server Room as per site requirement. |
| 10 | Supply & laying of suitable cable tray (for laying UTP & OFC cables) |
| 11 | Supply, Installation & Testing of Instrumentation systems & other associated activities as per tender technical specifications |
| 12 | Fire Suppression system |
| 13 | Supply of Rack Mount Based Fire Suppression System |
| 14 | Supply of Cylinder-less Tube based Fire Suppression System |
| 15 | Installation & Commissioning of Fire Suppression System (mentioned at 2.101 & 2.102) along with supply of necessary accessories required for installation of system. |
| 16 | Access Control System |
| 17 | Supply of RFID and Biometric based Access Control Terminal for Entry |
| 18 | Supply of RFID based Card Reader for exit |
| 19 | Supply of Electro Magnetic Lock with Push Button Type Door Release switch |
| 20 | Supply of MiFARE Desfire RFID Cards |
| 21 | Supply of Access Control Management Software & installation of this software on HWB designated Workstation PC |
| 22 | Installation, Commissioning & Configuration of Access Control System (mentioned at 2.201 to 2.205) along with Programming & enrolment of RFID cards & supply of necessary accessories required for installation of system |
| 23 | Supply, Installation & Testing of Electrical systems & other associated activities as per tender technical specifications |
| 24 | AC Distribution Boards |
| 25 | Supply of Main AC Distribution Board :AC Distribution Board The A.C. Distribution Board shall be floor/ wall mounted type i) INCOMERS: One no. with SFU with fast acting fuses, `ON’ indicating lamp, Voltmeter and ammeter The incomer shall be designed for minimum 160 Amp rating.ii) OUT GOING FEEDERS: 4 nos of 100A O/G feeder shall have double pole MCCB with `ON’ indicating lamp. The out going feeder shall have provision for connection of 2 C 50 sqmm Al cable |
| 26 | Supply of AC Distribution Board The A.C. Distribution Board shall be floor/ wall mounted type i) INCOMERS: One no. with SFU with fast acting fuses, `ON’ indicating lamp, Voltmeter and ammeter The incomer shall be designed for minimum 100 Amp rating.ii) OUT GOING FEEDERS: O/G feeder shall have double pole MCB with back-up protection through semiconductor fuses & `ON’ indicating lamp. 8 nos. 32 A feeder,12 nos. 20 A feeder. |
| 27 | Installation & Commissioning of AC Distribution Boards (mentioned at 3.101 & 3.102) along with supply of necessary accessories required for installation of distribution Boards. |
| 28 | Power cables |
| 29 | Supply, laying on walls, and fixing or existing cable tray of FRLS PVC Sheathed XLPE insulated, Copper conductor, armoured power cable of size 4 core x 16 sq.mm. |
| 30 | Supply, laying on walls, and fixing or existing cable tray of FRLS PVC Sheathed XLPE insulated, Aluminium conductor, armoured power cable of size 2 core x 50 sq.mm. |
| 31 | Supply, Laying, and Fixing of 3C x 6 sq.mm FRLS XLPE Copper Armoured Power Cable. |
| 32 | Termination of 4 core x 16 sq.mm above copper conductor cable including the supply of all necessary consumables. |
| 33 | Termination of 2 core x 50 sq.mm above cable including the supply of all necessary consumables. |
| 34 | Termination of 3C x 6 sq.mm FRLS XLPE insulated Copper conductor Armoured above cable including the supply of all necessary consumables. |
| 35 | Dismantling / Removal of electrical installation |
| 36 | Dismantling and removal of existing electrical installations including light fittings, ceiling/wall fans , switch sockets and other associated electrical accessories in the proposed server room. |
| 37 | Shifting of ASCO make 63/70 A 3 phase Automatic Power Transfer switch, This job involve uninstallation of the existing Automatic Power Transfer switch and installation at location as per EIC. Consumables and workmanship is in scope of the item. |
| 38 | Supply and Fixing of surface mounted 32A, 240V 2P-E Industrial Socket Outlet with Plug Top, the surface mounted socket is to be install at cable tray. All the necessary arrangement to in scope of the work. |
| 39 | Supply and installation 300 mm width, 100 mm height & 3 mm thick 60 micron GI coating cable tray with 2 mm thick cover including bends/ risers, hanging arrangement from roof and other accessories required for completion of work. |
| 40 | Civil work as per following scope |
| 41 | Demolition work |
| 42 | False Ceiling Demolition: Removal of existing false ceiling, Including careful removal of Electrical & service wires, refixing of wires/ cables etc. Handing over the same to departmental stores, disposal of debris to designated place at VS bhavan for onward transportation etc. complete with all leads and lifts and as per direction of Engineer-In-Charge |
| 43 | Glass partition/ door removal: Removal of existing Aluminium glass partition partly glazed, doors etc. Including careful removal of supported Electrical & service wires, handing over the same to departmental stores, disposal of debris to designated place at VS bhavan for onward transportation etc. complete with all leads and lifts and as per direction of Engineer-In-Charge |
| 44 | Furniture removal: Careful Removal of exiting furniture / work stations/cupboards/doors with shutter & frame including careful removal of wires/ cables etc. & relocating the furniture at a designated place or disposal of the same to designatd place at VS bhavan for onward transportation etc. complete with all leads and lifts and as per direction of Engineer-In-ChargeNote: Only top plan area will be measured for payment purpose as per the furniture removal drawing. |
| 45 | Wall demolition: Breaking of existing 6\\"-9\\" brick wall with plaster & tiles (if any) as per demolition layout as per approved drawing/as directed by Engineer In Charge, removing door / windows, stacking of all serviceable material and handing over the same to departmental stores, disposal of debris to designated place at VS bhavan for onward transportation etc. complete with all leads and lifts and as directed by the Engineer In Charge. |
| 46 | Rubble Collection & Disposal :Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground etc. complete outside BARC colony as approved by EIC, with all leads and lifts and as directed by the Engineer In Charge. |
| 47 | New Brick Wall: Providing and constructing 4 \\" to 6 \\" thick brick wall in partitions using common burnt clay bricks, with 1:4 cement mortar, providing RCC (1:2:4) stiffeners 105x75mm size at every 900mm with Two nos 8 mm dia steel and 8mm dia stirrups @ 300mm C/C, in the RCC band and including scaffolding, form work, racking of joints, curing, labour, materials, transport etc. to fill up the openings all complete as per specifications and as directed by the Engineer In Charge. |
| 48 | Wall plaster :- Providing and applying 15 mm thick internal wall plaster with 1:4 cement sand mortar, including necessary scaffolding, curing etc. complete as per specifications and as directed by the Engineer In Charge. |
| 49 | Refixing of doors: Refixing of existing door complete with shutter having standard size (7 ''x 3'') in the wall opening after making it even & smooth with cement mortar (1:4) for installation & refixing of the door including careful handling & shifting of all accessories viz.locks, handles, damper/ stopper, hinges etc. as per the location indicated in the drawing or as specified by the Engineer in charge. |
| 50 | Supply & installation of door with accessories : Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and laminated on both side upto 1.25mm thickness with two different shades with all door accessories viz. SS door handles with locking arrangement, brass stopper etc. as directed by EIC 35 mm thick Fixing with hinges of required size and necessary screws and door closure. Door closure shall be heavy duty aluminium (silver finish) hydraulic double speed door closure with all accessories & fittings. Door shall be provided with toughened glass vision panel of size(700mmx300mm) frosted as per requirement having all around teak wood lipping on both side etc. all complete as directed by EIC. Note: Only Front area on one side of door will be measured for payment. |
| 51 | Painting & Punning |
| 52 | Painting with wall putty - Walls & Beams : Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. over two coats of compatible primer as per manufacturer's recommendation using expert labour including scrapping existing paint, Surface preparation, filling the patches even with cement mortar (1:4), cleaning, applying Acrylic Wall Putty wall putty of average 1mm thickness of TruCare Acrylic Wall Putty or equivalent approved by the EIC over the entire wall surface to prepare the surface even and smooth etc. complete as per specifications and as directed by the Engineer. |
| 53 | Painting - Ceiling : Painting with two coats of premium interior emulsion paint (Royale paint of Aian Paint or equivalent approved by EIC ) over two coats of compatible primer as per manufacturer's recommendation (Royale base coat or equivalent approved by EIC) using expert labour including preparation of surface even, filling the holes/ doing patch work with cement mortar (1:4), applying 1 mm wall putty & rendering the surface smooth, clean before applying paint coating etc. complete as per specifications and as directed by the Engineer. |
| 54 | ACP panelling work: Supply & installation of Aluminium Composite panel for panelling & shuttering of cupboards with aluminium framing using 4 mm thick ACP panelling consisting of 3mm FR (Fire retardant) grade mineral core sandwiched between two aluminium sheet of 0.5mm each supported on a frame work made up of aluminium box/ angle/CP cleats section of weight not less than 0.81 kg/m (50mmx50mmx1.5mm) and necessary stainless Steel screws /MS bracketsetc.hardwares, accessories like hinges, handles, ,lock etc. all groves being filled with foam and silicon sealant including removal of existing cupboards, disposing at a designated place for onward transportation etc. all complete as per the direction of Engineer in charge. (Mode of payment is on finished surface area of ACP)(a) 4mm thick (0.50mm Al.+3.0mm FR grade mineral core +0.50mm Al. PVDF coating) |
| 55 | Flooring work - Cement concrete base & vinyl flooring Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) of 40 mm thickness or more using zero size aggregate finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. . This shall be overlaid by vinyl flooring of 2 mm thickness of approved pattern and shade including necessary adhesive over the IPS/ Mosaic flooring / Skirting including cutting to the required size and shape including wastage, removing existing vinyl flooring/carpet if any, cleaning the flooring before and after the completion of works all as per manufacturer's specifications in general and as per approved pattern, including disposal of debris within BARC colony or to a designated BMC dumping ground etc. complete with all leads and lifts and as directed by the Engineer In Charge. etc. complete and as directed by EIC. Flooring work is referred is a patch work which is to be carried out after removal of existing furniture. Notes:a) Finished top area shall be measured for the purpose of payment |
| 56 | Table of size 1200Wx600Dx 750HProviding, assembling, transporting & installation of Office Table - size 1200 Width mm x 600 Depth mm x 750 Height mm , consisting of : • Table top made out of 25 mm thick plain particle board (PPB) Clad with 0.6 mm thick post formed laminate and 1 mm thick backing laminate (bdl). Table flat edge duly sealed with 2 mm thick PVC beading. •Modesty shall be of 18 mm thick plain particle board ( ) PPB Clad with 1.0 mm thick decorative laminate (DL) on both sides. Edge Sealed with 2 mm thick PVC beading. Emission Class : Product should comply with emission norms CARB (E1 -P2 grade) Product should be certified by a NABCB Accredited agency for conformity assessment. Please Enable Macros to View BoQ information |