| 1 | Disconnection of transformer 250 KVA from HT and LT side carefully after taking proper safety measures and shifting the same in MES store as directed by Engr-in-Charge with proper T&P and vehicles complete all as specified and/or as directed by Engr-in-Charge. |
| 2 | Dismantling of ACSR or AAC conductors complete all as specified and/or as directed by Engr-in-Charge. |
| 3 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside complete all as specified and/or as directed by Engr-in-Charge. |
| 4 | Dismantling insulators any type, any size complete all as specified and/or as directed by Engr-in-Charge. |
| 5 | Dismantling stay assembly complete all as specified and/or as directed by Engr-in-Charge. |
| 6 | Dismantling earth wire or copper conductor, service feeder or distributor span complete all as specified and/or as directed by Engr-in-Charge. |
| 7 | Dismantling steel poles/ struts, any size complete all as specified and/or as directed by Engr-in-Charge. |
| 8 | Dismantling air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism complete all as specified and/or as directed by Engr-in-Charge. |
| 9 | Supply, installation, testing and commissioning of step down 11/0.433 KV capacity 630 KVA, level III, IS 1180 Part-l, outdoor type copper wound 3 Phase, 4 wire, 50 cycles as per second, oil immersed naturally cooled external cooling tube core type delta connection on primary side (HV side) and star connection on secondary side (LV side) having tapping 0, + 2.5%, +5%, + 7.5% to be charged by means of hand operated, off load/ tap changing gear including first filling of new transformer oil of dielectric strength not less than 60 KV with standard fitting such as two earthing terminals for body and one additional for neutral brought out in bushing, oil level gauge indicator for level minimum and maximum, lifting lugs, rating and terminal plate, plain breather device to prevent ingress of rain water and inserts, drain cum sampling valve 20mm bore steel with plug, dial type thermometer, oil filling hole 32mm threaded with plug. The transformer shall be powder coated for water/ dust and vermin proof. Note- (1) Transformer Oil shall be confirming to requirement of IS-335-1983 specification for new insulating oil for transformers. (2) Equipment shall be suitable to operate at 4200 Mtr above MSL at temperature variation between (-) 35 degree centigrade to (+) 35 degree centigrade complete all as specified or as directed. |
| 10 | Supply and fix HT 11 KV, out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 insulators of rating up to 200 Amps complete including taking down u/s air break switch all as specified and/or directed by the Engr-in-Charge. |
| 11 | M&L of ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag, jointing jumpers etc. complete all as specified and/or as directed by Engr-in-Charge. |
| 12 | M&L Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia complete all as specified and/or as directed by Engr-in-Charge. |
| 13 | M&L for anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and/or as directed by Engr-in-Charge. |
| 14 | M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and/or as directed by Engr-in-Charge. |
| 15 | M&L in replacement for lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11000 V grade complete all as specified and/or as directed by Engr-in-Charge. |
| 16 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and/or as directed by Engr-in-Charge. |
| 17 | Supply and fix of pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and/or as directed by Engr-in-Charge. |
| 18 | All as per Srl item No. 17 above, but size 150mm height, 150mm dia for 11000 volts grade complete all as specified and/or as directed by Engr-in-Charge. |
| 19 | M&L for Shackle type, porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, of size 100mm high and 115 mm dia suitable for working voltage 1100 V grade complete all as specified and/or as directed by Engr-in-Charge. |
| 20 | M&L for disc type insulator, porcelain, vitreous 145 mm high and 255mm dia ball and socket type, white, brown or green Two-in-series' assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and/or as directed by Engr-in-Charge. |
| 21 | Supply, erecting and fixing in true vertical position Steel tubular swaged poles (11.0 metres long) complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55, including painting with two coats of aluminium paint over a coat of red oxide paint complete all as specified and/or as directed by Engr-in-Charge. (for four pole construction). Note: Earth work, PCC and MS work will be measured & paid seperately under relavent items. Please Enable Macros to View BoQ information |
| 22 | Supply, erecting and fixing in true vertical position Steel tubular swaged poles (11.0 metres long) complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55, including painting with two coats of aluminium paint over a coat of red oxide paint complete all as specified and/or as directed by Engr-in-Charge. (for four pole construction). Note: Earth work, PCC and MS work will be measured & paid seperately under relavent items. Please Enable Macros to View BoQ information |