| 1 | Control Room |
| 2 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use, dual -action hammerless resettable type (operated by special key), and transparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two- wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessories and fully compatible with Fire detection alarm panel. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 3 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories. The module shall have 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 4 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), compliant with EN54-3, suitable for indoor use, with 16 selectable tones, adjustable sound output upto 4 levels, high-intensity LED for visual alarm, loop- powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 5 | Supply, installation, testing and commissioning of Addressable Control Module, with dry contact relay output (NO/NC) input/output function, relay output 30VDC/1A, EOL supervision, LED indication, with reverse-polarity protection and 16–28V DC operation, complete with base. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 6 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 7 | Supply, Installation, Testing and Commissioning of Manual Release Switch |
| 8 | Supply, Installation, Testing and Commissioning of Manual Abort Switch |
| 9 | Supply, Installation, Testing and Commissioning of Electrically Actuated Fire Suppression Generators containing 5.7 kg Aerosol with provision for discharge feedback |
| 10 | Supply, Installation, Testing and Commissioning of 5 Amp SMPS |
| 11 | Supply, Installation, Testing and Commissioning of Fiber Optic Cable with FOC Core Diameter: 62.5μm; Fiber CladdingDiameter: 125μm; FOC Core: Single Core Multimode where Outer sheath material is Anti-static, flame retardant, low smoke halogen- free materials and inner core material is composed of stainless-steel spiral tube, with measuring temperature range -40℃ ~ +120℃. |
| 12 | Supply, Installation, Testing and Commissioning of 2Cx1.5 sq.mm. armoured copper FRLS cable. |
| 13 | Supply, Installation, Testing and Commissioning of 2Cx2.5 sq.mm. armoured copper FRLS cable. |
| 14 | Supply, Installation, Testing and Commissioning of 6kgs Portable fire extinguisher CF Green 100% PED (CE MARKED), BIS (IS 15683) CERTIFIED capable of extinguishing fire of type A, B, C,E and ESF, Working pressue 15 Bar cylinder material -Steel CR2(DC01) and at least 5 year warranty |
| 15 | Providing of First Aid Kit as per Section 45 of the Factories Act, 1948 |
| 16 | INSIDE GENERATOR |
| 17 | Supply, installation, testing, and commissioning of an Intelligent Microprocessor-based Addressable Fire Alarm Control Panel, LPCB approved and EN 54 certified or higher or IS/ISO 7240 series. The panel shall be 1 built-in SLC loop expandable up to 32 loops, supporting up to 256 addressable devices per loop for Class A, and 512 addressable devices per loop for Class B networkable with up to peer-to peer 128 panels via RS485 or Fiber Optic cable. Details given in Scope of work of SBD |
| 18 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use, dual -action hammerless resettable type (operated by special key), and transparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two- wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessories and fully compatible with Fire detection alarm panel. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 19 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories. The module shall have 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 20 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), compliant with EN54-3 or higher or IS/ISO 7240 series, suitable for indoor use, with 16 selectable tones, adjustable sound output upto 4 levels, high-intensity LED for visual alarm, loop- powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 21 | Supply, installation, testing and commissioning of Addressable Control Module, with dry contact relay output (NO/NC) input/output function, relay output 30VDC/1A, EOL supervision, LED indication, with reverse-polarity protection and 16–28V DC operation, complete with base. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 22 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 23 | Supply, Installation, Testing and Commissioning of Manual Release Switch |
| 24 | Supply, Installation, Testing and Commissioning of Manual Abort Switch |
| 25 | Supply, Installation, Testing and Commissioning of Electrically Actuated Fire Suppression Generators containing 5.7 kg Aerosol with provision for discharge feedback |
| 26 | Supply, Installation, Testing and Commissioning of 3 Amp SMPS |
| 27 | Supply, Installation, Testing and Commissioning of Distributed Temperature Monitoring Controller having minimum 10 inches industrial grade colour graphics display ,4 channel controller with minimum 20 km measurement range where 1 channel take up to 5km Multimode/Single mode Fiber optics cable , - Measure temperature -40°C ~ +120°C (Depends on the Sensing Fiber) with ±1°C accuracy and 16 in-built Relays with temperature resolution 0.1°C and can be set/customized minimum 4 different alarm temperature settings, communication interface with 1RS485(standard MODBUS RTU protocol) along with all necessary accessories. |
| 28 | Supply, Installation, Testing and Commissioning of Fiber Optic Cable with FOC Core Diameter: 62.5μm; Fiber Cladding Diameter: 125μm; FOC Core: Single Core Multimode where Outer sheath material is Anti-static, flame retardant, low smoke halogen- free materials and inner core material is composed of stainless-steel spiral tube, with measuring temperature range -40℃ ~ +120℃. |
| 29 | Supply, Installation, Testing and Commissioning of 2Cx1.5 sq.mm. armoured copper FRLS cable. |
| 30 | Supply, Installation, Testing and Commissioning of 2Cx2.5 sq.mm. armoured copper FRLS cable. |
| 31 | MACHINE HALL |
| 32 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use, dual -action hammerless resettable type (operated by special key), and transparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two- wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessories and fully compatible with Fire detection alarm panel. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 33 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), compliant with EN54-3, suitable for indoor use, with 16 selectable tones, adjustable sound output upto 4 levels, high-intensity LED for visual alarm, loop- powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 34 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories. The module shall have 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 35 | Supply, Installation, Testing and Commissioning of dual IR powered flame detection system designed for critical infrastructure and harsh outdoor environments. The device shall have minimum dual sensors including a 5MP progressive scan super low lux CMOS sensor and an IR flame sensor using 4.3 µm main detection with a 5.0 µm comparative band, and the device shall have a fixed F1.6 4 mm 5MP lens with horizontal field of view of 90° and vertical field of view of 48°. The deatils are given in Scope of work in SBD. |
| 36 | Supply, Installation, Testing and Commissioning of 5 Amp SMPS |
| 37 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 38 | Supply, Installation, Testing and Commissioning of 2Cx1.5 sq.mm. armoured copper FRLS cable. |
| 39 | Supply, Installation, Testing and Commissioning of 6kgs Portable fire extinguisher CF Green 100% PED (CE MARKED), BIS (IS 15683) CERTIFIED capable of extinguishing fire of type A, B, C, E and ESF, Working pressue 15 Bar cylinder material -Steel CR2(DC01) and at least 5 year warranty |
| 40 | Turbine Floor Cable Tray |
| 41 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use, dual -action hammerless resettable type (operated by special key), and transparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two- wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessories and fully compatible with Fire detection alarm panel. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 42 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories. The module shall have 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 43 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), compliant with EN54-3, suitable for indoor use, with 16 selectable tones, adjustable sound output up to 4 levels, high-intensity LED for visual alarm, loop- powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 44 | Supply, installation, testing and commissioning of Addressable Control Module, with dry contact relay output (NO/NC) input/output function, relay output 30VDC/1A, EOL supervision, LED indication, with reverse-polarity protection and 16–28V DC operation, complete with base. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 45 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. LPCB approved to EN 54 standard or higher or IS/ISO 7240 series |
| 46 | Supply, Installation, Testing and Commissioning of Manual Release Switch |
| 47 | Supply, Installation, Testing and Commissioning of Manual Abort Switch |
| 48 | Supply, Installation, Testing and Commissioning of Electrically Actuated Fire Suppression Generators containing 10 kg Aerosol with provision for discharge feedback |
| 49 | Supply, Installation, Testing and Commissioning of 5 Amp SMPS |
| 50 | Supply, Installation, Testing and Commissioning of Fiber Optic Cable with FOC Core Diameter: 62.5μm; Fiber Cladding Diameter: 125μm; FOC Core: Single Core Multimode where Outer sheath material is Anti-static, flame retardant, low smoke halogen- free materials and inner core material is composed of stainless-steel spiral tube, with measuring temperature range -40℃ ~ +120℃. |
| 51 | Supply, Installation, Testing and Commissioning of 2Cx1.5 sq.mm. armoured copper FRLS cable. |
| 52 | Supply, Installation, Testing and Commissioning of 2Cx2.5 sq.mm. armoured copper FRLS cable. |
| 53 | LT PANEL |
| 54 | Supply and Installation of Thermally Actuated Aerosol based Fire Extinguishing Cylindrical Generator with SS-304 Enclosure. The Aerosol Generators shall contain the solid aerosol-forming compound which when activated, transforms into a rapidly expanding fire extinguishing condensed aerosol, with total flooding characteristics, whose function is to interrupt the chemical chain reactions within the flame thus extinguishing it, without the depletion of oxygen within the enclosure. The device shall have no pressure at stand-by condition. should have dual ports for activation (thermal and electrical) with the ability to function properly, when utilizing both methods of actuation simultaneously. The device shall be UL Listed as per FM standards or VdS certified as per EN54 standards or higher or IS/ISO 7240 series and shall have certifications for Human and Environmental Safe application. retrofitting and modifications in the existing panels without affecting the integrity or working of the panel Cylindrical Fire Extinguishing Generator - 30g capacity with BTA The job includes retrofitting and modifications in the existing panels without affecting the integrity or working of the panel. |
| 55 | GRAPHIC SOFTWARE FOR FIRE MONITORING |
| 56 | Supply, Installation, testing and commissioning of Computer Based Graphics User Interface for Monitoring & Control of complete Fire Alarm System. The GUI shall graphically represent each facility being monitored with floor plans and icons depicting the actual locations of the various systems, and/ or sensors’ locations. The GUI should have minimum 5000 fire points monitoring lisence with at least 5 nos. Client License for simultaneous monitoring of the facility from multiple operator station. The GUI based main network software shall network with other panels on True Peer-to-Peer network & Failure of Fire Panel CPU shall not result in failure of the GUI.This item should include necessary server grade Workstation of having processor of Intel i5, 13th Generation and HD Monitors of minimum 20 inch. |
| 57 | Miscellaneous or Civil work required for the installation and commissioning of the fire-fighting system Please Enable Macros to View BoQ information |