| 1 | Taking up ductile iron water mains (including all fittings) of any description of pipe for cleaning/ removing deposited mud, sludge etc including burning out joints and recovering lead or gasket joint for pipes of following size complete all as specified and directed :- |
| 2 | MS/DI pipe 150 mm bore size |
| 3 | MS/DI pipe 100 mm bore size |
| 4 | Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/ laying CI/GI/DI pipes and getting out in any type of soil complete all as specified and directed. |
| 5 | Cutting road, concreate surface for laying of DI/MS pipe and making good of disturbed surface as per existing complete all as specified and directed. |
| 6 | Removing excavated soil at a distance not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed. |
| 7 | Returning,filling in including spreading, leveling, watering and well rumming in layers not exc 25 cm complete all as specified and directed. |
| 8 | Supply and laying 150mm dia centrifugally cast (spun) Ductile iron pressure pipes with double flanged end, class K-9 conforming to IS-8329/2000 (latest revision) with inside cement mortar lining and metalic zinc coating and outside black bitumen coating and having portland cement properties suitable for gasket joints including suitable size of rubber gasket, nuts, bolts and washer but excluding specials complete all as specified and directed. |
| 9 | All as per BOQ Serial item No 6 above but 100mm diameter complete all as specified and directed. |
| 10 | M&L for rubber gasket joint (as per IS 638) for 150mm dia flanged DI pipe with gasket and suitable size of nuts, bolts and washer complete all as specified and directed. |
| 11 | All as per BOQ Serial item No. 8 above but for 100mm dia pipe, complete all as specified and directed. |
| 12 | Dimantling and taking up of old fittings and S&F DI special, class K-12, both end flanged or both end spigot/socket or one end flanged and other end spigot/socket (as required at site) any type such as bends, tapers, reducers, duck foot bend, tee pieces (single and double branch), etc including cutting of pipes for upto 150 mm dia ductile iron pipe as per site requirement complete all as specified and directed. |
| 13 | Taking up the following MS pipes & connections unserviceable valves, etc. of any size from trenches/ floors/walls of different sizes complete all as specified and directed:- |
| 14 | MS pipe 150 mm bore. |
| 15 | MS pipe 80mm bore. |
| 16 | S&F MS Pipes 150 mm dia, heavy grade, conforming to IS 1239:1990 with all fittings laid in floors or fixed to walls and ceilings etc including connection of pipe and valve by carrying out necessary welding, suitable size of nuts and bolts, washers etc including necessary supporting arrangement for fixing rising pipe in high rise bldg and scoffolding works up to 4th floor complete all as specified and directed .Note: (i) Care of labours working on multistoried bldg shall be the responsibility of the contractor .(ii) Cost of scaffolding, etc is deemed to be inmcluded in the quoted unit rate. (iii) Pipe jointing material such as flange joints, bends, and suporting clamps on wall shall be measured and paid separately. |
| 17 | All as per BOQ Serial item No. 12 above but for working in 5th floor to 12th floor complete all as specified and directed. |
| 18 | S&F MS Pipes 80 mm dia, heavy grade with flanged end conforming to IS 1239:1990 with all fittings; laid in trenches or vertically in ground including necessary connection of pipe, welding/jointing complete all as specified and directed . |
| 19 | S&F MS Pipes 150 mm dia, heavy grade conforming to IS 1239:1990 with all fittings laid in trenches or in ground including necessary connection of pipe, welding/jointing complete all as specified and directed . |
| 20 | S&F in replacement CI Foot valve of 150 mm dia conforming to IS : 4038 complete all as specified and directed. |
| 21 | S&F in replacement CI sluice valve of 150 mm dia, conforming to IS:14846, PN 1.6 with matching flanges and connection with nuts, bolts and rubber gaskets complete all as specified and directed. |
| 22 | S&F in replacement Hose box made of 18 gauge MS sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard fixed in the premises of the bldg cabinet complete all as specified and directed. |
| 23 | S&F in replacement Hose box made of 18 gauge MS Sheet 1200mm X 900mm X 450mm. with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard fixed on floor of blg upto 4th floor complete all as specified and directed. |
| 24 | All as per BOQ Serial item No 19 above but internally fixed on floor of blg from 5th to 12 th floor and of size 1200mm X 900mm X 450mm complete all as specified and directed. |
| 25 | S&F in replacement hydrant valve single headed conforming to IS-5290 with 80 NB flanged inlet, 63mm oblique outlet, SS body, CI hand wheel F4-200 as per IS-210, phosphor Bronze string IS-7608 complete all as specified and as directed. Make :- Safex/Newage or equivalent as approved by GE |
| 26 | S&F in replacement Rubber hose reel of 20mm dia and 30 metre length with reel drum including stainles steel (SS) shut off nozzle conforming to IS 5132 complete all as specified and as directed. |
| 27 | S&F in replacement 63 mm dia 15 meter long canvas non-percolating flexible delivery hose conforming to IS 636-1988 with SS male and female delivery coupling made conforming to IS 903 complete all as specified and as directed . |
| 28 | S&F in replacement Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet,15mm bore nozzle short complete all as specified and directed. |
| 29 | S&F in replacement SS adapter for 63 mm fire hydrant valve conforming to IS: 903 complete all as specified and directed. |
| 30 | S&F in replacement Fire brigade inlet connection 150 mm dia, 4 way complete all as specified and directed.Make : Safex/New Age/ Shah Engineering Industries or euivalent as approved by GE |
| 31 | S&F in repairs fire hydrant stand post, made of 80 mm dia heavy duty MS pipe,1.5 mtr height, flanged type stand post position as per site requirment including, necessary earth work, new fibre board gasket and nut, bolt & washers complete all as specified and directed. |
| 32 | S&F in replacement Gun metal Gate valve 25mm dia complete all as specified and directed. |
| 33 | S&F in replacement Pressure guage 4\\" dial having pressure rating 0-14 Kgs for fire fightiing system complete all as specified and directed. |
| 34 | Hacking out old broken glass (any thickness, size, quality or description) from metal frames of hose box including punching or drilling out old glazing pins/spring clips complete all as specified and directed. |
| 35 | S&F Sheet glass of 4mm thickness in hose box door, ordinary quality and glazing with oil putty in rectangular shape n exc 0.5 sqm in each pane complete all as specified and directed. |
| 36 | M&L for painting Hose box, MS pipes with two coats of synthetic enamel paint red in colour over a coat of red oxide primer after removing/ scrubbing old painted/ rusted surface complete all as specified and directed. |
| 37 | Taking down carefully electric driven centrifugal pump set of any capacity from MS channels frame in foundations after disconnecting all pipes / main electric supply from motor starter panel and keeping the MS channel frame at site for repairs/painting and carrying the pump set to nearest repairing workshop including bring back after necessary repairs complete all as specified and directed. |
| 38 | M&L for Overhauling of centrifugal pump installed at pump house with cleaning, greasing, minor repairs to pump & motor including replacement of spares parts like clamps, shaft sleeve, bearing, water ring, inter stage ring, PVC air vent, Air release nozzles of brass for pump, Water deflector, impeller check nut, body stud bolt & nuts, coupling PVC bush, S nuts and bolts of iron full thread with washers,gaskets, etc & connected minor accessories including refixing all disconnected spare parts, checking for alignment with motor and reassembling of the following pump capacity complete all as specified and directed:-Note: Major spares like impeller, shaft, stage bushing, coupling, ball bearing shall be measured and paid seperately. |
| 39 | 75 HP 3 Phase . |
| 40 | Upto 20 HP 3 phase . |
| 41 | Dismantling and opening the motor from pump set in existing position and M&L for rewinding with super enamelled copper wire of suitable gauge as per existing conforming to IS 13730 and heat varnishing with all other material required for rewinding, re-assembling and refixing the same with pump in original position complete all as specified and directed for the following capacity:- |
| 42 | 75 HP 3 Phase . |
| 43 | 10/20 HP 3 phase . |
| 44 | Supply only of following spare parts for pump set including motor complete for 75 HP centrifugal pump complete all as specified and directed :- |
| 45 | Impeller CI |
| 46 | Shaft |
| 47 | Stage bushing |
| 48 | Coupling |
| 49 | Ball bearing as per sample |
| 50 | M&L for painting of 75/20 HP capacity centrifugal pump set including MS channel after removing old painted/rusted surface by paint removers such as blow lamps, scrapers etc over the surface of motor/pump/MS chanel and painting with two coat of synthetic enamelled paint over a coat of red oxide primer using spray machine and writing MES No. & Capacity using white paint on painted surface at locations as directed complete all as specified and directed. |
| 51 | M&L for Cleaning of RCC underground sump of fire hydrant pump house of 60000 Gln capacities; lifting the excess semi-solid water from the sump, removing the entire deposited sludge, mud, silt etc,; applying bleaching power and scrapping the internal wall / floor with wire brush (to remove deposited scales, mud etc from the walls / floors by using suitable tools and plants, manually from the bottom of the tank); removing the sludge/debris to a distance n.exc 50m from site where directed; opening the blocked holes etc before normalising flow of water and including writing letters with synthetic paint in date \\" Tank cleaned on : (date)\\" after cleaning just below the previous date complete all as specified and as directed. Note : Consumption of bleaching power for cleaning of tank shall not be less than 30kg. |
| 52 | S&F in replacement PVC insulated, PVC sheathed , stranded copper conductor as in flat submersible water proof cable of size 6 sqmm, 3 core, 1100 volts grade complete all as specified and directed. |
| 53 | S&F in replacement PVC insulated, PVC sheathed , stranded copper conductor as in flat submersible water proof cable of size 10 sqmm, 3 core, 1100 volts grade complete all as specified and directed. |
| 54 | S&F in repairs fully automatic (FASD) star delta starter along with single phase preventor in powder coated enclosure with PU gasket including all electric connections with Ammeter and volt meter on/off & trip indicator including protection against phase failure, phase imbalance, phase reversal for the following capacity pump complete all as specified and directed :-Make :L&T MU-G75 FASD /BCH/ Havells or equivalent as approved by GE |
| 55 | 75 HP 3 Phase . |
| 56 | 20 HP 3 phase . |
| 57 | S&F in repairs CI screwed end single air valve, size 20 mm dia as per IS:14845, PN-1.6 complete all as specified and directed. |
| 58 | M&L for carrying out general servicing and maintenance to diesel engine driven pump/fuel injection pump of capacity 85 HP including B check and service as per manufactures recommendation, overhauling including replacement of oil filter, air filter, gland packing, diesel filter with replacement of O rings, Engine Oil and toping up of Coolant up to required level, etc; required to make 100 % serviceability of the engine complete all as specified and as directed. |
| 59 | M&L for the following item for maintanance of IC Engine pump set complete all as specified and directed :- |
| 60 | Greaves lub oil |
| 61 | Lubrication oil filter and element |
| 62 | Filter element with O ring |
| 63 | Fuel insrt with O ring |
| 64 | Fuel Off sol, 12V DC with fine |
| 65 | Coolant additive |
| 66 | Battery cable 2 PC set |
| 67 | Oil pressure switch |
| 68 | Tempreture switch |
| 69 | Supply, installing, testing of battery charger suitable for 150 AH battery including taking down old one complete all as specified and directed. |
| 70 | S&F installing, testing 12 V DC battery 150AH including taking down old one complete all as specified and directed. |
| 71 | M&L for testing, checking, trial run and commissioning of 75 HP fire fighting pump set including main electric motor driven pump, suction & delivery header, valves, pressure gauges, control panel, electrical connections, earthing and all associated accessories as per NBC-2016, IS 15105 & IS 13039 standards; job includes cleaning of lines, air removal, checking of alignment, insulation resistance testing of motor, operational testing under load conditions and recording of hydraulic performance such as Head available at last point/ floor as per fire fighting parameters complete all as specified and directed. NOTE:- In case any leakage/disturbance found in pipe line/ pump contractor shall rectify all the defect . |
| 72 | S&F in replacement Mild steel cross arms, bracings, supports, clamps, and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat with red oxide Zinc Chrome and two coats of synthetic enamel paint complete all as specified and directed. |
| 73 | S&F in replacement Gland Packing of pump set / sluice valves / hydrants; any make / metal / size including washers of any shape / size to avoid water leakage as indicated complete all as specified and directed. |
| 74 | S&F in replacement MS bend 150mm dia flange type any /with angle holes, nut bolts etc complete all as specified and directed. |
| 75 | S&F in replacement flanged joints of MS pipe 150mm dia with rubber or fibre board gasket, nuts, bolts etc complete all as specified and directed. |
| 76 | All as per BOQ Serial item No 51 above but for 80mm dia pipe complete all as specified and directed. |
| 77 | M&L for construction of masonary Inspection pit of size 1000x1000x900mm internally with burnt brick (Sub class \\"B\\") full brick thick brick work in cement mortor (1:6), 10 mm thick plastering in CM (1:4) internally and externally upto 150mm below the ground level, 150mm thick PCC (1:4:8) type D-2 (using 40mm graded stone aggregated) as in foundation bed with 150mm all round ofset from outer side of brick work, 3 mm thick MS sheet cover with locking arrangement hinged with 50 x 50 x 6 mm angle iron frame embeded in PCC (1:3:6) type C-1 (using 20mm graded stone aggregated) as coping etc including painting with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer on steel surfaces including necessary earth work in any type of soil and demolition of old broken pit of any size and removal of debrish outside MoD land complete all as specified and as directed. |
| 78 | S&F in replacement Pressure switch Universal type complete all as specified and directed. Make : Danfoss / Indfoss /Honeywell or equivalent make as approved by GE |
| 79 | S&F in replacement Pressure Gauge, 100mm dia, 0 - 14 Kgs rating complete all as specified and directed. Make : H Guru /Baumer/ Mass or equivalent make as approved by GE |
| 80 | S&F in replacement of 1000 litres capacity ISI marked Rotational Molded polyethylene water storage tank (cylindrical Vertical with Close top ) hoisted and fixed in position all as Specified and directed. |
| 81 | S&F in replacement 150 mm nominal bore cast iron double flanged Non Return Valves as per IS : 5312, part- I, suitable for pressure 15 KG/cm2, including transportation to worksite, supply & fixing nuts, bolts, gaskets and washers etc. and testing complete all as specified and directed. Please Enable Macros to View BoQ information |