| 1 | Supply of PVC insulated and PVC sheathed XPLE power cable of 1.1 KV grade armoured UG aluminium conductor cable conforming to IS 7098 part 1 with up-to-date amendment of the following size as required. |
| 2 | 4 x 50 sq.mm |
| 3 | 4 x 10 sq.mm |
| 4 | 3 × 6 sq.mm |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 6 | Upto 35 sq. mm |
| 7 | Above 35 sq. mm and upto 95 sq. mm |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 9 | Up to 35 Sq mm |
| 10 | Above 35 sq. mm and upto 95 sq. mm |
| 11 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 12 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 13 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 14 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required. |
| 16 | 4 X 50 sq. mm (35 mm) |
| 17 | 4 X 10 sq. mm (25mm) |
| 18 | 3 X 10 sq. mm (22mm) |
| 19 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 20 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 21 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 22 | 4 way (4 + 12), Double door |
| 23 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper busbar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 24 | 12 way , Double door |
| 25 | 8 way , Double door |
| 26 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 27 | Single pole and neutral |
| 28 | Single pole |
| 29 | Triple pole and neutral |
| 30 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 31 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 32 | Supplying and fixing MS metal box of 200mm X 150mm X 60mm deep (nominal size) in recess with hinged door made up of 16SWG MS sheet with locking arrangement etc., with suitable size of phenolic laminated sheet cover in front including providing and fixing 04 Nos 5/6 A piano type switch, connections, painting etc. and dismantling of existing metal box at the site of work as required. |
| 33 | Supplying and fixing MS metal box with 300mm×300mm ×100mm deep(nominal size) in recess with hinged door made up of 16SWG MS sheet with locking arrangement etc., with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 5/6 A & 15/16 A piano type switches, connections, painting etc. and dismantling of existing metal box at the site of work as required. |
| 34 | Supplying and fixing of Hot press moulded SMC junction Box of size 140x140x95 with 6A SP MCB, 2/4 way strip connector including testing commissioning etc. as reqd. |
| 35 | Supplying and drawing of 2.5 Sq.mm,three core PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts, conforming to IS: 694 in the existing surface/ recessed steel/ PVC conduit and connection of the fixtures as required. |
| 36 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 37 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 38 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 39 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 40 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 41 | Group A |
| 42 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 43 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 44 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 45 | 12 Module (200mmX150mm) |
| 46 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 47 | 3 pin 5/6 A socket outlet |
| 48 | 5/6 A switch |
| 49 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 50 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 51 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 52 | Earthing with 60mm outer dia ,2 mtr length GI earthing electrode, completely filled with conductive crystalline compound ,fitted with minimum of 40x6x2000mm GI strip including 50 kgs of eco friendly maintenance free earthing compound to enhance soil conductivity and providing masonry enclosure with cover plate having locking arrangement etc at the site of work as required. |
| 53 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 54 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 55 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 56 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 57 | Supplying and fixing of single phase, 230V, 50Hz, 300mm dia sweep, 4 blade Exhaust fan with bird screen for protection against birds & foreign material and fixing on the wall surface including giving connections etc. at site of work as required. |
| 58 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 59 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 ̊C to 50 ̊C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 60 | 100 W |
| 61 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 62 | 18- 22 Watt |
| 63 | HI - WALL SPLIT SYSTEMS: Supplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system hall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only |
| 64 | 1.0 TR with 5 Star BEE Rating |
| 65 | 1.5 TR with 5 Star BEE Rating |
| 66 | Design, Fabrication, Supplying, Installation, Testing and commissioning of Concrete base Mounted Dust and vermin proof Cubicle type Feeder pillar box suitable for 3 Phase, 415v, 50 Hz 4 Wire AC Supply System fabricated in compartmentalized System made out of 14 SWG CRCA Sheet Steel with doors and painted with powder coating in approved shade, ELR with CBCT, Complete with aluminium busbars of adequate capacity for Phases & neutral, Suitable M.S Angle Base Frame of 50 X 50 mm, interconnections control wiring, including incoming and outgoing cables connections, Door Earthing 2.5 mm Flexible Copper, suitable spread terminals for MCCBs, danger plate etc as required at site of work and as directed by the Engineer in charge. of following sizes and switchgear: |
| 67 | Size: 120 x 135 x 35 cm with 2 mm CRCA Sheet with doors Bus Bar Size: 25 x 6 mm Aluminium- 4no.s- 110cm length each. Earth Bar: 25 x 3 mm Copper- 1 no.s- 140 cm length. Incoming: 4 pole MCCB, 100A, 30KA- 1 No with extended rotary handleOutgoing: 63A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle 32A, 4 pole MCCB, 25/30KA- 1 No with extended rotary handle63A, 4 Pole MCB, 10KA -04Nos 32A, 2 Pole MCB, 10KA -02Nos Metering PannelingDigital Voltmeter - 01 NosDigital Ammeter - 01 NosRYB phase indication lamps -1 set6A SP MCB for control Ckts -04 Nos |
| 68 | Supplying and fixing of 2 KVAR Box type Heavy Duty Capacitor on existing surface/Panel including giving connection etc at site of work as required. |
| 69 | Supply of 1.8m×0.9mrubber mat of 6mm thick (ISI approved) suitable for electrical works at site of work as required. |
| 70 | Dismantling of existing conduit along with aluminium wire, main board, sub-main boards, switch boards and shifting to depot stores etc., as required. |
| 71 | Removing and Refixing of existing LED batten on Surface/truss with suitable clamps ,nut and bolts etc. including giving connections etc. at site of work as required. |
| 72 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 73 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 74 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 75 | Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq.meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge |
| 76 | With cement mortar 1:4 (1 cement : 4 fine sand) |
| 77 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 78 | Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. |
| 79 | Two coats |
| 80 | Insurance and ocean shipping charges, comprising loading at the mainland port, sea carriage, unloading at the island port and related handling activities, as per existing market rates. |
| 81 | CREDIT ITEMS |
| 82 | Dismantled MS conduit pipe of different sizes, DB’s, GI wire and clamps etc. |
| 83 | Dismantled Aluminium insulated wire |
| 84 | Dismantled Box type 1x40W/Street light fitting Please Enable Macros to View BoQ information |