| 1 | WORK NAME |
| 2 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 9.0 Mtr long PCC pole of 200 Kg Working Load |
| 3 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as reqd. All as per pre approved by Engineer in- charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 4 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR LT cross arm 600 mm long with clamp |
| 5 | LT cross arm 1200 mm long with clamp |
| 6 | Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 100 mm x 70 mm |
| 7 | Supply and fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in- charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 75mm x 90mm |
| 8 | Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 9 | 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog) |
| 10 | Supply & drawing Wiring for sub mains ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 4.0 sq.mm |
| 11 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 12 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB /sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 13 | Providing and Laying RCC Foundation for Octagonal / ConicalStreet Light poles, High mast Poles as per Drawing attach at TableP-4 with Following Procedure & All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR .A) Excavation of Pit for Foundation Size upto required depth fromGround levelB) Dressing of Pit and Dry stone pitching 200 mm thick includingsupply of stones and preparing surface complete.C) Providing and laying in position cement concrete of M-10 grade of75 mm thicknessD) Reinforcement for R.C.C. work with TMT bars includingstraightening, cutting, bending, placing in position and binding allcomplete.E) Centring and shuttering including strutting , propping etc. andremoval of form work for Footing and PedestalF) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe &Foundation Bolt with template as per OEM Recommendations.G) Providing and Laying Reinforce cement Concrete of M-25 gradein Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2no. 100 mm long, 10 mm dia. Lugs on each face.Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr |
| 14 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in-charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annex ure \\"A\\" attached with this BSR. Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. Electrolytic grade Aluminium bus bar 6010 grade |
| 15 | Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . One day reserve (Analog type ) |
| 16 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting |
| 17 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. 140 Amp |
| 18 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in- charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Four pole MCB (With B/C curve tripping Characteristics) 50/63 A rating |
| 19 | P & Fixing Powder coated CRCA sheet enclosures on existing angle iron frame by means of nuts and bolts and making holes , Din rail etc. as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 1.6 mm thick |
| 20 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediatedLaboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 10.0 Sq. mm 4 core |
| 21 | 50.0 Sq. mm 3.5 core |
| 22 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. outgoing. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 23 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 24 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 50.0 Sq.mm |
| 25 | 185.0 Sq.mm |
| 26 | 10.0 Sq.mm |
| 27 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 28 | Add Extra in Item no.62.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 29 | Add Extra for Laying of one number additional XLPE power cable of11/33 KV (Earthed) voltage grade direct in ground in the sametrench in one tier horizontal formation including excavation of trenchof size additional 20 cm in width, with procedure as per followingpoints:- (a) Make a river sand bed of height 125 mm along thetrench, (b) Lay another cable in middle of trench in such manner thatspacing between another cable is 20 cm, (c) Provide sand bed ofheight 125 mm on top of the cable. (d) Lay the protective Commonburnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabsof 50 mm thickness and 225 mm wide just above the sand bedvertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfillthe excavated soil leaving 300 mm from the Ground level. (f)Lay theCable warning tape and again back-fill the remaining portion of thetrench upto the ground level and compacting the earth |
| 30 | Add Extra in Item no. 62.5 if Excavation done in Hard Rock / CCroad / TAR Road and making Good the same |
| 31 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 11 KV End Termination Kit Outdoor type 3 core 120/150/185 Sq.mm 11 KV Straight Through Joint Kit |
| 32 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR 3 core 185.0 Sq.mm |
| 33 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 34 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . 25mm x 3mm Alum. Strip |
| 35 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in-charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 36 | Supply and fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required. All as per pre approved by Engineer incharge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR B & S type hardware 45 KN |
| 37 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 38 | Dismantling of existing LT/HTelectric lines including poles/towers, ACSR conductors, guard wires, stay wire, insulators and other electrical items of the pole coming along the alignment of the road or in the plant premises and removal and transportation as well as disposal of all the items as per the direction of engineer incharge.(Serviceable material or can-dum material.) Dismantling of the Double Pole structure with mounted transformers, distribution boards G.O, D.O, street light panel, stays, earthing wire pipe, cabling,etc & installing the same transformer on the structure newly erected along with distribution board along with erection, testing and commissioning |
| 39 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on die cast housing to allow traceability/ authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR. High Power LED Flood Light Minimum lumen output 8700 lm |
| 40 | High Power LED Flood Light Minimum lumen output 14800 lm Please Enable Macros to View BoQ information |