| 1 | TYPE-IIIWiring for light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 2 | Wiring for fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 3 | Wiring for fresh air/exhaust fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 4 | Wiring for call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 5 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVCconduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 7 | 2x2.5 sqmm. + 1x2.5 sqmm. |
| 8 | 2x4 sqmm. + 1x4 sqmm. |
| 9 | 2x6 sqmm. + 1x6 sqmm. |
| 10 | 2x16 sqmm. + 1x6 sqmm. |
| 11 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 12 | 1 x 1.5 sq. mm |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 16 | 4 Way Double Door |
| 17 | 8 Way Double Door |
| 18 | 12 Way Double Door |
| 19 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/recess, complete with testing and commissioning etc. as required. |
| 20 | For 4 way, Double door SPN MCBDB |
| 21 | For 8 way, Double door SPN MCBDB |
| 22 | For 12 way, Double door SPN MCBDB |
| 23 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 24 | Supply and fixing of 240 volts C Curve 5A. To 32A. amp SP miniature circuit breaker suitable for inductive load of following poles in the existing MCB, DB complete with connection, testing and commissioning etc. |
| 25 | Supply and fixing of 100 Amp. DP MCB in existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 26 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required for AC Point |
| 27 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required for AC Point |
| 28 | 1 or 2 Module (75mmX75mm) |
| 29 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required for AC Point |
| 30 | 6 pin 15/16 A socket outlet |
| 31 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required for Gyser Point |
| 32 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc.as required for Gyser Point |
| 33 | 1 or 2 Module (75mmX75mm) |
| 34 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required for Gyser Point |
| 35 | 6 pin 15/16 A socket outlet |
| 36 | LED Batten light (System lumen efficacy ≥105 <120lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 37 | 18 - 22 watt |
| 38 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard completein all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 39 | 40 Watt |
| 40 | Supply & fixing of water tight oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming to IP65 and above protection, IK 08, High purity/ transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detacable driver set,open and short circuit protection, suitable for 24Hr continuous Operation, Compelete in all respect. CAT-AA 1100 system lumens, 110 Lm/W, PF>0.95, CRI>70, with 3 years warrantee. |
| 41 | Supply and fixing of Single LED light wall Fixture Lights suitable with 9 Watt LED Lamp B22 base. complete in all respect. (Make-Havells & Model -1Nx9W LED Lamp/LHFOFTE1TZ1W012) or Eq. |
| 42 | Supply and fixing of Angle / Batton Holder |
| 43 | Supply and fixing 9 W LED bulb |
| 44 | Supplying and fixing call bell/ buzzer suitable for single phase, 230V, complete as required. |
| 45 | Brush Less Direct Current (BLDC) Fan without Remote. Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 46 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 47 | Supply and fixing of Fresh Air Fan 300mm Sweep (Metallic) |
| 48 | Supply and fixing of Heavy Duty Exhaust Fan 300mm. Sweep 900 RPM. |
| 49 | Earthing with GI earthing plate 600mmx6mm including accessories & providing masonry encloser with cover plate havig loking arrangment & watering pipe etc. with charcoal/ coke and salt as required. |
| 50 | Providing and fixing of 25mmx5mm G.I. strip on surface or in recess for connections etc. as required. |
| 51 | Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1100 V grade on wall as directed by the Engineer-Incharge, complete in all respect including exavation and refilling. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. Size 10 sqmm 2 Core. |
| 52 | TYPE-IVWiring for light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 53 | Wiring for fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 54 | Wiring for fresh air/exhaust fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 55 | Wiring for call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group-A |
| 56 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVCconduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 57 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 58 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 59 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required for AC Point |
| 60 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required for AC Point |
| 61 | 1 or 2 Module (75mmX75mm) |
| 62 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required for AC Point |
| 63 | 6 pin 15/16 A socket outlet |
| 64 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required for Gyser Point |
| 65 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc.as required for Gyser Point |
| 66 | 1 or 2 Module (75mmX75mm) |
| 67 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required for Gyser Point |
| 68 | 6 pin 15/16 A socket outlet |
| 69 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 70 | 2x2.5 sqmm. + 1x2.5 sqmm. |
| 71 | 2x4 sqmm. + 1x4 sqmm. |
| 72 | 2x6 sqmm. + 1x6 sqmm. |
| 73 | 4x16 sqmm. + 2x6 sqmm. |
| 74 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 75 | 1 x 1.5 sq. mm |
| 76 | Supply and fixing of 4 ways Double door TPN. distribution board, 415 V, recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (without MCB/Isolator) |
| 77 | Supply and fixing of 63 Amp/415V. 4P MCB in existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 78 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 79 | 4 Way Double Door |
| 80 | 8 Way Double Door |
| 81 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/recess, complete with testing and commissioning etc. as required. |
| 82 | For 4 way, Double door SPN MCBDB |
| 83 | For 8 way, Double door SPN MCBDB |
| 84 | Supply and fixing of 240 volts C Curve 32A. amp DP miniature circuit breaker suitable for inductive load of following poles in the existing MCB, DB complete with connection, testing and commissioning etc. |
| 85 | Supply and fixing of 240 volts C Curve 5A. To 32A. amp SP miniature circuit breaker suitable for inductive load of following poles in the existing MCB, DB complete with connection, testing and commissioning etc. |
| 86 | LED Batten light (System lumen efficacy ≥105 <120lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 87 | 18 - 22 watt |
| 88 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard completein all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 89 | 40 Watt |
| 90 | Supply & fixing of water tight oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming to IP65 and above protection, IK 08, High purity/ transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detacable driver set,open and short circuit protection, suitable for 24Hr continuous Operation, Compelete in all respect. CAT-AA 1100 system lumens, 110 Lm/W, PF>0.95, CRI>70, with 3 years warrantee. |
| 91 | Supply and fixing of Single LED light wall Fixture (Lights) suitable with 9 Watt LED Lamp B22 base. complete in all respect. (Make-Havells & Model -1Nx9W LED Lamp/LHFOFTE1TZ1W012) or Eq. |
| 92 | Supply and fixing of Angle / Batton Holder |
| 93 | Supply and fixing 9 W LED bulb |
| 94 | Supplying and fixing call bell/ buzzer suitable for single phase, 230V, complete as required. |
| 95 | Brush Less Direct Current (BLDC) Fan without Remote. Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 96 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 97 | Supply and fixing of Fresh Air Fan 300mm Sweep (Metallic) |
| 98 | Supply and fixing of Heavy Duty Exhaust Fan 300mm. Sweep 900 RPM. |
| 99 | Earthing with GI earth pipe 4.5 mtr long 40mm dia including accessories & providing masonry encloser with cover plate havig loking arrangment & watering pipe etc. with charcoal/ coke and salt as required. |
| 100 | Providing and fixing of 25mmx5mm G.I. strip on surface or in recess for connections etc. as required. |
| 101 | Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1100 V grade on wall as directed by the Engineer-Incharge, complete in all respect including exavation and refilling. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. Size 10 sqmm 4 Core. Please Enable Macros to View BoQ information |