| 1 | CIVIL WORKEarth work in excavation of foundation trenches in hard soil including dressing of sides and levelling the bed up to the required depth and depositing the excavated materials away from the work site within 50m initial lead & 1.5m initial lifts with sundries & T&P required for the work complete including cost of all labour,labour cess,T&P,sundries etc. as directed by the Engineer in charge. |
| 2 | Supplying and filling in foundation and plinth with good quality river sand including watering, ramming with cost, conveyances, royalties of all materials and cost of all labour with T&P required for the work etc. complete as per specification & direction of Engineer-in-charge. |
| 3 | Providing and laying plain cement concrete of proportion (1:3:6) in foundation and floors using 4 cm. size black hard crusher broken granite stone metal and screened and washed sharp sand for mortar of approved quality and from approved quarry including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels laid in layers not exceeding 15 cm. thick in each layer including cost, conveyance, royalties of all materials and cost of all labours,labour cess, T&P etc complete as per the direction of the Engineer-in-charge. |
| 4 | Plain cement concrete (1:2:4) using 12mm size black hard crusher broken granite chips of approved quality from approved quarry including hoisting, lowering and laying concrete in layers, watering, curing etc. complete including cost, conveyance, royalties of all materials with labour,labour cess and T&P etc. required for the work complete as per the direction of the Engineer-in-charge. |
| 5 | Providing, lifting, hoisting and laying Reinforced cement concrete of M-25 grade as per approved designs and drawings having a minimum compressive strength (in work test) 250 Kg. / Square cm. in 15 cm. cubes at 28 days after mixing and test conducted in accordance with I.S. 516 using 12 mm. to 20 mm. size black hard crushed broken granite stone chips and screened and washed sharp sand for mortar of approved quality from approved quarry, washed and cleaned ( 20mm. size chips not to exceeds 25 % ) to be mixed in concrete mixture with Portland slag cement (PSC) including hoisting, lowering, laying and compaction concrete by using vibrators, watering and curing for 28 days, centering and shuttering then after dismantling and removing debris from the work site and finishing the exposed surface smooth providing grooves or beads wherever necessary including cost, conveyance, loading, unloading, royalties and taxes of all materials and cost of all labours, sundries, T & P required of the work etc. complete in all respect as directed by the Engineer-in-Charge. But excluding cost and conveyance of M.S. rods or Tor steel and binding wires and labour charges for straightening, cutting, bending etc. of M.S. rods or tor steel tying the grills and placing in proper position. Footing. |
| 6 | COLUMN BASE FOOTING |
| 7 | COLUMN SUPER STRUCTURE |
| 8 | Ground Floor |
| 9 | First Floor |
| 10 | Second Floor |
| 11 | Third Floor |
| 12 | Head Room |
| 13 | PLINTH BAND |
| 14 | LINTEL BAND |
| 15 | Ground Floor |
| 16 | First Floor |
| 17 | Second Floor |
| 18 | Third Floor |
| 19 | FLOOR BEAM |
| 20 | Ground Floor |
| 21 | First Floor |
| 22 | Second Floor |
| 23 | Third Floor |
| 24 | Head Room |
| 25 | CHAJJA |
| 26 | Ground Floor |
| 27 | First Floor |
| 28 | Second Floor |
| 29 | Third Floor |
| 30 | Head Room |
| 31 | STAIRCASE |
| 32 | Ground Floor |
| 33 | First Floor |
| 34 | Second Floor |
| 35 | Third Floor |
| 36 | Head Room |
| 37 | ROOF SLAB |
| 38 | Ground Floor |
| 39 | First Floor |
| 40 | Second Floor |
| 41 | Third Floor |
| 42 | Head Room |
| 43 | Drain wall |
| 44 | Drain slab |
| 45 | Supplying Cutting, straightening coiled or bent up M.S. Rod or tor steel of primary steel producers such as SAIL / Tiscon / RINL / JINDAL STEEL / SHYAM STEEL (grade Fe-500D) etc. including bending, binding, welding, wastage & over lapping and jointing if necessary and tying the grills and placing in position as required for R.C.C. Work and for providing fan hooks as required, hoisting, lowering, laying including cost, conveyances of M.S. Rod or tor steel and binding wires of 18 to 20 gauge and labour required for the work for bending, binding and tying the grills in all floors with labour cess etc. (payment will be made on standard weight of B.I.S. for M.S. Rods or tor steel only) etc. complete as per specification & direction of Engineer-in-charge. |
| 46 | Ground Floor |
| 47 | First Floor |
| 48 | Second Floor |
| 49 | Third Floor |
| 50 | Head Room |
| 51 | Fly Ash brick masonry in cement mortar (1:6) in foundation & plinth using Fly Ash bricks of 25 x 12 x 8 cm size having a crushing strength of not less than 75 kg./sqcm with dimensional tolerance ± 2% including splays cutting circular moulding chamfering and corbelling and similar such type of works with all necessary projections watering and curing after immersing the bricks in water at least for six hours before use including cost, conveyance, and royalties of all materials with all labour,labour cess and T & P required for the work complete in all respect as per direction of Engineer-in-Charge. |
| 52 | Ground Floor |
| 53 | Fly Ash brick masonry in cement mortar (1:6) in super structure using Fly Ash bricks of 25 x 12 x 8 cm size having a crushing strength of not less than 75 kg./sqcm with dimensional tolerance ± 2% including splays cutting circular moulding chamfering and corbelling and similar such type of works with all necessary projections watering and curing after immersing the bricks in water at least for six hours before use including cost, conveyance, royalties and taxes of all materials with all labour,labour cess and T & P required for the work complete in all respect as per direction of Engineer-in-Charge. |
| 54 | First Floor |
| 55 | Second Floor |
| 56 | Third Floor |
| 57 | Head Room |
| 58 | Providing 12 mm thick cement plaster with cement mortar of mix (1:6) with screened and washed sharp sand for mortar and finished smooth to the rough surface of walls in all heights after racking out joints including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties of all materials with cost of all labour,labour cess, T&P, and scaffolding required for the work etc. complete in all respect as directed by the Engineer in charge. |
| 59 | Ground Floor |
| 60 | First Floor |
| 61 | Second Floor |
| 62 | Third Floor |
| 63 | Head Room |
| 64 | Providing 16 mm thick cement plaster with cement mortar of mix (1:6) with screened and washed sharp sand for mortar and finished smooth to the rough surface of walls in all heights after racking out joints including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties of all materials with cost of all labour,labour cess, T&P, and scaffolding required for the work etc. complete in all respect as directed by the Engineer in charge. |
| 65 | Ground Floor |
| 66 | First Floor |
| 67 | Second Floor |
| 68 | Third Floor |
| 69 | Head Room |
| 70 | Providing 6 mm thick cement plaster with cement mortar of mix (1:4) with screened and washed sharp sand for mortar and finished smooth to R.C.C. work after closed deep chipping & slurry treatment including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties of all materials with cost of all labour, T&P, and scaffolding required for the work etc. complete in all respect as directed by the Engineer in charge. |
| 71 | Ground Floor |
| 72 | First Floor |
| 73 | Second Floor |
| 74 | Third Floor |
| 75 | Head Room |
| 76 | Supplying, fitting and fixing vitrified tiles of premium grade having thickness 8mm to 10mm confirming to IS 13756 of size 600mm x 600mm plain (Ivory) of approved make (JOHNSON / SOMANY/ KAJARIA/ RAK) in floors on 20mm thick bed of C.M. (1:4) (1cement:4course sand) and filling the joint with white cement mixed with pigment to match the shades of the tileincluding cost of all materials, labour, labour cess, T&P etc. required for the work complete in all respect as directed by the Engineer in charge. |
| 77 | Ground Floor |
| 78 | First Floor |
| 79 | Second Floor |
| 80 | Third Floor |
| 81 | Fixing granite tiles of approved dimension area above 0.4 sqm (20mm thick) in floor, treads of steps and landing on 20mm thick bed of cement mortar (1:4) jointed with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing etc. complete with cost, conveyance, royalties of all materials complete in all respects as per direction of Engineer-in-Charge. |
| 82 | Ground Floor |
| 83 | First Floor |
| 84 | Second Floor |
| 85 | Third Floor |
| 86 | Fixing of Chequered tiles of premium grade having thickness 7mm to 8mm confirming to IS 13755 of size 30cm x 30cm special plain / printed series in floors over 20mm thick bed of cement mortar 1:4 jointed with cement slurry mixed with pigments to match the shade of the tiles, including rubbing & polishing etc. complete including cost, conveyance & royalties of all materials, labour with T&P complete in all respects as per direction of Engineer-in-Charge. |
| 87 | Ground Floor |
| 88 | Providing, fitting, fixing vitrified tiles of premium grade having thickness 8mm to 10mm confirming to IS 13755 of size 600mm x 600mm (homogeneous) of premium quality) of approved make (JOHNSON / SOMANY/ KAJARIA/ RAK) as directed by Engineer-in-charge in dados skirting and risers of steps on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing etc. complete with cost, conveyance, royalties of all materials all labour,labour cess complete in all respects. |
| 89 | Ground Floor |
| 90 | First Floor |
| 91 | Second Floor |
| 92 | Third Floor |
| 93 | Finishing plastered surfaces of walls with cement based wall putty (Water based) of approved make (JK White/ Birla white or equivalent make duly approved by Engineer-in-Charge) and finishing the surface smooth and even by sand papering to receive painting in walls, at all heights with staging wherever necessary with cost, conveyance, cost of all labour,labourcess, all T&P etc. required for the work complete in all respect as per the direction of the Engineer-in-charge. |
| 94 | Ground Floor |
| 95 | First Floor |
| 96 | Second Floor |
| 97 | Third Floor |
| 98 | Priming one coat with wall cement primer (water bound) to make an even finished surface in all floors and heights to wall surface of approved make and shade including sand papering, applying putty wherever necessary & cost of scaffolding, staging charges with cost, conveyance, cost of all labour,labour cess T&P etc. complete as per the direction of the Engineer-in-charge.(Make: Asian/ Berger/ Dulux/ Nerolac or equivalent make duly approved by Engineer-in-Charge). |
| 99 | Ground Floor |
| 100 | First Floor Outside |
| 101 | First Floor Inside |
| 102 | Second Floor Outside |
| 103 | Second Floor Inside |
| 104 | Third Floor Outside |
| 105 | Third Floor Inside |
| 106 | Head Room Outside |
| 107 | Head Room Inside |
| 108 | Painting two coats with plastic emulsion paint with a approved quality primer to make an even finished surface in all floors and heights to wall surface of approved make and shade including sand papering, applying putty wherever necessary & cost of scaffolding, staging charges with cost, conveyance, cost of all labour,labour cess, T&P etc. complete as per the direction of the Engineer-in-charge.(Make: Asian/ Berger/ Dulux/ Nerolac or equivalent make duly approved by Engineer-in-Charge). |
| 109 | Ground Floor |
| 110 | First Floor |
| 111 | Second Floor |
| 112 | Third Floor |
| 113 | Head Room |
| 114 | Wall painting two coats with weather coat paint (1st quality) exterior grade of approved make & approved shade over a coat of primer to make an even finished surface in all floors and heights with all scaffolding and staging charges including cost, conveyance, cost of all labours, T & P, sundries etc. as required for the work complete in all respect as per the direction of the Engineer-in-Charge.(Make: Asian/ Berger/ Dulux/ Nerolac or equivalent make duly approved by Engineer-in-Charge). |
| 115 | Ground Floor |
| 116 | First Floor |
| 117 | Second Floor |
| 118 | Third Floor |
| 119 | Head Room |
| 120 | Supplying, fitting & fixing in all floors of M.S. grills, grill gates, M.S. gates, garage door, collapsible gates with top and bottom rails, steel windows, critical frames for windows, stair case and parapet railing made out of M.S Square bar/ flat including stair case hand railing with 40mm. dia G.I.pipe etc. including painting two coats over a coat of redoxide primer as per approved drawing and design with cost of all materials & labour, labour cess, T&P, sundries etc. complete in all respect as per specification & direction of the Engineer-in-Charge. |
| 121 | Ground Floor |
| 122 | Grill |
| 123 | First Floor |
| 124 | Grill |
| 125 | Second Floor |
| 126 | Grill |
| 127 | Third Floor |
| 128 | Grill |
| 129 | Head Room |
| 130 | Grill |
| 131 | Supplying, fitting and fixing of Stainless steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x 32mm x 2mm @ 0.90mtr. C/C and stainless square pipe bracing of size 32mm x 32mm x 2mm in 3 rows in stair case as per approved design and specification, buffing, polishing etc with cost, conveyance, cost of all labour,labour cess, T&P etc. required for the work complete in all respect as per direction of the Engineer-in-charge. (Make-JINDAL). |
| 132 | Ground Floor |
| 133 | First Floor |
| 134 | Second Floor |
| 135 | Third Floor |
| 136 | Providing and fixing ISI marked 35 mm thick flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak three ply veneering with vertical grains or cross bands and face veneers on both faces of shutters of approved design including cost of all door fittings and fixtures etc. complete in all respect as per direction of the Engineer-in-charge. |
| 137 | Ground Floor |
| 138 | First Floor |
| 139 | Second Floor |
| 140 | Third Floor |
| 141 | Supplying , fitting and fixing of two track UPVC sliding window of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures etc. complete in all respect as per direction of the Engineer-in-charge.(Make-FENESTA/ Koemmerling/ Saint Gobain/ Prominance) |
| 142 | Ground Floor |
| 143 | First Floor |
| 144 | First Floor |
| 145 | Second Floor |
| 146 | TOUGHEN DOOR :-Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Item Code: 21.4.1 DSR 2019-2020) |
| 147 | Ground Floor |
| 148 | Priming one coat with any approved primmer (To Receive Enamel paint) including cost of primmer & labour to give an even shade excluding cost of primer. |
| 149 | Ground Floor |
| 150 | First floor |
| 151 | Second Floor |
| 152 | Third Floor |
| 153 | Head Room |
| 154 | Painting two coat with approved synthetic enamel paint to new wood/ iron work over a coat of Red oxide primer including cost, conveyances, royalties of all materials and cost of all labour with T&P required for the work etc. complete as per specification & direction of Engineer in charge.(Make: Asian/ Berger/ Dulux/ Nerolac or equivalent make duly approved by Engineer-in-Charge). |
| 155 | Ground Floor |
| 156 | First floor |
| 157 | Second Floor |
| 158 | Third Floor |
| 159 | Head Room |
| 160 | Providing 2.5cm thick Grading Concrete over roof slab with cement concrete (1:2:2) using 6mm size black hard granite crusher broken chips and screened & washed sharp sand for mortar and finished smooth to the rough surface of slab including watering and curing with cost, conveyance, royalties of all materials with cost of all labour, labour cess and T&P required for the work etc. complete in all respect as directed by the Engineer in charge. |
| 161 | Third Floor |
| 162 | Head Room |
| 163 | Providing fitting and fixing of false ceilling with Aluminium anodised T Section No. 3215 with 2'-0\\" center to center, L section No. 1705 upto 15 micron on 4 walls to be fixed by means of steel screw and P.V.C plug and the Aluminium grid 2'-0\\"x2'-0\\" with prelaminated particle board suspended from ceiling etc complete as per direction of Engineer-in-Charge. |
| 164 | METAL FRAME WITH JALLI (CNC CUTTING) work. :- Providing and fixing MS Metal Framed CNC Cutting Brass plate Jalli in approved size, pattern, design, shade over 30-50 mm frame and design element in 2-4 mm thick Brass plate. The fixing of Jalli should be Dry fixing i.e. to be done with S.S clamps, fixtures and fasteners of Hilti/Fischer etc. all complete as per direction of Engineer-In-Charge at all floors and all heights. |
| 165 | Providing fitting and fixing up partition walling OEL aluminum anodized section No.9210 and 9207 as single groove and double groove respectively as horizontal and vertical member and OEL section 4660 as Tapered clip for fixing up 12mm thick pre-laminated board (Nova pan make) and jointing angle No.1855 etc. including cost, conveyance, taxes of all materials with labour and T&P complete in all respect as direction of Engineer-in-Charge. |
| 166 | 10mm Thick Plain Glass |
| 167 | Supplying and fixing of 80mm thick cement concrete interlocking paver block of M-35 grade of approved make, design, colour and size made by Block making machine with proper compaction laid in required pattern etc. complete in all respect conforming to IRC SP - 63:2018. |
| 168 | Construction of granular sub-base by providing of grading-VI ( close graded GRII) material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller to achieve the. |
| 169 | Clearing and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used. |
| 170 | Excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the emb. |
| 171 | Construction of embankment with approved materials deposited at site from roadway cutting and excavation from drain and foundation of other structures graded and compacted to meet requirement of table 300-2. |
| 172 | Dismantling brick or stone masonry in lime or cement mortar above 3m height including stacking the useful materials for re-use and removing the debris with in 50m lead including cost of all labour with T&P etc. complete as per the specification and direction of the Engineer-in-charge. |
| 173 | Dismantling and removing R.C.C. columns beams slab staircase landing lintels including stacking the useful materials for reuse and removing the debris within 50m lead including cost of all labour with T&P etc. complete as per the specification and direction of the Engineer-in-charge. |
| 174 | Dismantling and removing lime concrete flooring 7.5 cm to 10 cm thick including stacking the useful materials for reuse and removing the debris within 50m lead including cost of all labour with T&P etc. complete as per the specification and direction of the Engineer-in-charge. |
| 175 | Cutting of trees, including cutting of trunks, branches and removal of stumps, roots, stacking of serviceable material with all lifts and up to a lead of 1000 metres and sand filling in the depression/pit. |
| 176 | Construction of embankment with approved material obtained from borrow pits with all lifts and leads, transporting to site, spreading, grading to required slope and compacting to meet requirement of table 300-2. |
| 177 | Carriage for Disposal of Roadway cutting Earth with a lead of 5 km |
| 178 | Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density as per approved Drawing & Technical Specifications and as per Clause -406 of MoRT&H Specifications for Road & Bridge works (5th Revision) including cost, conveyance, royality & other taxes of materials, cost of labour, machinery, T&P etc complete. |
| 179 | P.C.C. M-15 in Foundation and sub structure |
| 180 | R C C M-25 in foundation |
| 181 | R C C M-25 in wall |
| 182 | Filtermedia in Abutment back |
| 183 | Providing weepholes |
| 184 | Filling Foundation & plinth with excavated earth |
| 185 | E.I. WORKRecessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/ Anchor/ Polycab/ HAVELLS/ RR KABLE/ KEI/ V-Guard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type (flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) (flame retradant type) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.N.B: 2way switch shall be used for living room for controlling room light and fan adjacent to bed. |
| 186 | GROUP-A |
| 187 | GROUP-B |
| 188 | GROUP-C |
| 189 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type)( (flame retradant type)) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 190 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type)( (flame retradant type)) with suitable size modular box & cover( flame retradant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 191 | Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type)((flame retradant type)) with suitable size modular box & cover(flame retradant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 192 | Supplying,fixing of 2 nos 6A Plug on the separate board with complete fitting by 02 no of 6A switch & socket(modular type)( (flame retradant type)) with suitable size modular box & cover( flame retradant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 193 | Supplying,fixing of 1x6A+1X1 6A Plug on the separate board with complete fitting by 01 no of 16A+1 no 6A switch & socket(modular type) ( (flame retradant type) with suitable size modular box & metallic cover plate (both side)( flame retradant type)including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 194 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)(2X1.5+1X1.5) |
| 195 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) (2X2.5+1X1.5) |
| 196 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) (2X4+1X1.5) |
| 197 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 6 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) (2X6+1X2.5) |
| 198 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI /V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 6 sq. mm copper wire for phase and neutral and 02 nos of single core 4 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallic heavy duty conduit.(LFDB TO LBDB/Medical equipement) (4X6+2X4) |
| 199 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI /V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 6 sq. mm copper wire for earth continuty conductorin 32 mm dia non metallic heavy duty conduit .(LFDB TO FLOOR PANEL TO TPN BDB power) (4X10+2X6) |
| 200 | Supply and fixing CALL bell (Ding dong type) /Buzzer on the existing switch box/cover.Make- Havells/Anchor as required as per direction of Engg.-in-Charge.All the Components should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 201 | S/F of Bakelite angle holder/batten holder (make-Anchor/Havells or equievalant reputed make A catagory ISI marked as approved )of ISI marked conforming to IS-1258/1987 in place of ceiling rose as per direction of Engg.-in-Charge .All the Components should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 202 | Sub-Head II (Light fitting Fixture & Fan) |
| 203 | Supplying, installation, of exhaust fan of heavy duty 300 mm sweep 1400 rpm with louvers (Make- Havells/Crompton/Usha/Orient/Bajaj ) of exhaust fan in the existing wall, including fixing & conntection as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years. |
| 204 | Supplying, installation, of exhaust fan of heavy duty 380 mm sweep 1400 rpm with louvers(Make- Havells/Crompton/Usha/Orient/Bajaj ) of exhaust fan in the existing wall, including fixing & conntection .as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years. |
| 205 | Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour BLDC ceiling fan with aluminium blades having wattage not more than 28W and air delivery ≥215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 4 years.(With fan Regulator) |
| 206 | S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect as per direction of Engineer in charge (Make: legrand (Myrius) /Schneider(Zencelo)/Panasonic(Vision) |
| 207 | Supplying and fixing of Energy efficient surface /recess mounted round shape 6 W LED spot luminaire of dimension of consists of white powder coated , die-cast Aluminium housing with high quality opal diffuser for glare-free uniform lighting distribution and lumen output of 660 lumens, CRI not less than 80,CCT of 6500 K,THD less than 10%, with electronic driver, internal surge protection of 2.5 KV , The fixture design should be with flicker free operations ripple <5%, L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge.( TO BE USED FOR LIVING ROOM ,BED ROOM,MEETING ROOM AND CONTROLLED BY GROUP WIRING )(Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years |
| 208 | Supplying an fixing of recess/surface mounted 2'x2'(595mmx595mmx70mm(+/-5%) square shaped LED made up of CRCA powder coated housing with lumen efficacy not less than 140lm/W and lumen output not less than 3600 lumens , CRI not less than 80, CCT of 5700-6500 degree K, THD less than 10%,internal surge protection of 3 KV, complete with Non integrated isolated electronic driver (protects the output /secondary side from any disturbance on the input / primary side ensuring safe operation)and all other accessories suitable for operation on140- 270 V, 50 Hz ,L70 @50,000 burning hrs (5 years warranty) as required as per direction of Engg.-in-Charge (Make: Panasonic/ LT/ Havells / Philips/ Wipro/ Crompton/ Bajaj) . The luminaire must be Replacement Warranty will be 5 years. |
| 209 | Supplying and fixing of Energy efficient surface /recess mounted square /round shape 18 W LED luminaire of dimension of consists of white powder coated , die-cast Alluminium housing with high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 18 watt and lumen output of 1800 lumens, , CRI not less than 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 3 KV , L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years |
| 210 | SITC of energy efficient LED tube light fittings with decorative alluminium batten and LED tube light having power rating not more than 20 watt and lumen output not less than 2200 lumen complete with electronic driver and all other accessories with diffuser having 2 years warranty i/c connection etc as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj). The luminaire should be Replacement Warranty will be 2 years . |
| 211 | SITC of Sleek LED 10 watt mirror light fitting with extruded polycarbonate housing,High optically efficient diffuser,above wash basin complete with all accessoriesetc. directly on wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj)The luminaire should be Replacement Warranty will be 2 years |
| 212 | Supply & fixing of 5watt Wall Decorative LIGHT opal glass with all accessories as per the direction of Engineer-in-charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj). The luminaire should be Replacement Warranty will be 2 years . |
| 213 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge .(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved. |
| 214 | Supplying and fixing of 32A MECHANICAL KEY Tag with 32A 2 Moduled Mechanical key tag switch & Electronic key tag etc. as requiredas required as per direction of Engg.-in-Charge.Make-Anchor/Cona/Havells |
| 215 | SITC of PIR based occupancy sensor for corridor , connected load upto 10Amp, mounting height upto 2.8 mtr and 5m diameter coverage in complete as per the direction of Engineer-in-charge. Make-Schneider/Legrand/Siemens/ABB |
| 216 | BDBS,DB,AC DB,FLOOR PANELS,MCBS |
| 217 | Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9 /ABB ITUS as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years. |
| 218 | 4 Way(8+12+12) Way TPN MCB DD 7 Segment DB Horizontal Type as per IEC 61439-3 with configuration of incomming I-8 modules,sub incommer-12 module & out going-12 modules,suitable for Flush mounting and Surface mounting with Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years (for LDB, PDB, UPSDB) |
| 219 | Supply and fixing of 12 way DD single pole and neutral sheet steel MCB distribution board 250V on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required (but with out MCB/ RCCB/ Isolator) Warranty on DB is 3 years |
| 220 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge.The MCB should be Replacement Warranty will be 1 year. |
| 221 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 415 volts, RCCB 30mA . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 1 year |
| 222 | Supplying and fixing 40 amps rating, 240 volts, C series,10KA breaking capacity, Double poles MCB of Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 year |
| 223 | Supplying and fixing 40 amps rating, 415 volts, C series,10KA breaking capacity, FOUR poles MCB of Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. .Warranty on MCB is1 year |
| 224 | Supplying and fixing 63Amps 4P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.Warranty on MCB is 1 year |
| 225 | Supplying and fixing 63Amps 2P 240 volts RCCB 30 mA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.The RCCB should be Replacement Warranty will be 1 year |
| 226 | Supplying and fixing 40-63Amps 2P 240 volts AFDD(arc fault detection device) Make-ABB S ARC1 M/Equivalent model of Schneider/Legrand/Siemens ,10KA,C,IEC-62606 for arc fault in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.Warranty on MCB is 1 year |
| 227 | Supplying and fixing of Type (I +II) 3P+N SPD with Lightening impulse discharge current I imp(10/350) µs 7kA/POLE and 25kA total and maximum discharge current Imax(8/20) msec-50kA,with response time<25 nanosec in the incommer of Distribution board, Make-LEGRAND / Siemens/ Schneider/ABB in the existing MCB DB with connections as per direction of Engg.-in-Charge.The SPD should have Replacement Warranty will be 1 year.(To be used in PDB) |
| 228 | (Earthing) INSTALLATION |
| 229 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 230 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 231 | Providing and fixing 50mm x 6 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 232 | CABLING AND END TERMINATION MAIN AREA |
| 233 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. |
| 234 | 3.5core x 150 sq mm |
| 235 | 3.5core x 240 sq mm |
| 236 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. |
| 237 | 4core x 16 sq mm |
| 238 | 3.5core x 50 sq mm |
| 239 | LAYING OF CABLE |
| 240 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 241 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 242 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 120 SQ. MM but not exceeding 400 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 243 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 244 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 400 SQ. MM direct in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 245 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in open duct etc as required as per direction of Engg.-in -charge. |
| 246 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM in open duct 400 SQ. MM direct in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 247 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM on surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 248 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 120 SQ. MM but not exceeding 400 SQ.MM on surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 249 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. |
| 250 | 3.5 core x240 sq mm |
| 251 | 3.5core x 150 sq mm |
| 252 | 4core x 16 sq mm |
| 253 | 3.5core x 50 sq mm |
| 254 | Providing,fixing and laying of following dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. |
| 255 | 50 mm dia |
| 256 | Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete with fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. |
| 257 | 200 mm dia |
| 258 | PANELS |
| 259 | MAIN CONTROL PANEL AT GF |
| 260 | S/I/T&Commissioning of CPRI Approved LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. (FOR ALL MAIN CONNECTED LOAD) as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.3P+N Type1+ 2 65 kA SPD shall be installed in the incomers.50x10mm Separate Aluminium Earth bus bar should be installed.All the incoming and outgoing feeders shall have ON/OFF/TRIP indication.Mandatory provision of cable alley is to be given.MAIN PANELIn commer-1-01 number of 400A(40%-100% I n rated) 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release ( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA).(FROM TRANSFORMER).In commer-2-01 number of 200A(40%-100% I n rated) 4P Icu=100%Ics,36kA MCCB with Thermal magnetic based release ( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA). (DG INCOMMER).Changeover-1- 01 no of 200A 4P onload changeover switch ( DG 01 NO) ( Make-LEGRAND/ Siemens/ Schneider/ABB) .Busbar-1&2 04 numbers of 500Amps al busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing) .Out going- 4 numbers of 63A rating,10 KA breaking capacity,C series, 4P MCB ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200).Out going- 02 numbers of 250A 4P MCCB,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA.out going 12 no 100A 4P 25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA).(AC,POWER BDB).Out going- 4 numbers of 40A rating,10 KA breaking capacity,C series, 4P MCB ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200)(LIGHT BDB).Instrument- (i) 06 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 02 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data for incomerALL MCCB outgoing feeders shall have digital ammeter suitable rating class 1 CT as per feeder rating.2 no. 3P+N 65kA type 1+2 SPD with 63A rating,10KA breaking capacity ,4P MCB ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200). |
| 261 | LIFT PANEL |
| 262 | SITC of LT indoor floor mounted cubical type electrical main panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder coated paint is designed as G.A drawing. (FOR LIFT)as per direction of Engg.-in-Charge. Warranty period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.Type 2 SPD(3P+N) 40ka with 63A rating,10KA breaking capacity ,4P MCB shall be installed in the incomer. 20X10MM Separate Aluminium Earth bus bar should be installed. 63amp panel board having 63A Amp 16KA 4P MCCB TMR based release with adjustable overload ,Icu=100%Ics as incommer, 100 amp electrolyte cu bus ba-1 Set, 63A Amp TPN RCCB 300mA- 1 No,25A Amp DP RCCB 30mA- 2 No,6-32A DP MCB 10ka, c series -2 No as Outgoing with ampere meter, voltmeter, toggler switch,three nos led indicator,Drum insulator,transparent isolation glass,danger Board and Rubber Mat as per the direction of site engineer in charge (make of mccb :-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA) Make of MCB-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB200(Lift Panel) |
| 263 | FLOOR POWER and LIGHT PANEL(1F-2F,3F,4F) |
| 264 | S/I/T&Commissioning of CPRI Approved LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. )as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.3P+N Type 2 40 kA SPD with 63A rating,10KA breaking capacity ,4P MCB shall be installed in the incomer.20x10mm Separate Aluminium Earth bus bar should be installed.All the incoming and outgoing feeders shall have ON/OFF/TRIP indication.In commer 1- 01 no 100A 4P MCCB Icu=100% Ics,,25Ka MCCB withTMR based release with adjustable overload ( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA).Busbar-1&2 04 numbers of 200Amps al busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing).Out going- 5 nos 40-63A 4P MCB 10kA,C series.( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200).Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 01 set digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication . |
| 265 | AC VRF OUT DOOR PANEL |
| 266 | S/I/T&Commissioning of CPRI Approved LT OUTDOOR,IP 66 floor mounted cubical type electrical main panel (for AC ODU) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.3P+N Type 2 40 kA SPD with 63A rating,10KA breaking capacity ,4P MCB shall be installed in the incomer.40x10mm Separate Aluminium Earth bus bar should be installed.All the incoming and outgoing feeders shall have ON/OFF/TRIP indication.In commer 1- 01 no 250A 4P MCCB Icu=100% Ics,,25Ka MCCB with TMR based release with adjustable overload ( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA).Busbar-1&2 04 numbers of 300Amps al busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing) .Out going- 5 nos 40A 4P RCBO,300MA. ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200).Out going- 3 nos 25A 4P RCBO,300MA. ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200).Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 01 set digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication . |
| 267 | UPS MAIN PANEL |
| 268 | S/I/T&Commissioning of CPRI Approved LT indoor floor mounted cubical type electrical ups outgoing panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. (FOR ALL MAIN CONNECTED LOAD) BUILDING POWER)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.3P+N Type 2 65 kA SPD shall be installed in the incomer.20x10mm Separate Aluminium Earth bus bar should be installed.All the incoming and outgoing feeders shall have ON/OFF/TRIP indication.In commer 1- 01 no 63A 4P MCCB Icu=100% Ics,,25Ka MCCB with TMR based release with adjustable overload ( Make-LEGRAND DPX3/ Siemens 3VA/ Schneider CVS/ABB FORMULA).Busbar-1&2 02 numbers of 100Amps al busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing).Out going- 6 nos 32A 4P MCB 10kA,C series.( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200).Out going- 4 nos 32A DP MCB 10kA,C series.( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200).Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 01 set digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication . |
| 269 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 300mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge. |
| 270 | Supplying,fixing of FLOOR RACE WAY WITH JUNCTION box GALVANIZED(GC) type AS PER EN-ISO-1461 , with internal dimensions of size 38mm(H) x 225mm(W), of MAKE- Profab/OBO/Neidax .(With all accessories,bend,cover,supporter)WITH REQUIRED SIZED JUNCTION BOX ,COVER CONNECTOR as required as per direction of Engg.-in-Charge. |
| 271 | 10 PASSENGER LIFT WITH WIRRING |
| 272 | Supply,Installation, Testing & Commissioning of of 10 Passenger lift gearless with Machine room Capacity(680Kg),Elevator B+S+G+3 Floors (6 stop) with ACVVVF drive/Control with ARD 1.25 MPS, SS honeycomb interior ,2hr fire rated door with simplex operation without attendant car position indicators,battery operated alarm bell & emegency light,SS honeycomb finish door finished car interior, recess Granite flooring ,power operated centre opening automatic sliding SS honeycomb finish doors for car entrance & hoist way entrance etc . All SS Material shall be of SS-304 Grade and the thickness shall not be less than 1.2mm. Machine beams,buffer support channels,facia plate including sills pit ladder metal screen in Elevator pit etc.as per specifiaction including cost of (i)Overload detection,(ii)Voice announcement,(iii) Intercom,(iv)Braille Buttons(V) Flat cat 6 cable provision for CCTV with all Civil & Electrical works required for installation of Elevator in the existing lift well and machine room,scaffolding ,floor cutting including Fireman's switch complete in all respect.The Elevator should be suitable for physically handicapped person. (make:OTIS/Mitsubishi/Johnson/Schindler) |
| 273 | FIRE FIGHTING |
| 274 | PUMPS AND APPURTENANCES |
| 275 | Supplying, installation, testing and commissioning of Electric Motor Driven Pressurization Terrace Pump having discharge of 900 LPM at 35 Mtr head complete with Pump Set, Electric Motor suitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame.Make-Wilo/KSB/Kirloskar/Grundfoss |
| 276 | Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable for 7.5 HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge Control panel for fire pumps for auto action.make-Legrand/schneider/Siemens/ ABB |
| 277 | Supplying, Installing, Testing and commissioning of 1100 V GRADE POWER/CONTROL CABLES :SITC of FRLS, PVC outer sheateh, steel armoured, aluminium, 1100v grade power cables with glands etc. The minimum size of the cables shall as mentioned below as per direction of engineer in charge. Make - Polycab / KEI/Gloster/RR kabel/Havells/Finolex2 C x 1.5 mmsq |
| 278 | PIPE & VALVES ETC. |
| 279 | Supplying, installation testing and commissioning of the following-: ‘C’ class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pyp kote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Make-Tata/Jindal/Sail.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete. Make-TATA/JINDAL/SAIL |
| 280 | 100mm NB |
| 281 | 80mm NB |
| 282 | 25mm NB |
| 283 | Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C.Make-Zoloto/AUDCO/Leader |
| 284 | 100mm NB |
| 285 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader |
| 286 | 100mm NB |
| 287 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru |
| 288 | Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge.Make-Danfoss/Grundfoss/Indfoss |
| 289 | Supply,Installation,Testing & Commissioning of stainless steel strainer fabricated out of 1.6 mm thick stainless steel sheet Y Stainer with 3 mm dia hloes with stainless steel flange as required. Make-Zoloto/AUDCO/Leader |
| 290 | 100mm NB |
| 291 | WET RISER CUM DOWN COMER SYSTEM |
| 292 | Providing and fixing Single headed hydrant having outlet of 63 mm dia (2.1/2”) N.B. hydrant (IS:5290) landing valve in Stainless Steel Morris Pattern instanteous coupling type TAC / LFA approved & ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc.Make-Minimax/Newage/Fireshield/SafexMake-Minimax/Newage/Fireshield/Safex |
| 293 | Supply,Installation,Testing & Commissioning of SS short branch pipe with 63 mm male inlet and 19 mm outlet nozzle, as per IS:903 and as per direction of Engineer-in-charge.Make-Minimax/Newage/Fireshield/Safex |
| 294 | Supply,Installation,Testing & Commissioning of 63 mm NB and 15meter long RRL Fire Hose fitted with 63mm intstantaneous stainless steel male & female SS coupling, complete by GI wire binding for Internal Hydrant as per direction of Engineer-in-charge.Make-Minimax/Newage/Fireshield/Safex |
| 295 | Providing supply & fixing of MS Hose Box for of suitable size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long fire hose and a branch pipe, wall mounted type as per direction of Engineer-in-charge.Make-Minimax/Newage/Fireshield/Safex |
| 296 | Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing first aid hose reel made from MS sheet and waterways and moving parts with rubber hose of 20 mm dia. and 30 mtrs. long with ABS(Plastic) shut-off nozzle as per IS: 444/IS: 12585 Type-I., complete with all accessories as per direction of Engineer-in-charge.Make-Minimax/Newage/Fireshield/Safex |
| 297 | Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. |
| 298 | Providing, fitting & fixing of 2-Way GM fire brigade connection consisting of 63 mm dia instantaneous type male couplings with built-in check valves, 150mm dia flanged outlet complete with bolts, nuts and rubber insertions confirming to IS:904 with ISI mark including testing & commissioning the system etc. all complete as per apporoved specification & direction of EIC. Make-Minimax/Newage/Fireshield/Safex |
| 299 | EXTINGUISHER SYSTEM |
| 300 | Portable Fire Extinguisher System Supplying, installation, testing and commissioning of CO2 type Fire Extinguisher 4.5 kg capacity confirming to IS: 2878 made from ISI marked seamless cylinder confirming to IS: 7285, fitted with ISI marked controlled valve confirming to IS: 3224, high pressure 1mtr discharge hose & horn complete with initial gas charged with carrying handle & wall mounting bracket as per direction of Engineer-in-charge. Make-Safex/Fireshield/Ceasefire/FLAMEKLOG |
| 301 | Supplying, installation, testing and commissioning of ABC type fire extinguishers of 6 kg capacity including cost of all material & labour etc complete. Make-Safex/Fireshield/Ceasefire/FLAMEKLOG |
| 302 | Providing and Fixing of Mechanical Foam type fire extinguisher 9Lts. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket etc. complete, confirming to IS: 15683.Make : Fireshield/Kanex/ Safex/ ceasefire/Flameklog |
| 303 | SITC of 2 kg capacity Eco friendly stored pressure type filled with HFC 236(Clean agent fire extinguisher having zero ozone depletion potential) clean agent fire extinguisher s with safety seal,pressure gauge, controlable discharge mechanism helium leak detection tested and confirming to IS:15683 complete with initial charge as required. Make : Fireshield/Kanex/ Safex/ ceasefire/Flameklog |
| 304 | Supplying and installing at approved location approved make fire buckets at 24 gauge galvanized stseel sheet, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letter \\"FIRE\\" in black and gold. Cost shall be inclusive of Providing MS stand duly painted over a coat of primer (one stand shall be suitable for hanging 5 buckets. |
| 305 | FIRE ALARMING SYSTEM |
| 306 | Manual Fire AlarmSystem-:Supply, installation, testing and commissioning of Conventional type Main Fire Alarm Control Panel (FACP), the panel shall be conventional type fire detection and alarm system with capacity of 4 zone complete with all accessories and battery back up for 48 hours in standby mode and 15 minutes in alarm condition. The panel shall have minimum of 80 character display complete accessories. Make - System sensor / Ravel/Bosch/Agni |
| 307 | Supplying, installing, testing and commissioning of conventional type Manual call point with all accessories complete. Make - System sensor / Ravel /Bosch/Agni |
| 308 | Supplying, installing, testing and commissioning of conventional type Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make - System sensor / Ravel/Bosch/Agni Please Enable Macros to View BoQ information |
| 309 | Supplying, installing, testing and commissioning of conventional type Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make - System sensor / Ravel/Bosch/Agni Please Enable Macros to View BoQ information |