| 1 | BOQ Dated Mar 2026 |
| 2 | GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XIII are prepriced by MES under Ser No. 1 to 14. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 3 | Lumpsum price worked out by the contractor for “UG SUMP\\" as listed in Schedule ‘A’ Part - I. |
| 4 | Lumpsum price worked out by the contractor for “Site Clearance and development\\" as listed in Schedule ‘A’ Part - II. |
| 5 | Lumpsum price worked out by the contractor for \\"Road/Path/Culvert/Hardstanding\\" as listed in Schedule ‘A’ Part - III. |
| 6 | Lumpsum price worked out by the contractor for \\"Area Drainage\\" as listed in Schedule ‘A’ Part - IV. |
| 7 | Lumpsum price worked out by the contractor for \\"Rain water harvesting\\" as listed in Schedule ‘A’ Part - V. |
| 8 | Lumpsum price worked out by the contractor for “Sewage Disposal” as listed in Schedule ‘A’ Part – VI. |
| 9 | Lumpsum price worked out by the contractor for “Compound wall / Fencing & Gate” as listed in Schedule ‘A’ Part – VII. |
| 10 | Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part – VIII |
| 11 | Lumpsum price worked out by the contractor for “External Electric Supply/DG Set” as listed in Schedule ‘A’ Part –IX |
| 12 | Lumpsum price worked out by the contractor for “Lightning Protection” as listed in Schedule ‘A’ Part – X |
| 13 | Lumpsum price worked out by the contractor for “Telephone/TV cable and aviation obstruction light” as listed in Schedule ‘A’ Part –XI |
| 14 | Lumpsum price worked out by the contractor for “Fire fighting” as listed in Schedule ‘A’ Part – XII |
| 15 | Lumpsum price worked out by the contractor for “Lift” as listed in Schedule ‘A’ Part – XIII |
| 16 | Sch 'A' Part - XIV : BUILDINGS OR WORKSDESIGN & CONSTRUCTION OF STILT+5 FLOORS MARRIED ACCOMMODATION BUILDING FOR SQN LDRS UPTO 4TH FLOOR & LT TO CAPT AT 5TH FLOOR WITH RCC FRAMED STRUCTURE IN M 30 GRADE CONCRETE WITH AAC BLOCK WALL IN CEMENT MORTAR, RCC ROOF WITH PERMANENT SPECIFICATION WITH STILT PARKING, RCC OHT OF 25000 LITRE CAPACITY INCLUDING ALL INTERNAL SERVICES AS DETAILED IN SCOPE OF WORK AND OTHER DOCUMENTS OF THE TENDER COMPLETE ALL AS SPECIFIED AND SHOWN ON DRAWINGS. |
| 17 | DESIGN & CONSTRUCTION OF STILT+5FLOORS MARRIED ACCOMMODATION BUILDING FOR SGTS & BELOW RANKS WITH RCC FRAMED STRUCTURE IN M 30 GRADE CONCRETE WITH AAC BLOCK WALL IN CEMENT MORTAR, RCC ROOF WITH PERMANENT SPECIFICATION WITH STILT PARKING WITH RCC OHT OF 25000 LITRE CAPACITY INCLUDING ALL INTERNAL SERVICES AS DETAILED IN SCOPE OF WORK AND OTHER DOCUMENTS OF THE TENDER COMPLETE ALL AS SPECIFIED AND SHOWN ON DRAWINGS. |
| 18 | DESIGN & CONSTRUCTION OF SINGLE STOREY BUILDING WITH PERMANENT SPECIFICATIONS WITH RCC FRAMED STRUCTURE IN M 30 GRADE CONCRETE WITH AAC BLOCK WALL IN CEMENT MORTAR, RCC ROOF WITH WATER PROOFING TREATMENT INCLUDING ATT FOR PUMP HOUSE INCLUDING ALL INTERNAL SERVICES AS DETAILED IN SCOPE OF WORK AND OTHER DOCUMENTS OF THE TENDER COMPLETE ALL AS SPECIFIED AND SHOWN ON DRAWINGS. |
| 19 | DESIGN & CONSTRUCTION OF SOAKAGE WELL WITH TOP RING OF M25 CONCRETE INCLUDING INTERCEPTING CHAMBER AND SCREEN CHAMBER MADE OF AAC BLOCK MASONRY IN CM, RCC COVER SLAB IN M25/ SFRC COVER, INTERCONNECTING PIPES OF RCC/DWC COMPLETE FILLED WITH BRICK BATS OF SIZE 2.4 M DIA X 3.0 M EFFECTIVE DEPTH INCLUDING ALL SERVICES AS DETAILED IN SCOPE OF WORK AND OTHER DOCUMENTS OF THE TENDER COMPLETE ALL AS SPECIFIED AND SHOWN ON DRAWINGS. |
| 20 | DESIGN & CONSTRUCTION OF OF 100 USER RCC SEPTIC TANK DESIGNED TO CARRY SEWAGE AND SULLAGE WATER WITH RCC M-30 DESIGN MIX IN WALLS , BASE SLAB, BAFFLE WALLS AND ROOF SLAB INCLUDING BEAMS ETC WITH VENT INCLUDING ALL SERVICES AS DETAILED IN SCOPE OF WORK AND OTHER DOCUMENTS OF THE TENDER COMPLETE ALL AS SPECIFIED AND SHOWN ON DRAWINGS. |
| 21 | SCHEDULE \\"A\\" Part- XV (FITTINGS AND FIXTURES & MISC ITEMS) |
| 22 | SITE CLEARANCE AND DEVELOPMENT Cutting and levelling of any type of soil, waterring, ramming rolling and finishing to rquired size and shape etc of any depth and depositing the surpls earth/ soil to the site inclusing watering well ramming, rolling etc to a distance not exceeing 1km from the starting point complete all as specified and directed by Engr in Charge. |
| 23 | RAIN WATER HARVESTINGFor borewell having casing pipe 200mm dia, fix cost for MS reducer, bail plug, well cap MS strip for centring MS iron clamps , electric logging and simple strata box complete all as specified and directed. |
| 24 | Trial bore of 200mm dia upto 50mtr depth below ground level in any kind of soil strata including hard stone / boulder including electric logging, MS cap, MS flat iron clamps reducing socket etc complete all as specified and directed. |
| 25 | Additional cost for slotted pipe of 200mm dia in lieu of casing pipe of 200mm dia all as specified and directed. |
| 26 | SEWAGE DISPOSALM&L for DWC pipe of outer dia 180mm and inner dia 150mm pipes laid and joined with collars complete all as specified and directed. |
| 27 | EXTERNAL ELECTRIC SUPPLYSupply, erection, testing and commissioning of 12KV , 630 Amps, 20KA/3 Sec outdoor extensible mannual compact switchgear (Ring main Unit), 3-Way, comprising of 1 No. incoming and 2 Nos outgoing 11KA, 630Amps, 20KA SF6 Insulated Load Break switch ring main unit each with independent manual charged spring mechanism and fully rated earth swith with provision for earth and testing of cable including Air insulated cable boxes with gland plate suitable for bottom entry 3 core cable up to 185 sqmm, with provision for earthing of cable including set of hooks strong enough to take the load of entire unit while lifting by means of crane-01 set with the following standard datas/ accessories etc complete all as specified and as directed. |
| 28 | STANDARD AND MECHANICAL DATAMetal Enclosed switchgear IEC 62271 - 200 General Purpose switches IEC 60265 - 1 Disconnectors and Earthing switches IEC 62271 - 102 Switch Fuse combination IEC 62271 - 105 Circuit Breakers IEC 62271 - 100 Common clauses IEC 60694 Pressure of SF6 gas 1.4 bar at 20 0C Cable bushings DIN 47636 Temperature class -25 0C - + 40 0C OutdoorSF6 tank IP 67 Front cover IP 2X Cable cover IP 3X Enclosure IP 55 Busbars 240 mm2 Cu 240 mm2 Cu - Bolt dimensionEarth bar (external) M10Thickness of stainless steel Tank 2.5 /3.0 mm- Enclosure IS 632ELECTRICAL DATA - 12 KV - 28 KV -1 MINNominal voltage 11 KVRated frequency 50 HzRated current busbars 630 ARated current cable switch disconnector 630 ASec. rated current for trasformer T - Off 630 A To earth and between phase 75 KV-Power frequency 1 Min 28 KV |
| 29 | (I) LBS UNIT SHALL COMPRISE OF THE FOLLOWING:- 1 Safeplus type C : Cable switch 12 KV, 630 A1 Bushings outside cone interface C for connection of external busbar1 Manometer1 Busbar cover1 Snap action mech, for manual operation1 Cable cover standard with Interlocking1 Cable bushings interface C (400 bolted), 630 A standrad1 Earth Fault Indicator type EKL 1B1 Capacitive voltage indication fixed type VPIS 9-15 KV1 Cable support bars, standard for 1 - way unitSet of 630 Amps continuously rated bus bars -01 No.Set of positive standard mechanical interlocks to avoid unsafe operation -01 Set |
| 30 | Provision for pad locking for open, close , earth and test position in correct sequence -01 No Two Nos Over current and one No earth fault self powered relay with digital display -02 Nos. Mannual operated spring stored energy trip for closing and opening of the breaker.Fuses for metering and protection system. Internal bus earthing with GI flat strip of size 50 x 6 mm- 01No. Epoxy moulded low energy tripping coil for tripping the circuit breaker in fault condition -01 No. ACCESSORIES/ADD ONS Anti Reflex Operating handle -01 No Jointing box - 01 No. Space heater and thermostat - 01 No. |
| 31 | Supply, erection, testing and commissioning of 12KV, 630Amps, 20KA/3Sec outdoor Non-Extensible mannual compact switchgear (Ring Main Unit), 4-Way, comprising of 1 No.incoming and 3 Nos outgoing 11KV, 630Amps, 20KA SF6 Insulated Load Break Switch Ring Main unit each with independent manual charged spring mechanism and fully rated earth switch with provision for earth and testing of cable including Air insulated cable boxes with gland plate suitable for bottom entry 3 core cable up to 185 Sqmm, with provision for earthing of cable including set of hooks strong enough to take the load of entire unit while lifting by means of crane -01 set complete all as specified and directed |
| 32 | STANDARD AND MECHANICAL DATAMetal Enclosed switchgear IEC 62271 - 200 General Purpose switches IEC 60265 - 1 Disconnectors and Earthing switches IEC 62271 - 102 Switch Fuse combination IEC 62271 - 105 Circuit Breakers IEC 62271 - 100 Common clauses IEC 60694 Pressure of SF6 gas 1.4 bar at 20 0C Cable bushings DIN 47636 Temperature class -25 0C - + 40 0C Outdoor SF6 tank IP 67 Front cover IP 2X Cable cover IP 3X Enclosure IP 55 Busbars 240 mm2 Cu 240 mm2 Cu - Bolt dimensionEarth bar (external) M10Thickness of stainless steel Tank 2.5 /3.0 mm Enclosure IS 632 ELECTRICAL DATA - 12 KV - 28 KV 1 MINNominal voltage 11 KV Rated frequency 50 HzRated current busbars 630 A Rated current cable switch disconnector 630 ASec. rated current for trasformer T - Off 630 ATo earth and between phase 75 KV-Power frequency 1 Min 28 KV |
| 33 | (I) LBS UNIT SHALL COMPRISE OF THE FOLLOWING:- 1 Safeplus type C : Cable switch 12 KV, 630 A1 Bushings outside cone interface C for connection of external busbar1 Manometer1 Busbar cover1 Snap action mech, for manual operation1 Cable cover standard with Interlocking1 Cable bushings interface C (400 bolted), 630 A standrad1 Earth Fault Indicator type EKL 1B1 Capacitive voltage indication fixed type VPIS 9-15 KV1 Cable support bars, standard for 1 - way unitSet of 630 Amps continuously rated bus bars -01 No.Set of positive standard mechanical interlocks to avoid unsafe operation -01 Set |
| 34 | Provision for pad locking for open, close , earth and test position in correct sequence -01 No Two Nos Over current and one No earth fault self powered relay with digital display -02 Nos. Mannual operated spring stored energy trip for closing and opening of the breaker.Fuses for metering and protection system. Internal bus earthing with GI flat strip of size 50 x 6 mm - 01 No. Epoxy moulded low energy tripping coil for tripping the circuit breaker in fault condition -01 No. ACCESSORIES/ADD ONS Anti Reflex Operating handle -01 No Jointing box - 01 No. Space heater and thermostat - 01 No. |
| 35 | Supply and fixing street light brackets made out of GI tubing, light grade, 40mm bore 1200 mm Long bent to shape at 120 degree, fixed on pole by providing MS clamp made up of flat iron 50x6 mm including bolts, nuts and washer of suitable size, complete all as specified and as directed. |
| 36 | Supply and fixing of PVC Junction box with appropriate size ,including provision of bubar connectors ,MCB SP 10Amps, Loop in/Out including PVC glands, light weight pole mounting hinged type mounting of Box on pole with MS flat frame arrangement and necessary connector for looping in and looping out cable connection and suitable glands complete all as specified and as directed. |
| 37 | Supply, installation,testing and commissioning Main LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC,50 HZ, indoor type,cubicle dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting , CPRI approved,separate compartment for ACB/MCCB/metering equipments/cable gallay etc,Front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50mmx50mmx6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:- |
| 38 | Incomer (a) 600 A rated copper bus bar with colour coded heat shrinkable sleeve(b) MCCB 4 Pole, 400 A, 415V, 35 KA with microprocessor based release - 01 No. (In coming)(c) MCCB 3 Pole, 63 A, 415V, 16 KA - 07 No. (Out going) (d MCB 4P , 63A, 230 V, 10 KA - 01 Nos. (Out going) (f) Ammeter, Digital type, with suitable CTs of suitable capacity - 01 set(g) Voltmeter, Digital type of suitable capacity- 01 No.(h) R-Y-B phase indicating lamp- 01 set(j) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. |
| 39 | Supply, installation,testing and commissioning Main LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC,50 HZ, OUTDOOR type,cubicle , dust and vermin proof, air ventilation with IP-65 protection fabricated out of 3.15 mm thick CRCA sheet powder coated painting , CPRI approved,separate compartment for ACB/MCCB/metering equipments/cable gallay etc,Front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50mmx50mmx6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:- |
| 40 | Incomer (a) 600 A rated copper bus bar with colour coded heat shrinkable sleeve(b) MCCB 4 Pole, 400A, 415V, 35 KA with microprocessor based release - 01 No. (In coming)(c) MCCB 4 Pole, 160 A, 415V, 25 KA - 03 Nos. (Outgoing)(j) Voltmeter, Digital type of suitable capacity- 01 No.(k) R-Y-B phase indicating lamp- 01 set(l) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. |
| 41 | Supply, installation,testing and commissioning Main LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC,50 HZ, indoor type,cubicle dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting , CPRI approved,separate compartment for ACB/MCCB/metering equipments/cable gallay etc,Front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50mmx50mmx6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:- |
| 42 | (a) 320 A rated copper bus bar with colour coded heat shrinkable sleeve(b) MCCB 4 Pole, 160A, 415V, 25 KA with microprocessor based release - 01 No. (In coming)(c) MCCB 4 Pole, 63A, 415V, 25 KA - 02 Nos. (d) MCCB 4P, 40A, 415V, 25KA - 06 Nos. (e) MCB TPN, 63 A, 230V, - 01 No. (g) Ammeter, Digital type, with suitable CTs of suitable capacity - 01 set(h) Voltmeter, Digital type of suitable capacity- 01 No.(j) R-Y-B phase indicating lamp- 01 set(k) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. |
| 43 | STANDBY DG SETSupply, installation, testing and commissioning of silent LT diesel generator set of 82.5 kVA rating, conforming to IS/IEC 60034-1 along with AMF cum synchronizing panel with associated switchgear, control panel and exhaust piping as per latest CPCB norms (with amendments up to date at the time of execution), with necessary foundation, HSD oil storage & distribution system etc. with all necessary statutory approvals complete all as specified and directed by the engineer-in-charge. |
| 44 | The diesel generator set shall conform to the following technical specifications.[A] Engine(i) Rating: 82.5 kVA (ii) Emissions / Fuel Strategy: Low Fuel Consumption (iii) Duty: Prime Power(iv) Overload: 10% for 1 hr in every 12 hrs(v) Site Output: 82.5 kVA (vi) Governor Type: Electronic-A1(vii) Cooling System: Radiator Cooled (viii) Silencer Type: Residential [B] Starting System(i) Type of Starting System: Battery Starting System (Ele.) (ii) Type of Battery: SMF VRLA type (iii) Battery Voltage: 12 V (iv) Number of Battery: 01 Nos. (v) Ah Capacity: 90 Ah[C] Fuel Oil System(i) Fuel consumption @ 75% load: ≤ 15 litre/hr (ii) Fuel consumption @ 100% load: ≤ 21 litre/hr (iii) Fuel tank capacity: ≥ 150 litre (outside) (iv) Fuel tank thickness & MOC: 3 mm thick mild steel |
| 45 | [D] Lube Oil System(i) Lube oil sump capacity: ≥ 14 litre [E] Alternator Details(i) Rating: 82.5 kVA (ii) Voltage: 415 V (iii) Power Factor (PF): 0.8 lag (iv) Connection: 3-Phase, 4-Wire (v) Degree of Protection: IP 23(vi) Insulation: Class H (vii) Temperature Rise: Limited to Class H (viii) Excitation System: Separately Excited (ix) Frequency: 50 Hz (x) Voltage Variation: ±5% (xi) Voltage Regulation: ±1%[F] DG Set Details(i) Mounting Type: AVM Pad |
| 46 | [G] Integrated DG Set Controller(1) Control: (i) Run/ Off / Auto Switch (ii) Emergency Stop (iii) Manual Run Stop Control Switch (iv) Idle / Run Mode Control(2) Metering (Engine): (i) Starting Battery Voltage (ii) Lube Oil Temperature & Pressure (iii) Engine coolant Temperature (iv) Coolant Pressure (v) Engine rpm (vi) Operating Hours (vii) Number of Starts(3) Electrical: (i) Current (ii) Voltage (iii) Frequency(iv) kW (v) kWh (vi) PF(vii) kVA(4) Protection / Warning (Engine): (i) Overspeed Shutdown (ii) Low Lube Oil Pressure Warning / Shutdown (iii) High coolant Temperature Warning / Shutdown |
| 47 | (iv) Low coolant Temperature Warning (v) Low Coolant Level Warning / Shutdown (vi) Low and High Battery Voltage Warning (vii) Weak Battery Warning(viii) Over Crank Shutdwn (ix) Fail to Crank Shutdown (x) Magnetic Pickup Failure Shutdown(4) Alternator: (i) Overcurrent (ii) High Voltage (iii) Low Voltage (iv) Under / Over Frequency (v) Reverse Power (kVA & kVAr) (vi) Phase Sequence(5) Misc: (i) Digital AVR (ii) Amp Sentry Protection (iii) Sensor Failure Indication (iv) Programmable Idle Speed Control (v) Digital Synchronizing Function (vi) Sync Check (vii) Synchronoscope (viii) Auto Load Sharing (ix) Compatibility to Remote Monitoring (x) Smart Starting Please Enable Macros to View BoQ information |
| 48 | (iv) Low coolant Temperature Warning (v) Low Coolant Level Warning / Shutdown (vi) Low and High Battery Voltage Warning (vii) Weak Battery Warning(viii) Over Crank Shutdwn (ix) Fail to Crank Shutdown (x) Magnetic Pickup Failure Shutdown(4) Alternator: (i) Overcurrent (ii) High Voltage (iii) Low Voltage (iv) Under / Over Frequency (v) Reverse Power (kVA & kVAr) (vi) Phase Sequence(5) Misc: (i) Digital AVR (ii) Amp Sentry Protection (iii) Sensor Failure Indication (iv) Programmable Idle Speed Control (v) Digital Synchronizing Function (vi) Sync Check (vii) Synchronoscope (viii) Auto Load Sharing (ix) Compatibility to Remote Monitoring (x) Smart Starting Please Enable Macros to View BoQ information |