| 1 | Taking down/out of old unserviceable earthing, M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised strip earth lead 32X6mm by means of bolts, nuts, check nuts and washers of galvd iron or steel. Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth lead and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover and all as shown in electrical plate No 5 of MES Standard Schedule Pt I of 2009 and also including testing of earthing, earthing value not less than 2 ohm and made of earthing test point made out of gun metal or phosphorous bronge size 75x75x25 mm complete all as specified and directed. Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover.2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. 4. Earthing will be made in the presence of JE/Engr-in-charge |
| 2 | M&L for repair and maintenance of existing chemical/conventional earthing and connected works ie. funnel, water/protection pipe, welding, brazing, earth work etc including taking out old unserviceable earthing materails , earth plates of any type /size and testing of earthing complete all as specified and directed. Note :- 1. Earth work and excavation, common salt, charcoal dust, earthing pit and cover, test point terminal block, earth enhencement compound, GI pipe etc will be measure and paid seperately under respective items of sch 'A'. 2. Earthing resistance value not less than 2 Ohm |
| 3 | S&F Galvanised steel earth plate of size 600x600x6mm complete all as specified and directed |
| 4 | S&F copper earth plate of size 600x600x3.15mm complete all as specified and directed |
| 5 | S&F GI tube 40mm bore light grade complete all as specified and as directed |
| 6 | S&F GI tube 20mm bore light grade complete all as specified and as directed |
| 7 | S&F GI funnel and wire mesh complete all as specified and as directed |
| 8 | S&F in repair earthing pit indicator of different shape, size and colour marking (Circular /tringular/ Rectengular, as per drawing) made out of 3mm thick GI sheet and 1 mtr long, 8mm dia MS rod welded with GI sheet including painting with one coat of red oxide primer and two coat synthetic enamel paints and marking earthing pit number as per digram attached complete all as specified and directed. |
| 9 | S&F common salt commercial for earthing complete all as specified and directed. |
| 10 | S&F charcoal dust/breeze for earthing pit complete all as specified and directed. |
| 11 | S&Fin repair precast earthing pit made out PCC 1:3:6 type C-1, 40 mm stone aggregate with pre cast cover slab of RCC(1:2:4) type B-1 using 20 mm graded stone aggregate reinforced with 8 mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided complete all as specified and directed. |
| 12 | S&F chemical earthing powder (earth enhencement compound) having chemical compostion Marconite/Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% in earth pit complete including all labour and earth work required at site complete all as specified and directed. |
| 13 | S&F in repair PVC chemical earthing pit and cover complete with accessories complete all as specified. |
| 14 | S&F MS wire galvainsed 4 mm dia complete with accessories all as specified. |
| 15 | S&F in repair earthing test point terminal block made of gun metal of phosphorus bronze of size 75mm x 75mm x 25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexognal head screw of brass fixed to wall complete all as specified. |
| 16 | Taking out of unservaiceable lightening conductor complete of any type any description and of any size and as directed . |
| 17 | S &F in replacement single pointed air termination aluminium rod 12mm dia and 300 mm long for lightening conductor and fix to aluminium by making holes with nuts, bolts & washers as directed by Engineer-in-Charge. |
| 18 | S &F in replacement single pointed air termination copper rod 12mm dia and 300 mm long for lightening conductor and fix to copper strips by making holes with nuts, bolts & washers as directed by Engineer-in-Charge. |
| 19 | Material and labour for re fixing of old GI / Aluminium strips with saddles and fixing screws for roof conductors and down conductors above level etc including M & L for PCC work in 1:2 :4 type B-1 using 20 mm graded stone aggregates complete all as specified and directed. Note : Cost of refixing strip of one earthing will be considered as one Job . |
| 20 | S &F in replacement GI strip of size 32 mm x6 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed |
| 21 | S &F in replacement aluminium strip of size 25 mm x3 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed |
| 22 | S &F in replacement copper strip 20 mm x3 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed |
| 23 | M&L for Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed. |
| 24 | M&L for Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 25 | M&L for Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed. |
| 26 | Taking down/out of old unserviceable earthing, Material, labour,testing and commisssioning Chemical Earthing with copper pipe electrode 3.0 M long having outer pipe dia 50mm & inner pipe dia 44mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical compostion Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% buried in ground by digging a bore of 150mm dia surrounded by soil friendly backfill compound non soluble in water including connection with Copper earth strip 20x3mm upto 7 meter length, making PCC pit of size 0.3mx0.3mx0.3m (inner size) in mix 1:3:6 type CI with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting hook made out of 8mm dia bar and testing on completion to acheive value not more than 1.0 ohm complete all as specified and directed by Engineer-in Charge. Note :- Earthing will be made in the presence of JE/Engr-in-charge |
| 27 | Taking down/out of old unserviceable earthing, Material, labour,testing and commisssioning Chemical Earthing with copper pipe electrode 3.0 M long having outer pipe dia 50mm & inner pipe dia 44mm duly filled with highly conductive and anti corrosive compound of required quantity having chemical compostion Bentonite 40%, copper sulphate 20%, Gypsom 5%, Graphite 10%, Alum 5%, Zinc sulphate 10%, Aluminium sulphate 10% buried in ground by digging a bore of 150mm dia surrounded by soil friendly backfill compound non soluble in water including connection with Copper earth strip 20x3mm upto 7 meter length, making PCC pit of size 0.3mx0.3mx0.3m (inner size) in mix 1:3:6 type CI with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting hook made out of 8mm dia bar and testing on completion to acheive value not more than 1.0 ohm complete all as specified and directed by Engineer-in Charge. Note :- Earthing will be made in the presence of JE/Engr-in-charge |