Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 2 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift |
| 3 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) ,including cost of form- work,in foundation and floors. |
| 4 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 5 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floorWith Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 6 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.. [FOR LINTEL] M-25. UP TO PLINTH LVL. |
| 7 | All works above plinth level upto floor V level |
| 8 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 9 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in .foundation and plinth in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 10 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 11 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 12 | Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. |
| 13 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick -Double leaf |
| 14 | Single leaf |
| 15 | Mild steel or iron work Fabrication of hold fast for door chaukhats and windows. |
| 16 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. 9.48.1 Fixed to steel windows by welding Grill |
| 17 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P brass/ stainless steel screws @ 200mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 18 | Using R3 series with frame (98mm & above) x (40mm & above) & both glazed and fly screen sash (30mm & above) x (55mm & above) with zinc alloy (zamak) powder coated handle on every glazed panel along with multi-point locking system, (Height upto 1.8m). |
| 19 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C.1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 20 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 21 | Fixing of steel Door & wooden chaukhats in position. |
| 22 | 15mm thick plaster with cement mortar in proportion of 1:4 cement & Coarse sand) |
| 23 | 15mm thick plaster with cement mortar in proportion of 1:4 cement & Coarse sand) |
| 24 | 15mm thick plaster wit cement mortar in proportion of 1:6 cement & Coarse sand) |
| 25 | Making grooves 10 to 12 mm widex 8mm deep in plaster of the wallor in ceiling vertically or horizontally as required. |
| 26 | 25 mm thick 1:2:4 cement concrete floor with cement approved coarse sand & 2cm graded dala stone grit laid in planels finished with 3mm floating coat of neat cement bor cement and marble dust in ratio of 5:1 as specific over and excluding base concrete and removing any overlapping mortar at the joints of the panels if any giving them a uniform finish, including supply of all materisls labour, T&P etc. required for proper completion of work |
| 27 | 40mm thick 1:2:4 cement concrete floor with cement approved coarse sand & 2cm graded dala stone grit laid in planels finished with 3mm floating coat of neat cement bor cement and marble dust in ratio of 5:1 as specific over and excluding base concrete and removing any overlapping mortar at the joints of the panels if any giving them a uniform finish, including supply of all materisls labour, T&P etc. required for proper completion of work |
| 28 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. [IN FLOORING](600X600) |
| 29 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. [IN SKIRTING](600X600) |
| 30 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing he joints with white cement and matching pigment etc., complete |
| 31 | Ground Floor |
| 32 | Ground Floor |
| 33 | Ground Floor |
| 34 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 35 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 36 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 37 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour. New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre . |
| 38 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 39 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : 4.0 mm thick glass panes (weights not less than 10 kg/ sqm). |
| 40 | Providing & fixing stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 300mm x 16mm |
| 41 | P/Fixing stainless steel tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as / IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. 250 mm x 10mm |
| 42 | As Item No.39 And 150x10mm |
| 43 | Providing & fixing stainless steel door handles with screws and 150mm long.SI marked |
| 44 | Making drain along with apron. |
| 45 | S/F of glass strips for flooring.35mm wide & 4 mm thick |
| 46 | (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge :22.7.1 With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 47 | Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil. |
| 48 | Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete. |
| 49 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 50 | Providing and fixing fly and Mosquito proof stainless steel grade 304 wire mesh gaugewith 0.5 mm dia wire and 1.4 mm wire aperture |
| 51 | Providing and fixing wire gauge shutters using With ISI marked stainless steel butt hinges required sizeof aperture 1.4 mm in both directions with wire of dia 0.63 mm, for doors, windows and clerestory windows with hinges and necessary screws :32mm thick shutters With ISI marked stainless steel butt hinges of required size Second class teak wood |
| 52 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it’s components. System shall consist of metal profiles with an universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063).HORIZONTAL EXPANSION JOINT |
| 53 | Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shallconform to ASTM 6063). VERTICAL EXPANSION JOINT |
| 54 | Providing & laying cement concrete in 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggreagate 20mm nominal size) including supply of all materials,labour and T & P etc. required for completion of work and curing complete including cost of form work in foundation and floors |
| 55 | 12.5 mm thick square edge PVC Laminated Gypsum Tile of size 595x595 mm, made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16mm thick fire retardant PVC film on the face side and 12micron metalized polyester on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyester film so as to make the tile a completely sealed unit. |
| 56 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 57 | Suspended floors, roofs, landings, balconies and access platform. with water proof ply 12 mm thick. |
| 58 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. with water proof ply 12 mm thick |
| 59 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 60 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 61 | Chequerred precast cement concrete tiles 20 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand). |
| 62 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanitycounters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cementmortar 1:4 (1 cement: 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Area of slab over 0.50 sqm PHYSICS, CHEMISTRY LAB &BIOLOGY LAB |
| 63 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete PHYSICS & CHEMISTRY LAB & BIOLOGY LAB |
| 64 | Filling of good earth for filling low land pocket from 8 km distance including loading unloading & ramming watering proper compaction with not exceeding 20 cm layer work to be executed as per direction of engineer-in-charge complete. |
| 65 | Providing and fixing wire gauge shutters using galvanized M.S. wire gauge of average width of aperture 1.4 mm in both directions with wire of dia 0.63 mm, for doors, windows and clerestory windows with hinges and necessary screws :35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size Kiln seasoned and chemically treated hollock wood |
| 66 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and lerestory windows using wire gauge with average width of aperture 1.4 mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading |
| 67 | Providing and fixing chromium plated brass curtain rod having wall thickness of 1.25mm with two chromium plated brass brackets fixed with C.P. brass screws and PVC sleeves etc., wherever necessary complete :25 mm dia |
| 68 | Finishing with Epoxy paint (two or more coats) at all locations preparedand applied as per manufacturer's specifications including appropriatepriming coat, preparation of surface, etc. complete On steel work |
| 69 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : With 4.0 mm thick glass panes. |
| 70 | Providing & fixing stainless steel sliding door bolts ISI marked required colour or shade with nuts and screws etc complete.300X12 MM |
| 71 | P/Fixing stainless steel tower bolts ISI marked to required colour or shade with necessary screws etc complete.250X10 MM |
| 72 | Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete. |
| 73 | Suspended floors, roofs, landings, balconies and accessplatform |
| 74 | Fabrication of angle iron. |
| 75 | (a) 300 mm x 10mm |
| 76 | Extra for double leaf door shutters |
| 77 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, |
| 78 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 79 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 1.0 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin- charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 80 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 81 | Ground floor |
| 82 | Providing and fixing cup board shutters with 25 mm thick veneered particle board IS : 3097 marked, exterior grade (Grade I), of approved make, including IInd class teak wood lipping of 25 mm wide x 12 mm thick with necessary screws and bright finished stainless steel piano hinges, complete as per direction of Engineer-in-Charge. |
| 83 | Fabrication of M.S. Z-section window and ventilators |
| 84 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete Size of Tile 600x600 mm |
| 85 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications Two or more coats applied on walls @ 1.25 ltr/10 sqm. over and including one coat of Special primer applied @ 0.75 ltr / 10sqm : |
| 86 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper |
| 87 | Supply and filling of cinder in sunken in portion of building including breaking into required sizes including supply of all material, labour T&P required for proper completion of the work. |
| 88 | Ground floor |
| 89 | S/F of glass strips for flooring.40mm wide & 4 mm thick |
| 90 | Aluminium sheet 26 gauge |
| 91 | 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 92 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick |
| 93 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 94 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete : |
| 95 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete : 125 mm. |
| 96 | Providing and fixing factory made ISI marked steel T Section 40x40x6 mm , windows and ventilators, side /top /centre hung, with beading and all members such as F7D, F4B, K11 B and K12 B etc. complete of standard rolled steel sections, joints mitred and flash butt welded and sash bars tenoned and riveted, including providing and fixing of hinges, pivots, including priming coat of approved steel primer, but excluding the cost of other fittings, complete all as per approved design, (sectional weight of only steel members shall be measured for payment). Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). |
| 97 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete.Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 98 | 12mm thick plaster in 1:4 on ceiling and soffits of stairs upto floor two level |
| 99 | Finishing walls with water proofing cement paint of required shade :Old work (one or more coats applied @ 2.20 kg/10 sqm) over priming coat of primer applied @ 0.80 litrs/10 sqm complete including cost of Priming coat. |
| 100 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. |
| 101 | P/F MS Grills of required pattern in frames of windows etc. with MS flats, square or round bars etc. including priming coat with approved steel primer all complete fixed to steel windows by welding. |
| 102 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80 mm thick C.C. paver block of M-35 grade with approved colour design and pattern. |
| 103 | Chequerred precast cement concrete tiles 20 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand) |
| 104 | Using grade 'A' sealing compound. |
| 105 | Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m height of wall with existing angle iron 'Y' shaped placed 2.4m or 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5mm thick) wire of high tensile strength of 165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) |
| 106 | Providing and laying in position ready mixed or site batched design mix cementconcrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete.Concrete of M10 grade with minimum cement content of 220 kg /cum |
| 107 | First Class brick work in 1:3 cement and coarse sand of 2.25 F.M. mortar in foundation and plinth including supply of all materials, labour, tools and plants etc. required for proper completion of the work. (1:6 cement & coarse sand). |
| 108 | Excavation in foundation in soilmixed with kankar required the use of special tools and plant such as pickaxes- sabbals including lift upto 1.50m and lead upto 30m and including filling watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and dosposal of surplus earth as directed by the Engineer-in-charge upto a distance of 30m from the foundation trenches. |
| 109 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to steel windows by welding |
| 110 | 2 cm thick cement piaster in dado or skirting in 1:2 consisting of one part of cement & two parts of approved coarse sand panels finished with 3 mm floating coat of cement mixed with marble dust in ratio 5:1 including supply of all material, labour, tools & plants etc. required for proper completion of work. |
| 111 | Providing and fixing ball bearing for rolling shutters. |
| 112 | Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100 mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick, 100 mm wide MS sheet duly painted over priming coat, reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc including cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge |
| 113 | Providing and fixing water closet squatting pan ( Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS:7231, Parryware/Hindware/Seabird/Orient (Coral) with all fittings and fixtures complete including cutting and making good the walls and floors wherever required. White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests |
| 114 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid |
| 115 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. |
| 116 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm or 340x410x265 mm sizes respectively. (Manual) |
| 117 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. White Agaria Marble Stone |
| 118 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 119 | Providing and fixing white vitreous china laboratory sink including making all connections excluding cost of fittings : Size 450x300x150 mm |
| 120 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Semi rigid pipe 40 mm dia |
| 121 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length 15 mm nominal bore |
| 122 | 45 cm length 15 mm nominal bore |
| 123 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in charge. |
| 124 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 125 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 a) 15 mm nominal bore |
| 126 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. ( for sink) a) 15 mm nominal bore |
| 127 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931 a) 15 mm nominal bore |
| 128 | Providing and fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore |
| 129 | Providing & Fixing Stainless Steel dustbin. |
| 130 | Providing and fixing twin coat hook complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 131 | RO Plant 40 LPH (Liter per hour) PLANT PLANT CAPACITY - 40 LPHTreated Water Quality Turbidity : <1NTUpH : 6.5-7.0Chlorides : < 10 ppm Sulphates : < 5 ppm TDS : < 150 ppm |
| 132 | Supply installation, testing and commissioning of water coolerCooling Capacity150Ltrs. / Hrs.,Storage Capacity 40 Ltrs |
| 133 | Providing and fixing of WB 46 x 36 with one pair mounting brackets, EWC & Cistern complete with fittings & seat cover, one no. hinged rail 76 cm & 4 nos. of grab rails 60 cm. |
| 134 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) 110 mm dia |
| 135 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. 110 mm |
| 136 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. Coupler 110 mm |
| 137 | Single tee with door 110x110x110 mm |
| 138 | Single tee without door 110x110x110 mm |
| 139 | Bend 87.5 degree 110 mm Bend |
| 140 | Shoe (Plain) 110 mm Shoe |
| 141 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 142 | Making khurras 45x45 cm with average minimum thickness of5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 143 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : 110mm dia pipe. |
| 144 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. Internal Toilet (Soil, Waste & Rain Water Pipe) 110 mm dia. |
| 145 | 160 mm dia.(For Storm Water in Court yard) |
| 146 | Cutting holes up to 30x30 cm in walls including making good the same: With With common burnt clay F.P.S. (non modular) bricks |
| 147 | Cutting holes up to 15x15 cm in R.C.C. floors androofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof |
| 148 | 110mm x 110mmX110mm |
| 149 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. Bend without door (45°) 110mm |
| 150 | Y' Fitting without door 110mm |
| 151 | Single Tee without door 110 mm |
| 152 | Coupler 110mm |
| 153 | 160mm |
| 154 | Clean Out Plug (COP) 110mm |
| 155 | Vent Cowl 110mm |
| 156 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc.For Wash basin & Urinal 50mm dia. Pipe |
| 157 | Providing, fixing, jointing and testing, unplasticized PVC pipes - 10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. For Wash basin & Urinal 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 158 | Elbow (90°) 50mm dia. Pipe |
| 159 | 40mm dia. Pipe |
| 160 | Elbow (45°) 50mm dia. Pipe |
| 161 | 40mm dia. Pipe |
| 162 | T fitting 50mm dia. Pipe |
| 163 | Coupler 50mm dia. Pipe |
| 164 | 40mm dia. Pipe |
| 165 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testiang of joints complete as per direction of Engineer in Charge. Concealed work including cutting chases and making good the walls etc. 15 mm dia nominal bore |
| 166 | 20 mm dia nominal bore |
| 167 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. 25mm dia nominal bore |
| 168 | 32mm dia nominal bore |
| 169 | 40mm dia nominal bore |
| 170 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc Internal work - Exposed on wall / Terrace 20 mm dia. nominal bore |
| 171 | 25 mm dia. nominal bore |
| 172 | 32 mm dia. nominal bore |
| 173 | 40 mm dia. nominal bore |
| 174 | 50 mm dia. nominal bore |
| 175 | 65 mm dia. nominal bore |
| 176 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : 20 mm diameter pipe. |
| 177 | 25 mm diameter pipe. |
| 178 | 32 mm diameter pipe. |
| 179 | 40 mm diameter pipe. |
| 180 | 50 mm diameter pipe. |
| 181 | 65 mm diameter pipe. |
| 182 | Providing and fixing gun metal gate valve with wheel of approved quality. 20mm dia nominal bore |
| 183 | 25mm dia nominal bore |
| 184 | 32mm dia nominal bore |
| 185 | 40mm dia nominal bore |
| 186 | 50mm dia nominal bore |
| 187 | 65mm dia nominal bore |
| 188 | Providing and fixing MS pipe puddle flanges of required size with 600mm long with 6mm thick MS plate of size 300mm x 300mm of suitable size properly fixed in RCC walls of water tanks, including necessary welding complete in all respect as per details shown on darwings and directions of Engineeer-in-charge for water tanks 25mm dia. |
| 189 | 40mm dia. |
| 190 | 50mm dia |
| 191 | 100mm dia. |
| 192 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 75 in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design:- With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 193 | Providing and fixing Stainless Steel AISI 304(18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40mm including painting of fittings and brackets, cutting and making good the walls wherrerever required. Kitchen sink with drain board 510x1040 mm bowl depth 250mm |
| 194 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Fire Fighting Tank Capacity |
| 195 | Supply installation, testing and commissioning of WATER DISPENSER |
| 196 | Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge. (For bath) 15 mm nominal bore |
| 197 | Providing and fixing toilet paper holder. Vitreous china |
| 198 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 199 | Providing and fixing C.P. brass shower rose with 15 or 20mm inlet 150 mm diameter |
| 200 | Providing & fixing storage type electric hot water heater 25 Litre made out of heavy gauge steel jacket finished with rust proof baked-on glossy white enamel paint, inside glass lined heavy gauge copper tank, 25 mm thick polyurethane foam insulation, thermostatically controlled immersion heater with pilot neon lamp, replaceable magnesium anode bar, suitable for 8.0 bar maximum working pressure, cold water inlet and hot water outlet pipe, suitable length of electrical cable and 15 amp 3 pin plug top, complete in all respect including testing etc. (Horizontal/Vertical) |
| 201 | 25mm dia nominal bore |
| 202 | Providing & fixing storage type electric hot water heater 25 Litre made out of heavy gauge steel jacket finished with rust proof baked-on glossy white enamel paint, inside glass lined heavy gauge copper tank, 25 mm thick polyurethane foam insulation, thermostatically controlled immersion heater with pilot neon lamp, replaceable magnesium anode bar, suitable for 8.0 bar maximum working pressure, cold water inlet and hot water outlet pipe, suitable length of electrical cable and 15 amp 3 pin plug top, complete in all respect including testing etc. (Horizontal/Vertical) |
| 203 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 204 | Providing & Fixing Stainless Steel dustbin. |
| 205 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. Internal Toilet (Soil, Waste & Rain Water Pipe) 110 mm dia. |
| 206 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 110mm x 110mmX110mm |
| 207 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :All kinds of soil Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. |
| 208 | Open timbering in trenches including shuttering and shoring complete. (Measurement to be taken of the face area timbered) Depth not exceeding 1.5 meter |
| 209 | Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto the haunches of pipes including bed concrete as per standard design 150 mm. dia. RCC Pipes |
| 210 | 250 mm. dia. RCC Pipes |
| 211 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. 150 mm. dia. RCC Pipes |
| 212 | 250 mm. dia. RCC Pipes |
| 213 | Providing and fixing square-mouth S.W. gully trap SP-1 complete with C.I. grating, brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design 150 x 100 mm size P type With common burnt clay FPS (non modular) bricks of class designation 75 |
| 214 | Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete: 100 mm diameter |
| 215 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design. Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg). With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 216 | Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :- With common burnt clay F.P.S. (non modular) bricks ofclass designation 7.5 |
| 217 | Extra for depth for manholes: Size 90x80cm With common burnt clay FPS (non modular) bricks of classdesignation 7.5 |
| 218 | Providing orange colour safety foot rests of minimum 6 mm thick plastic encapsulated as per IS:10910 on 12 mm dia steel bar conforming to IS:1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm thread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 219 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. 25 mm dia nominal bore |
| 220 | 32 mm dia nominal bore |
| 221 | 40 mm dia nominal bore |
| 222 | 50 mm dia nominal bore |
| 223 | 80 mm dia nominal bore |
| 224 | Painting G.I. pipes and fittings with two coats of anti- corrosive bitumastic paint of approved quality :- 25 mm dia nominal bore |
| 225 | 32 mm dia nominal bore |
| 226 | 40 mm dia nominal bore |
| 227 | 50 mm dia nominal bore |
| 228 | 80 mm dia nominal bore |
| 229 | Providing and filling sand of grading zone V or coarser grade alround the G.I. pipes in external work. 25 mm dia nominal bore |
| 230 | 32 mm dia nominal bore |
| 231 | 40 mm dia nominal bore |
| 232 | 50 mm dia nominal bore |
| 233 | 80 mm dia nominal bore |
| 234 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required:- 50 mm dia |
| 235 | 80 mm dia |
| 236 | Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : 25 to 40 mm nominal bore |
| 237 | 50 to 80 mm nominal bore |
| 238 | Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cementm concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design: |
| 239 | RAIN WATER HARVESTING Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil |
| 240 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. |
| 241 | In all kind of soil upto 3.0m to 4.5m. depth |
| 242 | In all kind of soil upto 4.5 m to 6.0m. depth |
| 243 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stoneaggregate 20 mm nominal size) |
| 244 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 245 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:1½:3 (1 Cement: 1½ coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size) |
| 246 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of gradeFe-500D or more. |
| 247 | 12 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) |
| 248 | Centering and shuttering including strutting, propping etc. and remova of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 249 | Suspended floors, roofs, landings, balconies and access platform |
| 250 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. M.D. -10- Circular shape 500mm internal diameter |
| 251 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. Drilling of 300mm dia bore hole manually. |
| 252 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire& labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 150 mm nominal size dia |
| 253 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 254 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per directionof Engineer-in-charge. |
| 255 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in- charge. |
| 256 | Centering and shuttering including strutting, propping etc. and remova of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and stringcourses etc. |
| 257 | BORE WELL INSTALLATIONS Transportation of Rig Machine All types of soil 350 mm dia |
| 258 | Rocky strata including Boulders 350 mm dia |
| 259 | `Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer- in-charge. |
| 260 | 150 mm nominal size dia having minimum wall thickness 5.00 mm. |
| 261 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed / plain bevel ended pipe (type A) of required dia, conforming to IS:8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge. 150 mm nominal size dia |
| 262 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 263 | Supplying & Installation of suitable Hp submersible pump B.S or K.S.B 10 HP or equivalent make with finolex cable 1x3x2.5 squmm(upto 75mtr) withflexible conduit25mm dia, electrical out door pannel with required electrical fitting such as MCB of 0-25Amp (Havell or Indocopp or MDS make), Volt & Ampere meter (AE make), single phase preventer (Minilac or VSP -1 make) starter (L&T or BCH make) etc of approved make, 40mm HDPE Pipe (25 mtr) and all accessories complete as per requirement of site. |
| 264 | In all kind of soil upto 1.5m depth |
| 265 | In all kind of soil upto 1.5m to 3.0m. depth |
| 266 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded stone aggregate 40 mm nominal size) and curing complete,including cost of form- work,in foundation and floors. |
| 267 | Class 150 bk. In 1:6 cement and coarse sand of 2.25 fineness modulous mortar in foundation & plinth including supply of materials, labour and tools & plants, etc. required for proper completion of the work. |
| 268 | Reinforcement cement concrete work in slab with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone agregrate 20mm nominal size) |
| 269 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor three level. |
| 270 | 12mm cement plaster with cement and fine sand of 1.25 F.M in 1: 6 over brick work minimum thickness not to be less than 1 cm including supply of all material, labour, tools & plants etc. required for proper completion of the work for all level. (1) 1 cement : 6 C. sand |
| 271 | 2.5 cm. (1”) thick 1:2:4 cement concrete floor with cement, approved coarse (FM 2.2 to 3.6) and 2 cm. graded approved stone ballast laid in panels finished with 3mm (1/8”) floating coat of neat cement and removing any overlapping mortar at the joints of the panels if any and giving them a uniform finish, including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 272 | Providing and fixing C.I. tee at the inlet and outlet of septic tank. |
| 273 | Providing & fixing 75mm dia vent pipes. |
| 274 | Providing & fixing of 75mm dia cast iron terminal guard. |
| 275 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. M.D. -2.5- Circular shape 450mm internal diameter |
| 276 | Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks of class designation 75 and S.W. drain pipe 100 mm diameter, 1.8m long complete as per standard design. With F.P.S. bricks |
| 277 | HANDPUMP Supply of 110mm dia plain PVC.(6kg/sqcm) pressure. |
| 278 | Supply of 110mm dia sloted PVC (6kg/sqcm) pressure. |
| 279 | Supply of P.V.C. soket 125mm dia. |
| 280 | Supply of end cap 110 mm dia. |
| 281 | Providing necessary boaring T&P including making arrangement of water for boaring 200mm dia bore hole by Rig machine in all type of streta complete item. 30 metre B.G.L. |
| 282 | Beyond 30 metre. |
| 283 | Supply & fixing of nylon jalli around the slotted pipe complete as required. |
| 284 | Lowering of 110mm dia Rogid P.v.c. pipe in bore hole including cutting jointing etc. complete. |
| 285 | Providing & packing of coarse sand around the P.v.c.pipe. |
| 286 | Supply of 32mm dia G.i.pipe B class with required fitting. ( SOR Aligarh - 2018 SI No 12 Ch- 23 ) |
| 287 | Supply of India marka - II hand pump ISI marked with cylinder & connecting rods |
| 288 | Installation of India marka - II hand pump over the bore hole as per direction of E/I |
| 289 | Development of bore by manual labour till discharge of free from turbity complete item. |
| 290 | SITC of Singal Headed Hydrant Landing Valve comprising of 80 mm dia flanged Bend 63 mm dia, with cap and chain conforming to IS:5290(Make : Newage/Minimax/Safex/Firex) |
| 291 | SITC of RRL Hose Pipe 63 mm dia × 15 Mtr. Long with GM Coupling conforming to IS : 636(Make - Newage/Jayshree/CRC) |
| 292 | SITC of Short Branch Pipe as per IS:903(Make : Newage/Safex/Firex) |
| 293 | SITC of Hose Cabinet Box of 18 SWG M.S.Sheet with glass to accommodate Hose Reel Drum with Ruber Pipe with Nozzle. 2 Nos. RRL Hose and 1 No. Branch Pipe with Nozzle |
| 294 | Providing and fixing MS Pipes conforming to IS:1239 (Medium- B class) including all fittings like anchor fasteners, brick masonry supports, couplings, bends, elbows, tees and flanges etc. welded or screwed joints as required, cutting holes and chases in brick or RCC walls and making good complete. (For Riser) 100mm dia |
| 295 | Supply, installation, testing and commissioning of Manual Swing Type First aid Fire Hose Reel conforming to IS: 444 complete with all other necessary fixing accessories. |
| 296 | Supply of Fire Man Axe. |
| 297 | Providing and fixing weather proof standard Fire Duct Door complete in all respect for internal. |
| 298 | SITC of Air cushion Tank (2000x1000)mm. |
| 299 | SITC of Air Release Valve. |
| 300 | Supply, Installation, Testing & Commissioning of NRV complete with flanges, gasket and nut bolts. 150 mm |
| 301 | SITC of Butterfly Valve complete with all respect. 150 mm |
| 302 | Supply, Installation, Testing & Commissioning of Pressure Gauge with gauge cock |
| 303 | Supply, Installation, Testing & Commissioning of Fire brigade inlet with 63 MM dia instantaneous inlet complete with all necessary fittings and MS enclosure with glass door made of 18/16 SWG sheet. 2 way |
| 304 | Supply, fixing , testing & commissioning of electrical motor driven fire pump suitable for automatic operation consisting of following : (Terrace Pump) (Make : Kirloskar/Mather+Platt) (a) Horozontally mounted, split casing, Centrifugal fire pump complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 30 meter at the highest and farthest outlet at the specified flow cmplete with necessary strainers, pressure gauge including bypass arrangement for periodic testing of the working of the pumpset with required length and size of medium class GI pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately blanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel. (b) Squirrel cage, TEFC induction motor suitable for 415 V, 3 phase having IP 55 protection and class 'B' insulation for the above pump and flexible coupling with the pump. The motor shall b rated for continuous duty and shall have HP rating necessary to drive th pump at 150% of it's rated discharge at 65% of rated head. © Common bed plate of fabricated mild steel channel or cast iron type. (d) Suitable cement concrete pump foundation and vibration clamping arrangement as required with foundation bolts, anti vibration pads, washers etc. (e) Pressure switch for automatic operation of motor including necessary wiring upto control panel. (f) Electrical Control panel with starter, 3 Pole motor protection category current limiting type MCCB, indicating light, ammeter, voltmeter, selector switches, CT's protective fuses, single phasing protection, dry suction cut off etc as requrd as per standard details. Discharge :450 liter per minute Head : 35 meter |
| 305 | Supply and fixing of ABC type (4 kg.) ISI Marked 1131 |
| 306 | Supply and fixing of CO2 gas type (4.5 kg.) ISI Marked 1132 |
| 307 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 308 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 309 | Supply and fixing of self glow type exit signage |
| 310 | Providing and placing on terrace (at all floor levels)polyethylene water storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fitting and base support for tank.[Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license] Per liters capcity. |
| 311 | Providing and fixing fire extinguisher of carbon dioxide (CO2) type consisting of brand new high pressure steel cylinder discharge tube, 1 meter long high pressure discharge hose, non conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed. 4.5 kg capacity cylinder (M.R.) |
| 312 | Providing and fixing ABC type fire extinguishers complete in all respects. Capacity 6.0 Kg. (M.R.) |
| 313 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed steel conduit, withmodular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 314 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 315 | Wiring for twin control light point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface /recessed steel conduit, 2 way modular switch, modular plate,suitable GI box and earthing the point with 1.5 sq.mm FRLSPVC insulated copper conductor single core cable etc. asrequired. |
| 316 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 317 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 318 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 319 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 320 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 321 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 322 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 323 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 324 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 325 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. 5/6 amps switch |
| 326 | 2 Way 5/6 amps switch |
| 327 | 15/16 amp switch |
| 328 | 3 pin 5/6 amp socket outlet |
| 329 | 6 pin 15/16 amp socket outlet |
| 330 | DATA outlet |
| 331 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete asrequired. |
| 332 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 333 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. 2 PAIR |
| 334 | 20PAIR |
| 335 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 2 run of cable |
| 336 | SInstallation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminatedsheet cover on the fan box etc. as required. |
| 337 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. (a): Up to 450mm sweep |
| 338 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 339 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 340 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 341 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan |
| 342 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with allaccessories including connections etc. as required. |
| 343 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 344 | Supply of recess/Surface mounting round 10-15 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 345 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips orEquivalent in approved make |
| 346 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 347 | Supply of 36W 2'X2' Square light fixture with specification complete as per architectural design. Make: Philips or Equivalent in approved make |
| 348 | 4 way (4 + 12), Double door |
| 349 | 6 way (4 + 18), Double door |
| 350 | 8 way (4 + 24), Double door |
| 351 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door |
| 352 | 8 way (4 + 24), Double door |
| 353 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. For 4 way, Double door TPN MCBDB |
| 354 | For 6 way, Double door TPN MCBDB |
| 355 | For 8 way, Double door TPN MCBDB |
| 356 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 357 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 358 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 4P |
| 359 | 40A 4P |
| 360 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required.63A 4P |
| 361 | 03 No.100 Amp 4P MCCB. (25 KA) |
| 362 | 160A 4P |
| 363 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 364 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 365 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess forconnections etc. as required. |
| 366 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess forconnections etc. as required. |
| 367 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.G |
| 368 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured/Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. 3.5C x 120 sqmm aluminium conductor, A2XWY. |
| 369 | 3.5C x 95 sqmm aluminium conductor, A2XWY. |
| 370 | 3.5C x 70 sqmm aluminium conductor, A2XWY |
| 371 | 3.5C x 50 sqmm aluminium conductor, A2XWY. |
| 372 | 3.5C x 35 sqmm aluminium conductor, A2XWY. |
| 373 | 3.5C x 25 sqmm aluminium conductor, A2XWY. |
| 374 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 375 | 4C x 10 sqmm aluminium conductor, 2XWY. |
| 376 | 2C x 16 sqmm aluminium conductor, 2XWY. |
| 377 | Supplying following 1.1kV grade, XLPE insulated, FRLS type control cables,suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation and with all components as mentioned in BOQ, specifications and schedule, complete as required. 2C X 2.5 sqmm copper conductor |
| 378 | 4C X 2.5 sqmm copper conductor |
| 379 | 6C X 2.5 sqmm copper conductor |
| 380 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE powercable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 381 | Above 35 sq. mm and upto 95 sq. mm (clamped with 1mm thick saddle) |
| 382 | Above 95 sq. mm and upto 185 sq. mm (clamped with 1mm thick saddle) |
| 383 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3½ X 120 sq. mm (50 mm) |
| 384 | 3½ X 95 sq. mm (45 mm) |
| 385 | 3½ X 70 sq. mm (38mm) |
| 386 | 3½ X 50 sq. mm (32mm) |
| 387 | 3½ X 35 sq. mm (32mm) |
| 388 | 3½ X 25 sq. mm (28mm) |
| 389 | 4 X 16 sq. mm (28mm) |
| 390 | 4 X 10 sq. mm (25mm) |
| 391 | 2C X 2.5 sqmm copper conductor (19mm) |
| 392 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 393 | Supply, Installation, Testing and Commissioning of 300mm size PVC Wall fan suitable for 230V, 50 Hz AC including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laidspecification or upto the satisfaction of engineer in charge. |
| 394 | Supply, Installation, Testing and Commissioning of 600mm size PVC Wall fan suitable for 230V, 50 Hz AC including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laidspecification or upto the satisfaction of engineer in charge. |
| 395 | S/f of 50 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 396 | LT PANEL Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications etc.complete in all respect so as to fulfill all as required. LT Panel The minimum clearances between bus bars shall be as follows : Phase to phase - minimum 20mm Phase to neutral-minimum 15mm Incoming : 1Nos 400 Amp. 4P MCCB of (36 KA) Breaking capacity Metering : 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter 1 Set of CT's one of 400/ 5Amp ratio 50/51 1 Nos. Set of Phase Indication Lamp. 1 Nos. of class-III Type SPD Bus Bar; 500 Amp.TPN aluminimum bus bar of suitable length.25KA Outgoing :Phase indication lamps on each outgoing to be provided. 02 No.160 Amp 4P MCCB. (25 KA) 03 No.100 Amp 4P MCCB. (25 KA) 02 No.63 Amp 4P MCCB. (25 KA) Panel described as above |
| 397 | Light Panel The minimum clearances between bus bars shall be as follows :Phase to phase - minimum 20mm Phase to neutral-minimum 15mm Incoming : 1Nos 160 Amp. 4P MCCB of (25 KA) Breaking capacity Metering : 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter 1 Set of CT's one of 400/ 5Amp ratio 50/51 1 Nos. Set of Phase Indication Lamp. 1 Nos. of class-III Type SPD Bus Bar : One (1) No.250 Amp.TPN aluminimum bus bar of suitable length.25KA Outgoing : Phase indication lamps on each outgoing to be provided. 08 No.63 Amp 4P MCCB. (25 KA) Panel described as above |
| 398 | Fire Panel |
| 399 | Pluming Panel |
| 400 | Supply, installation, testing & commissioing of 1 Nos. 20 kVA UPS UPS at 0.99 input power factor , inbuilt or external isolation transformer,Web SNMP as per SLD,specification given in the document with following broad features True online double conversion, IGBT Rectifier & inverter based UPS. Three phases Input/ three phase output. Input voltage operations on mains without switch over to battery : 340-478V at 100% load, 220-478 V @ 50% load. Input power factor 0.99 @ 100% linear load, input THDi ≤5% @ 100% linear load. UPS shall carry design output at 40 deg. Crest factor 3:1, . Output THD is less than 2% for full linear load & Less than 5 % for nonlinear load. Output Power factor 0.9 Over load 125% for 10 min, 150% for 1 min Parallel communication port, USB, EPO and SNMP interface, BMS interface,Dust Filter at Air Inlet point are required. LCD Display indicating all important parameters. To improve the UPS Security over LAN/WAN the SNMP card provided with UPS shall be having Cybersecurity enhancements for IEC & UL 2900-2-2 certification, including stronger encryption, configurable password policy. The card shall work on GIGABIT Speed and should support all major protocols. Input, Output, Bypass, Manual Bypass isolators shall be inbuilt inside the UPS. UPS shall be provided with Temperature Humidity Sensors to monitor Temperatureand Humidity over LAN through SNMP card Software. SMF batteries suitable for 30 Min backup on Full load at 0.8 Load P.f. with each 40kVA UPS , Battery Flexible design shall be available from 32 to 40. Battery type should be Valve regulated lead-acid (VRLA). Battery Calculations to besubmitted for approvals before supply. Battery open rack with top cover, battery interlinks, battery breaker(MCCB), Battery breaker enclosure, battery to UPS cable as required should be provided with UPS systems. Isolation Transformer shall be inbuilt at Input side of each 20kVA UPS |
| 401 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 402 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 403 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mmlong, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 404 | Fixing of lightning conductor finial (single prong) with base plateincluding holes etc. complete as required. |
| 405 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor and external lighting complete as required. (For Horizontal run) |
| 406 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 407 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. 2 Way 5/6 amps switch DATA outlet |
| 408 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan |
| 409 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 4P |
| 410 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. 100A 4P |
| 411 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 412 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured/Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. 4C x 16 sqmm aluminium conductor, 2XWY. |
| 413 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 414 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 16 sq. mm (28mm) |
| 415 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 416 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 417 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 418 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 419 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 420 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors, with connection and punching of same |
| 421 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. 10 Pair |
| 422 | Supply of LED Bracket led light complete suitable for both wall & surface complete in all respects. |
| 423 | Supplying and fixing following way, horizontal type Single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way Double door |
| 424 | 12 way Double door |
| 425 | 8 way Double door |
| 426 | 14 way Double door |
| 427 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 2P |
| 428 | S/f of 20 pair Telephone Tag Block for Floors and building with Krone connectors, with connection and punching of same |
| 429 | SUBHEAD VI-MAIN L. T. PANELS Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications LT Panel The minimum clearances between bus bars shall be as follows : Phase to phase - minimum 20mm Phase to neutral-minimum 15mm Incoming : 1Nos 100 Amp. 4P MCCB of 25kA Breaking capacity Metering : 1 Set of CT's one of 100/ 5Amp ratio for Multifunction Meter1 Nos. Set of Phase Indication Lamp. 1 Nos. of class-III Type SPD Bus Bar : 200 Amp.TPN aluminimum bus bar of suitable length.50KA Outgoing : Phase indication lamps on each outgoing to be provided. 08 No.63 Amp 2P MCB. (10 KA) 1PHASE Energy Meter Boxes Panel described as above |
| 430 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 1 or 2 Module |
| 431 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. |
| 432 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 433 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. 10 sqmm 4 core |
| 434 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 435 | Supply and laying of 3 core standered aluminium conduktor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098(Part-II with latest amendments) 11 KV grade at a depht of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks in sides and on the top put across. The armouring of cable shall be properly connected with earth condutor by clamps etc. 300 sq. mm 3 Core |
| 436 | Supply and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required. |
| 437 | Supply and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required. |
| 438 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing. |
| 439 | Supply and burring of Safe Earthing Electrode T-39 AAlloy Coated, Length 3000mm, outer pipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry |
| 440 | Supply and laying of 50mm x 6mm G.I. strip from earth electrode directly in the ground as required complete in all respects. |
| 441 | Supply and Laying of 50mm X 6 mm Copper strip from earth electrode directly in the ground as required complete in all respects. |
| 442 | Providing and fixing MV danger notice plate of 200 mm x 150 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side |
| 443 | Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as |
| 444 | Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge. |
| 445 | Supplying & Laying of 1800 mm x 900 mm X 12 mm thick chequered rubber matting of tested quality |
| 446 | Supply and fixing danger board fabricated from 10 gauge MS sheet as per IE Rules |
| 447 | S/F of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T & P for proper completion of |
| 448 | Providing & fixing in position 1000 mm wide, Electrical Insulating Mats, 2mm thick, suitable upto 1.1 KV grade including cutting to required length complete as required per specifications or upto the satisfaction of engineer-in-charge. |
| 449 | Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd. |
| 450 | Supply of Tool & First Aid Box with all necessary tools for maintenance of electrical installation & First aid. |
| 451 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12 mm thik) having 3mm thikness with Single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. |
| 452 | Supply and fixing of LED street light fitting having die cast aluminium body and diffuser with driver set suitable for 45 watt to 50 watt. Confirming to IP 66 and above protection complete in all respect. |
| 453 | Supply and fixing of 20 Amp DP MCB (10KA) (C curve) for poles |
| 454 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminiumhousing built with dirver set suitable for 65 to 80 Watt. Confirming to IP 66 protection complete in all respect. |
| 455 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. 3.5C x 300 sqmm aluminium conductor, A2XWY. |
| 456 | 3.5C x 240 sqmm aluminium conductor, A2XWY. |
| 457 | 3.5C x 150 sqmm aluminium conductor, A2XWY. |
| 458 | 3.5C x 120 sqmm aluminium conductor, A2XWY. |
| 459 | 3.5C x 95 sqmm aluminium conductor, A2XWY. |
| 460 | 3.5C x 70 sqmm aluminium conductor, A2XWY. |
| 461 | 3.5C x 50 sqmm aluminium conductor, A2XWY. |
| 462 | 3.5C x 35 sqmm aluminium conductor, A2XWY. |
| 463 | 3.5C x 25 sqmm aluminium conductor, A2XWY. |
| 464 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 465 | 4C x 10 sqmm aluminium conductor, 2XWY. |
| 466 | 2C x 16 sqmm aluminium conductor, 2XWY. |
| 467 | 2C x 10 sqmm aluminium conductor, A2XWY. |
| 468 | 2C x 6 sqmm aluminium conductor, A2XWY. |
| 469 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 1mm thick saddle) |
| 470 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3½ X 300 sq. mm (70 mm) |
| 471 | 3½ X 240 sq. mm (62mm) |
| 472 | 3½ X 185 sq. mm (57mm) |
| 473 | 2 X 16 sq. mm (22mm) |
| 474 | 2 X 10 sq. mm (19mm) |
| 475 | 2 X 6 sq. mm (19mm) |
| 476 | 2C X 2.5 sqmm copper conductor (19mm) |
| 477 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 478 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 479 | 160 mm dia (OD-200 mm & ID-175 mm nominal) |
| 480 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 481 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia |
| 482 | 150 mm dia |
| 483 | 250 mm dia |
| 484 | 300 mm dia |
| 485 | Making of following size of Cable Chamber made of 230 mm thick brick work in cement mortar (1 cement : 6 sand) with PCC 100 mm thick PCC base plastering of inner and outer surface with cement mortar including providing of Heavy Duty C.I Cover complete with digging, refilling and removal of surplus soil complete as required. 900 mm x 800 mm x 1000 mm deep |
| 486 | 600 mm x 600 mm x 800 mm deep |
| 487 | SUB-HEAD VI SUBHEAD VIII-MAIN L. T. PANELS SITC OF MAIN PANEL FEEDER PILLAR Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires/ copper strips, neutral links, control wiring with 1.5 sqmm. &2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications etc.complete in all respect so LT Panel The minimum clearances between bus bars shall be as follows : Phase to phase - minimum 20mm Phase to neutral-minimum 15mm Incoming : 1Nos 630 Amp. 4P MCCB of 36kA Breaking capacity Metering : 1 Set of CT's one of 630/ 5Amp ratio for Multifunction Meter 1 Set of CT's one of 630/ 5Amp ratio for AFCR Relay 1 Set of CT's one of 630/ 5Amp ratio for 50,50N,51,51N Relay 1 Nos. Set of Phase Indication Lamp. 1 Nos. of class-III Type SPD Bus Bar : 800 Amp.TPN aluminimum bus bar of suitable length.36KA Outgoing : Phase indication lamps on each outgoing to be provided. 03 No. 400 Amp 4P MCCB. (36 KA) 03 No. 250 Amp 4P MCCB. (36 KA) 01 No. 100 Amp 4P MCCB. (25 KA) 01 No. 63 Amp 2P MCB. (10 KA) Panel described as above |
| 488 | EM Panel The minimum clearances between bus bars shall be as follows Phase to phase - minimum 20mm Phase to neutral-minimum 15mm Incoming : 1 Nos. 250 Amp. 4P MCCB of 36kA Breaking capacity 1 Nos. 250 Amp. 4P ATS Metering : 1 Set of CT's one of 250/ 5Amp ratio for Multifunction Meter 1 Set of CT's one of 250/ 5Amp ratio for 50,50N,51,51N Relay 1 Nos. Set of Phase Indication Lamp. 1 Nos. of class-III Type SPD Bus Bar : One (1) No.300 Amp.TPN aluminimum bus bar of suitable length.25KA Outgoing : Phase indication lamps on each outgoing to be provided. 02 No.160 Amp 4P MCCB. (25 KA) 02 No.63 Amp 4P MCCB. (25 KA) 03 No.40 Amp 4P MCB. (10 KA) Panel described as above |
| 489 | CAPACITOR PANEL-120 KVAR SITC APFC Panel of 120 KVAR capacity suitable for operation on 415 + 5% Volt, 3 Phase, 50Hz, AC supply, having MPP type, resin bounded, static 10,15,25 KVAR capacitors (without oil) in tier formation complete with following TPN MCCB as incomer of the panel, 7 step microprocessor based power factor controller relay capable to select the rating from 1 KVAR to multiples thereon up to max rating of the panel, current limiting contactors for each capacitors protected with MCBs, Ammeter (Analogue type) with CTs, Voltmeter (Analogue type) selector switches indicating lights, cooling fans for panel, earthing the panel with 2 Nos. 25mm x 5mm thick GI steel flat from existing earth bar, connection of APFC panel with suitable size 3.5 core aluminium conductor armoured XLPE cable from main LT panel (maximum length of cable 10 mtrs.) and compression glands etc. as reqd. The panel should have provision of timer based circuit in APFC relay to switch ON and OFF the static part automatically as and when requried. Capacity of Static capacitors should be accommodated from the overall rating of the panel and should be designed to switch in independently. The panel should be manufactured with 1.6mm thick CRCA sheet duly powder coated. Incoming One (1) No 400 Amp. 3P MCCB of 36 KA Breaking capacity 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter 1 Set of CT's one of 400/ 5Amp ratio 55 1 Nos. Set of Phase Indication Lamp. BUS BAR 1 Set of 500 Amps TP Aluminium Bus Bars OUT GOING 02 No. 63 Amps. TP MCCB (25 KA) 04 No. 40 Amps. TP MCCB (25 KA) 01 No. 25 Amps. TP MCCB (25 KA) 01 No. 25 KVAR Capacitor Bank 01 No. 15 KVAR Capacitor Bank 06 No. 10 KVAR Capacitor Bank 02 No. 25 KVAR 7% Duty Reactor 06 No. 15 KVAR 7% Duty Reactor 01 No. 10 KVAR 7% Duty Reactor 02 No. 25 KVAR TSM 06 No. 15 KVAR TSM 01 No. 10 KVAR TSM Panel described as above |
| 490 | SFP Outdoor Type(IP 65) -1 Incoming : One (1) No 63 Amp. 4P MCCB of 25KA Breaking capacity Metering : Multifunction Meter One (1) Set of Phase Indication Lamp. Bus Bar : One (1) No. 150 Amp.TPN aluminimum bus bar of suitable length. Outgoing : Phase indication lamps on each outgoing to be provided. 6 No.20 Amp DP MCB. (10 KA) 4 No. Single Phase Timer Panel described as above |
| 491 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 492 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 493 | Supply of water tight oblong 10 Watt LED bulkhead luminaire with driver set confirming to IP 66 and above Protection . complete in all respect. |
| 494 | Supply of LED Tube Light with batten suitable for up to 1 X 20 watt LED tube light fitting including tube on Surface complete in all respect |
| 495 | [LANDSCAPING WORK] Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 496 | Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly levelling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed withsludge or / and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure). |
| 497 | Supplying and stacking of good earth at site including royalty and carriage upto 5 km lead complete (earth measured in stacks will be reduced by 20% for payment). |
| 498 | Providing and laying Neelgiri/Mexican grass turf with earth 50mm to 60mm thickness of existing ground prepared with proper level and ramming with tools wooden (Dhurmos) and than rolling the surface with light roller make the surface smoothen and light waterning with sprinkler and maintenance for 30 days or more till the grass establish properly, as per direction of officer-in-charge |
| 499 | Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20%: one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to 1.5 m complete (cost of sludge, manure or extra earth to be paid for separately) |
| 500 | Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately) Holes 60 cm dia, and 60 cm deep |
| 501 | Providing and stacking of Ficus benjamina (green) of height 150-165 cm., bushy with healthy branches and lush green foliage in big size HDPE bags as per direction of the officer-in-charge. |
| 502 | Providing and stacking of Foxtail palm of ht. 240-270 cm bottom girth 35- 40 cm well developed in big size HDPE bags as per direction of theofficer-in-charge. |
| 503 | Providing and stacking of Ficus blackii (F.vivion) of height 45-60 cm. with 6- 8 branches healthy foliage in earthen pots of size 25 cm as per direction of the officer-in-charge. |
| 504 | Providing and Displaying Ficus black vivion piller Topiary (sylinder type) well developed with fresh & healthy 180 to 210 cm ht in 40 cm Cement Pot as per direction of the officer-in-charge. |
| 505 | Providing and stacking of Plumeria alba dwarf dwarf of height 90-105 cm. with 3-4 branches and thick stem in big size HDPE bags as per direction of the officer-in-charge. |
| 506 | Providing and Displaying Bamboo Buddha Valley with fresh & healthy 5 to 6 suckers 1.80 m to 2.10m ht umbrella type well developed in 50 cm Cement Pot as per direction of the officer-in-charge. |
| 507 | Providing and stacking of Bottle palm of ht. 150-180 cm bottom girth 20-25 cm well developed in big poly bags of size 25 cm as per direction of the officer-in-charge. |
| 508 | Providing and stacking of Polyalthia pendula (Ashok Pendula) of height 180-195 cm. in gunny bag of size 30 cm as per direction of the officer-in-charge. |
| 509 | Providing & Fixing of Bolard light in park |
| 510 | ADD FOR SOLAR SYSTEM |
| 511 | ADD FOR GREEN BOARD |
| 512 | DG SETS SITC 125 KVA RADIATOR COOLED D.G. SET IN ACOUSTIC ENCLOSURE WITH AMF OR Equivalent & Exhaust System with complete Accessories. Providing, installation testing & commissioning of 'Silent Type' Diesel Generating Set along with having prime power rating 125 KVA, 415 Volts at 1500RPM, 0.8 lagging Factor at 415 V suitable for 50 Hz, 3 phase system and for 0.85 load factor and consisting of the following: Diesel Engine 4 stroke radiator cooled, electric start, of suitable bhp (CPCB-2 Compliance) having Six cylinders at 1500 RPM suitable for above output of alternator , 50% RH & at 1000 metre MSL and confirming to BS 5514, BS 649, is 10000, capable of taking 10% overloading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. The DG Set Controller shall be supplied by the same vendor of DG Set OEM. Engine Mounted Instrument Panel fitted with and having digital display for following: Start- stop switch with key. Water Temperature indication Lubrication Oil pressure indication Battery charging indication RPM indication Over Speed trip Indication Low lubrication oil Pressure trip indication Engine Hours Indication Synchronous alternator rated at 125 KVA, 415 Volts at 1500 RPM, 3 phase 50 Hz, AC Supply with 0.8 lagging power factor , 50% RH . The alternator shall be having SPDB enclosure, brushless, continuous duty, self-excited and self-regulated through AVR confirming to IS:4722/ BS 2613 suitable for tropical conditions and with class- H insulation. Alternator shall have end termination cable box on alternator to terminate the 800A Bus Duct. Alternator: Synchronous alternator rated at 125 KVA, 415 Volts at 1500 RPM, 3 phase 50 Hz, AC Supply with 0.8 lagging power factor , 50% RH . The alternator shall be having SPDB enclosure, brushless, continuous duty, self-excited and self-regulated through AVR confirming to IS:4722/ BS 2613 suitable for tropical conditions and with class- H insulation. Alternator shall have end termination cable box on alternator to terminate the 800A Bus Duct. Base Frame & Foundation Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. Fuel Tank:Daily service fuel tank of 990 litres capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C pipes of suitable dia. Complete with valves level indication & accessories as required asper specifications. Exhaust System : Dry exhaust mainfold with hospital grade exhaust silencer / Catalytic Convertor. Starting System: 24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 Nos. of batteries (25 plates, 160 AH lead Acid type) as required as per specifications. Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per specifications. The Acoustic Enclosure shall be factory fitted by the OEM Note:Foundation work for DG SETs is not included in Electrical works it will come on Civil work. |
| 513 | TRANSFORMER SITC of 400KVA 11KV/433V Dyn11 Copper Wound Oil Type Transformer with OCTC +5% to -10% in steps of 2.5% , Class of Insulation: A, Temperature rise limits of 40 deg.C over ambient of 50 degrees. Losses (As per IS tolerances) and all accessories and confirming to As per IS 1180 Level 1 & Testing parameter as per IS 2026 complete with all fittings and accessories as per specifications attached etc as required at site. Note:Foundation work for transformer is not included in Electrical works it will come on Civil work. |
| 514 | G.S.T Extra as per applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail