| 1 | Supplying & erecting inline D. P. Structure for 11/0.415 kV, 200 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 300 Amps as incomer & 6 Nos. 100 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos of Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire. D.P. Structure shall be erected in c.c. foundation complete. [DSR- 8-3-20] |
| 2 | Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 200 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45Ž by thermometer in oil and 50 Ž by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer)off load +2.5 to -5 in steps of 2.5%, having 4 number of tap positions, with standard accessories complete with test certificate with losses below 780 Watts at 50% load, 2300 Watts at 100% load as per IS:1180 (part 1) : 2014 , with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL.[DSR- 10-1-3] |
| 3 | Supplying, erecting, testing & commisioning metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and painted with one coat of red lead paint and 2 coats of enamel paint or powder coating complete as per specification no. CP/SH/CR [DSR- 6-1-1] |
| 4 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (strip) cable 11 kV(E), 3 x 185 sq. mm. aluminium conductorlaid in provided trench / pipe as per specification no. CB-HT DSR- 7-3-5 |
| 5 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL DSR NO.7-1-20 |
| 6 | Supplying & erecting G.I. pipe ‘A’ class 75 mm dia. for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE [DSR- 7-6-4] |
| 7 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete.DSR NO.7-6-12 |
| 8 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP [DSR- 9-1-4] |
| 9 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specificationno EA-EP. [DSR- 9-2-3] |
| 10 | Supplying and erecting GI earth conductor of required sizes used for earthing or any other purposes on wall with necessary GI clamps fixed on wall/cable/ conduit with screws complete. DSR NO. 9-2-5 |
| 11 | Supplying and erecting V cross arm with ISM channel of 75x40x6mm for 11kV HT OH line with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height of V cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VCA [DSR-8-3-12] |
| 12 | Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ [DSR- 8-1-3} |
| 13 | Supplying and erecting 75x40 x6mm with 4.4mm thick web and 7.3mm thick flange channel (top pin) with clamp of suitable length so as to maintain vertical clearance of 1065mm for 11kV, 1320mm for 22kV between insulators for erection of top pin insulators complete as per specification no. OH-PL/VCA [DSR-8-3-14] |
| 14 | Supplying & erecting single pole cut point channel set of for 11kV HT OH line two channel of size 100x50x6mm 1.6m long having stud angle of size 50x50x6mm 1.5m long with necessary clamps, nut bolts etc. complete as per drawing. [DSR-8-3-17] |
| 15 | Supplying and erecting ACSR conductor of size 6/1-3.60 mm complete. (Ferret) (171.3 kg/km) as per specification No. OH-CON/ACSR [DSR- 8-4-8] |
| 16 | Supplying and erecting polymer disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI [DSR-8-5-20] |
| 17 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6mm., straining screws, G.l. stay wire 7/10 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete. [DSR-8-6-1] |
| 18 | Supplying and erecting pole clamp made from 50x6mm MS flat for pole or pipe, post erected with 15mm bolts and nuts duly painted with one coat of red oxide and two coats of aluminium paint complete. [DSR-8-6-8] |
| 19 | Supplying and erecting pole clamp made from 50x10mm MS flat for pole or pipe, post erected with 15mm bolts and nuts duly painted with one coat of red oxide and two coats of aluminium paint complete. [DSR-8-6-9] |
| 20 | Making Cement concrete foundation including excavation (60 x 60 x 150)cm deep in 1:3:6 cement concrete 20 x 25 mm stone metal, (45 x 45 x 45)cm /45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (above 6m to 9m poles) DSR NO.16-3-3 |
| 21 | Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing orany other purpose). DSR NO.16-3-7 |
| 22 | Supplying and erecting double leaf hinged door each 1500 mm in width x2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD [10-5-20] |
| 23 | Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG |
| 24 | Supplying and erecting mini feeder pillar with 415V, 315-320A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket and enclosure must be dust proof, rust proof, vermin and water resistant, having slanting top and erected on angle iron/ GI frame in provided C.C. foundation complete as per specification no. SW-MFP.(5-2-2) |
| 25 | Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete.(10-5-19) |
| 26 | Supplying and spreading stone metal 25mm size for 100mm depth above the ground level complete. DSR NO. 16-2-3 |
| 27 | Supplying and erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.) DSR NO. 10-5-21 |
| 28 | Supplying, installing and testing earthing with galvanised iron earth plate size 60 x 60 x 0.6 cm complete with all accessories of GI materials & recording the results as per specification No. EA-EP DSR NO. 9-1-1 |
| 29 | Painting of steel tubular/ rail/ RSJ pole above 6.0m length along with street light pole brackets, clamps etc by scrapping the existing paint complete as per specification no CW -PTG/PTP. DSR NO. 16-4-3 |
| 30 | Supplying and erecting integrated LED flood light fitting Max. 195W IP65 & IK07 class having pressure die-cast aluminium housing, having system lumensoutput of Min. 23400 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surgeprotection of 4 kV, Life class of 50,000 Hrs at L70B50 including driver with U shaped bracket with minimum 2 Years warranty as per specification No. FGODF/FL. DSR NO. 2-3-18 |
| 31 | Supplying & erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places.as per specification no. WG-MA/BW DSR NO. 1-3-2 Please Enable Macros to View BoQ information |