| 1 | Wiring for Light point/Exhaust fan/Fan/Call Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable, (Havells/PolycabF/finolexMake) in surface/recessed Conduits laid in slabs (Including Cost of Conduit 25mm) with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified Schneider /Havells/ Legrand/Anchor roma plus/ eq. Make & shall be approved by EIC before execution of work. |
| 2 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required,ISO/IEC Certified of Havells/ Legrand/ Anchor roma plus/ Schneider/ eq. Make & shall be approved by EIC before execution of work. |
| 3 | Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/ / eq. Make to be approved by EIC) including cost of conduit |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified Havells/Legrand/Anchor roma plus/Schneider/ eq. Make & shall be approved before execution of work. |
| 5 | Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/Anchor/ / eq. Make to be approved by EIC) including cost of conduit |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified Havells/Legrand//Anchor roma plus/Schneider/ eq. Make & shall be approved by EIC before execution of work. |
| 7 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required of Havells/Legrand/ Panasonic/Anchor/Schneider/ / eq. Make to be approved by EIC |
| 8 | Supply/Fixing/Testing and Commissioning of 6Amp to 32 Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Schneider/ / eq. Make to be approved by EIC) |
| 9 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Schneider/ / eq. Make to be approved by EIC) |
| 10 | 40 Amp. |
| 11 | 63 Amp. |
| 12 | 100 Amp. |
| 13 | Supplying and Fixing of MCB 6-Way horizontal typed , sheet steel, Double Door Distribution Board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ eq. Make to be approved by EIC) |
| 14 | Supply/Installation/Testing and Commissioning of 18W + LED Surface Mounted Panel (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/HG / eq. Make to be approved by EIC. |
| 15 | Supply/Installation/Testing and Commissioning of 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells / eq. Make to be approved by EIC.(Minium 1-Star) |
| 16 | Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB of Following Sizes including connection etc USHA/Havells/ / eq. Make to be approved by EIC.(Min 1-Star) |
| 17 | Supply/Laying/Connecting and Commissioning of 35 sq.mm 2-Core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havells/Polycab/Anchor Make with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution) Please Enable Macros to View BoQ information |