| 1 | Supply installation, testing and commissioning of 25 kW Grid Connected Rooftop Solar PV System with Grid Interactive without battery should have MNRE / BIS / IEC Standards and with netmetring as per State DISCOM norms. Inverter and panels should be of same OEM with RMS and local service center support. Warrant of panel should be 12 years and performanance warrranty 24 years and inverter warranty 10 years. Make: Adani, Luminous, Tata, and Microtek |
| 2 | Rated output Power:25KW |
| 3 | Max. DC Input Power (kW):37.5 |
| 4 | Max. DC Input Voltage (V):1100 |
| 5 | Start-up Voltage (V):180 |
| 6 | MPPT Voltage Range (V):200-100 |
| 7 | Max Input Current per MPPT:32A-32A-32A |
| 8 | Number of MPPT:3 |
| 9 | Max Input Strings:6 |
| 10 | Output (AC) |
| 11 | Rated output power (kW):25 |
| 12 | Max. output power [kW] :27.5 |
| 13 | Max. output Current [A]:27.5 |
| 14 | Grid Frequency range (Hz) :50/60HZ |
| 15 | Power Factor (at rated output power) :0.8 |
| 16 | Total harmonic distortion [THDi] <3% |
| 17 | Feed-in phase/connection phase :THREE PHASE |
| 18 | Efficiency:98.505 |
| 19 | MPPT Efficiency:>99.5% |
| 20 | Inbuilt Protections:DC Reverse Polarity Protection, Short Circuit Protection, O/P Over Current Protection, O/P Over voltage protection, Insulation resistance monitoring, Residual current detection, surge protection, Islanding Protection, Temperature Protection, Integrated DC Switch (optional) |
| 21 | Interface DC Connection:MC4 connections |
| 22 | Display :LCD,2X20Z |
| 23 | Datalogger & Communication :RS485/GSM/WIFI*(Optional) |
| 24 | General Data: |
| 25 | Topology :transformarless |
| 26 | Consumption @ night :<1w |
| 27 | Operating Temperature Range :-25'cto60'c |
| 28 | Cooling Method :intelligent redundant fan cooling |
| 29 | Relative Humidity :0to 100% |
| 30 | Max. Operational Altitude :4000m |
| 31 | Noise [dBA] :<30DBA |
| 32 | Designed Lifetime :>20YEARS |
| 33 | Ingress Protection :IP66 |
| 34 | Safety/EMC Standard :BIS Certified as per IS/IEC standards |
| 35 | Inverter Techincal Date |
| 36 | Inverter Rating (KW):25KW(3PHASE) |
| 37 | Max. DC Power (kW):37.5 |
| 38 | No. of MPPT:3 |
| 39 | No. of Inputs/MPPT:6 |
| 40 | Max. Input Voltage (V):1100 |
| 41 | MPPT Voltage Range (V):200-1000 |
| 42 | Phase:415 |
| 43 | AC Voltage (V):41.8 |
| 44 | Max Output Current (A):41.8 |
| 45 | Solar Panel Specificatiaon |
| 46 | Peak Power Pmax (Wp):625 |
| 47 | Maximum Power Voltage Vmp (V):40.99 |
| 48 | Maximum Power Current Imp (A):15.13 |
| 49 | Open Circuit Voltage Voc (V):48.09 |
| 50 | Short Circuit Current Isc (A):16.16 |
| 51 | Module Efficiency (%):22.95 |
| 52 | Maximum System Voltage (V):1500V |
| 53 | NOTCH |
| 54 | Peak Power Pmax (Wp):465 |
| 55 | Maximum Power Voltage Vmp (V):38.09 |
| 56 | Maximum Power Current Imp (A):12.22 |
| 57 | Open Circuit Voltage Voc (V):45.59 |
| 58 | Short Circuit Current Isc (A):13.05 |
| 59 | Peak Power Pmax (Wp)687 |
| 60 | Maximum Power Voltage Vmp (V):40.99 |
| 61 | Maximum Power Current Imp (A):16.79 |
| 62 | Open Circuit Voltage Voc (V):48.09 |
| 63 | Short Circuit Current Isc (A):17.91 |
| 64 | Mechincal Data of Panel |
| 65 | Cell Type:TOPCON (N-TYPR) |
| 66 | No. of Cells:132 HALF CELLS(BIFACIA; SOLAR CELLS) |
| 67 | Rated Module Voltage (V):24 |
| 68 | Maximum Series Fuse Rating:30A |
| 69 | Module Dimensions (mm):2382X1134X30 |
| 70 | Module Weight (Kg):32.5 |
| 71 | Junction Box:IP68, Split Junction Box with Individual Bypass Diodes |
| 72 | Cable:300 mm Length (+ve & -ve), MC4 Compatible / MC4 Connectors |
| 73 | Frame:Anodized Aluminium |
| 74 | Front Glass:2.00MMARC |
| 75 | Back Glass:2.00MM NON ARC |
| 76 | Cell Encapsulant:HIGH QUAILITY ENCAPSULANT |
| 77 | Backsheet:GLASS |
| 78 | Max Surface Load:5400PA(SNOW),2400PA(WIND) |
| 79 | Application Class:CLASS A(SAFETY CLASS -II) |
| 80 | Product Warranty:12YEARS |
| 81 | Performance Warranty :Linear Performance warranty for 30 Years with 1% for 1st year degradation and 0.45% from year 2 to 30 |
| 82 | Approvals and Certificates:BIS certified as per IS/IEC standards |
| 83 | External Protection Device |
| 84 | AJB/DCDB |
| 85 | String (In-Out):6IN-6OUT |
| 86 | Fuse Rating (A):20 |
| 87 | Type II SPD Rating (DC):UC11VDC |
| 88 | ACDB / LT Panel |
| 89 | MCB/MCCB (A):40P50A |
| 90 | Type II SPD Rating (AC):UC-440VAC |
| 91 | Solar DC Cable (PV Panel to Inverter):1CX4SQMM |
| 92 | AC Cable Rating |
| 93 | Inverter to ACDB (Cu Flexible):4COREX25SQ.MM. |
| 94 | ACDB to LT Panel (<20 m) Armour:3.5COREX25SQMM |
| 95 | ACDB to LT Panel (20–50 m) Armour |
| 96 | Earthing Cable for Inverter:1CORE X 16SQMM |
| 97 | ROOF TOP INSTATION BOM |
| 98 | System Type:Grid-connected Rooftop Solar PV System |
| 99 | Mounting Type:FIXED TI LTSTRUCTURE |
| 100 | Installation Location: RCC/METALROOF |
| 101 | Standards: AS PER MNRE/BIS IEC standeres |
| 102 | Module Mounting Structure |
| 103 | Material:Hot Dip Galvanized Iron / Aluminium |
| 104 | Coating Thickness:>-80microns(hdg) |
| 105 | Tilt Angle:as per site latitude. |
| 106 | Fasteners:SS304/HDG BOLTS &NUTS |
| 107 | Wind Load Capacity:UP TO 150KM/H |
| 108 | Structure Type:Elevated structure with clearance for maintenance |
| 109 | Walkway |
| 110 | Material:Hot Dip Galvanized Iron / Aluminium |
| 111 | Width:Minimum 500 mm – 800 mm |
| 112 | Thickness:AS PE LOAD BEARING REQUIREMENTS |
| 113 | Surface::ANTI SKID/ANTI SLIP |
| 114 | Placement:Between module rows and access paths |
| 115 | Support:Mounted on structure with proper clamps |
| 116 | Load Capacity:Minimum 150 kg point load |
| 117 | Water Cleaning System |
| 118 | Type:Manual / Semi-Automatic Cleaning System |
| 119 | Water Source:Overhead tank / Existing water line |
| 120 | Pipeline:HDPE / PVC piping network |
| 121 | Pipe Size:20 mm / 25 mm (as per design) |
| 122 | Valves:Ball valves at intervals |
| 123 | Outlet Points:Hose connection points near module rows |
| 124 | Pump (if required):0.5–1 HP water pump |
| 125 | Cleaning Method:Soft water spray / brush cleaning |
| 126 | Frequency:Weekly / as per dust conditions |
| 127 | Filtration:Basic filter to avoid nozzle clogging |
| 128 | After Free/under warranty annual repair and maintenance for 1st Year and 2nd Year (Nil against warrenty |
| 129 | Maintenance Charges for 3rd Year @ 2.5% on capital cost |
| 130 | Maintenance Charges for 4th Year @ 2.5% on capital cost |
| 131 | Maintenance Charges for 5th Year @ 2.5% on capital cost Please Enable Macros to View BoQ information |