| 1 | Supply, installation, testing & Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event , 1000 alarm log history events, Qwerty/ Touch Screen keypad for operation. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 250 analog addressable devices (Devices and detectors). The panel shall work in degrade mode in case of CPU failure, Products not having this feature will offer Redundant CPU. Four access levels, flash EPROM, Panel Shall include 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall support with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and 2 ways Communication Fire Fighters System capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of Fire Panel CPU shall not result in failure of DVC operation. The Fire Fighters Telephone System shall be capable of having minimum 5 Telephones in conference in multiple FFT Risers. The panel shall be expandable upto Min. 10 loop, UL & FM approved. Panel shall have provsion for Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Designed to meet UL864, 10th.complete in all respects as approved and desired by the Engineer in-charge at site. The Panel must be complete along with its cabinet/ chasis etc. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 2 | Supply, installation, testing & Commissioning of Loop Cards Class A Wiring with min. supporting cable length Up to 1.2 Km UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 3 | Supply, installation, testing & Commissioning of Digital Voice Command Controlling Board combines the capabilities of a powerful digital audio processor, an eventdriven audio message generator, and a router.The DVC has two wire digital audio ports to connect to wire DAL segments. The DVC may be networked Programmable from NUP port. Up to 32 minutes of standard quality or 4 minutes of high quality digital audio storage of user-selected/created messages and tones. Supports twisted-pair wire media. Supports single- and multi-mode fiber-optic media when used with fiber option modules. 4-channel analog audio supported.The DVC Should be Compatible with Auxiliary input for line level, 1.0 VRMS, or 1.41 Vp-p low level audio. Selectable AGC, user control of audio level, and audio supervision are supported. UL Listed: S635.ULC Listed: S635.FM Approved. The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 4 | Supply, installation, testing & Commissioning of Digital Voice Command Keyboard/ Touch Screen for local annunciation and controls; status LEDs and 24 user-programmable buttons.Display All Call, Page Active Evac Areas, Page Active Alert Areas, Page Inactive Areas UL Listed . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 5 | Supply, installation, testing & Commissioning of Paging Microphone compatible with Emergency evacuation Control Panel UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 6 | Supply, installation, testing & Commissioning of Addressable photo-Thermal multi criteria Detector and base with sensitivity range as per NFPA 72. The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 7 | Supply, installation, testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 8 | Supply, installation, testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site.UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 9 | Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 10 | Supply, installation, testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 11 | Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 12 | Supply, installation, testing & Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device.UL & FM Approved Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.The solution should be from single OEM.complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 13 | Supply, installation, testing & Commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 14 | Supply, installation, testing & Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 15 | Supply, installation, testing & Commissioning of Addressable Fire Fighter's Telephone Jack for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 16 | Supply, installation, testing & Commissioning of Chassis assembly enclousre for Fire fighter telehphone handset, UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 17 | Supply, installation, testing & Commissioning of Digital Audio Amplifier.With Amp power supply Amplifier shall be capable of N:N/N:1 configuration and shall be dual channel capable of processing Two of 8 audio channels and a total of Min 95 W ( It may be 1 unit or Combination of Multiple units to achieve the Requirement) at 70.7 VRMS output along with necessary enclosures with local FFT Raiser. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital Audio Amplifiers shall (be Wall/Panel Mounted) Failure of Fire Panel CPU shall not result in failure of Amplifier operation. Amplifiers shall be distributed across the building/floor to manage the sound attenuation problem & for the best sound intelligibility. All amplifiers shall provide back up of minimum 5 hours using secondary power source(battery power/UPS power) complete in all respects as approved and desired by the Engineer in-charge at site. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 18 | Supply, installation, testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers. The speakers shall be of the same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 19 | Supply, installation, testing & Commissioning of Back Box for 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers as complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 20 | Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- (a)Fire Survival cable 2Core x 1.5 sq.mm |
| 21 | Supply, Installation, Testing and Comissioning of LED Glow Type EXIT Sign Board with minimum three hour backup, photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class-1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 22 | Supply, Installation, Testing and Comissioning of industrial grade Emergency Exit Light with LED Sign 2 Language, inbuilt Battery: 12V,7AH, with minimum 4 hours of backup made of power coated Sheet Metal, work with AC 220v,50Hz(+/15%) and Battery Light Source: 9W x 2 nos LED Bulbs, Battery operating volts: 11V to 14V, Battery charger: Regulated constant volt constant current Battery charging Time: 7 to 8 Hrs (app) Power consumption: 10W(app) while charging, LED display diffuser: Red/Green acrylic transparent, Tiltable, Auto lights up while power failure complete the job in all respect up to the entire satisfaction of of one year is Engineer-in-Charge of site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 23 | Supply, installation, testing & Commissioning of Online UPS 1 kva 800 Watts Tower UPS with 1 hour battery backup. Operating Temperature Range 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load,Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Input Socket IEC C13, Output Socket IEC C14, No of output sockets 3 No's, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load, 100 to 300 Vac @ 50% Load, Input Power Factor 0.99, Input THDi% 5%, Generator Set Yes 1.5 x UPS Capacity, Rated kVA 1000 VA, Rated kW 800 Watts, Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Online Efficiency 88%, Rated Battery Voltage 36 Vdc, Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC, Battery backup Back UP : 936VAH, Maximum charging current 10 Amps, ECO Mode Available, Communication (Independent SCI) Available, Intelligent Card slot (Independent SCI) Available, OVCD Available, EPO Function Available, Intelligent Fans Speed control Available, Auto restart function Available, Cold start Available complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 24 | HEAVY GUAGE WELDED CONDUIT PIPES:Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiringpurposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materialsetc., where necessary including painting as per PWD General Specifications:- |
| 25 | Heavy gauge welded conduit pipe 25mm dia. (ISI marked 1.60mm thick) Flushed |
| 26 | Supply, installation, testing & Commissioning of chassis of appropriate size requirement for Amplifier and Digital Series Distribution Board. Chassis should be fabricated from 14-gauge steel, e key-locked door is provided with a pin-type hinge, two keys and the necessary hardware to mount the door, Right- or left-hand hinges, selectable in the field. Door opens 180°, door should be heat dissipation refers to the process of transferring heat away from a system, component, or device to maintain its temperature within acceptable limits. Chassis should be of same make OEM as complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 27 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES:- Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket(shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½\\" deep for walls and CI 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 28 | Wiring 3 pin 6 Amp. wall socket point |
| 29 | Wiring 3 Pin 6 Amp. Plug control comprising wall socket point |
| 30 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge |
| 31 | Overall size 1.5sq.mm (Un-sheathed) |
| 32 | Overall size 2.5sq.mm (Un-sheathed) |
| 33 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications: |
| 34 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed Please Enable Macros to View BoQ information |