| Sl. No. | Item Description |
| 1 | MAIN BUILDING ] |
| 2 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 3 | In all kind of soil upto 1.5m depth |
| 4 | In all kind of soil upto 1.5m to 3.0m. depth |
| 5 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 6 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 7 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 8 | Construction of drain along with apron. 150X150MM |
| 9 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 10 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 11 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 12 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Lintel |
| 13 | Ground Floor |
| 14 | First Floor |
| 15 | Second floor |
| 16 | Mumty floor |
| 17 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in slab |
| 18 | Ground Floor |
| 19 | First Floor |
| 20 | Second floor |
| 21 | Mumty floor |
| 22 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Plinth Beam |
| 23 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Beam |
| 24 | Ground Floor |
| 25 | First Floor |
| 26 | Second floor |
| 27 | Mumty floor |
| 28 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in foundation |
| 29 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C.work in column (Up to plinth level) |
| 30 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C.work in column |
| 31 | Ground Floor |
| 32 | First Floor |
| 33 | Second floor/Mumty floor |
| 34 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 35 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 36 | Painting on DPC or over roof slab one coat of air blown bitumen 60/70 or 80/100 grade @ one Kg/Sqm including cost of fuel wood other materials, labour T & P etc required for proper completion of work. |
| 37 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 38 | Ground Floor |
| 39 | First Floor |
| 40 | Second Floor |
| 41 | Terrace floor/ Mumty floor |
| 42 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 43 | Ground Floor |
| 44 | First Floor |
| 45 | Second Floor |
| 46 | Terrace floor/ Mumty floor |
| 47 | Extra For providing and pracing in postion 2 Nos 6 mm dia. M.S. bars at every third course of half brick masonry. |
| 48 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 49 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 50 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 51 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 52 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 53 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 54 | Three track three panels sliding door with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, zinc alloy (Zamak) powder coated handle on two panels along with multi-point locking system, adjustable nylon rollers with SS 304 body. |
| 55 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 56 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 57 | Ground Floor |
| 58 | First Floor |
| 59 | Second Floor |
| 60 | Mumty Floor |
| 61 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 62 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 63 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 64 | Ground Floor |
| 65 | First Floor |
| 66 | Second Floor |
| 67 | Mumty Floor |
| 68 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 69 | Ground Floor |
| 70 | First Floor |
| 71 | Second Floor |
| 72 | Mumty Floor |
| 73 | 12mm thick plaster in 1:3 cement & coarse sand on ceiling and soffits of stairs upto floor two level. |
| 74 | Making grooves 10 to12mm wide x 8mm deep in plaster of the wal or in ceilng verticalLy or horizonta ly as required |
| 75 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 76 | Supply and fixing of Kota Stone in flooring 25mm thick and joint filled 1:2 cement and coarse sand with approved colouring materials to be given an even shade with 12mm base coat (bedding) of 1:2 cement & coarse sand mortar and polished by hand or machine and finally finished with french manson polish or other approved polish including supply of all materials, labour, tools & plants etc required for proper completion of the work. 25mm thick |
| 77 | Ground Floor |
| 78 | First Floor |
| 79 | Second Floor |
| 80 | Supply and fixing 10 to 12mm thick Kota Stone tiles in skirting or dado laid with 1:2 cement and approved coarse sand mortar finished with in its cement colour slurry, jointing and polished or approved quality complete, including supply of all materials, labour tools & plants etc required for proper completion of teh work. 25mm thick |
| 81 | Ground Floor |
| 82 | First Floor |
| 83 | Second Floor |
| 84 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 85 | Ground Floor |
| 86 | First Floor |
| 87 | Second Floor |
| 88 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 15mm thick cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 89 | Ground Floor |
| 90 | First Floor |
| 91 | Second Floor |
| 92 | Supply and fixing 6mm thick china white glazed tiles in flooring or in skirting or dado laid with 1:3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials, labour and tool sand plants etc. |
| 93 | Ground Floor |
| 94 | First Floor |
| 95 | Second Floor |
| 96 | Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing,curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :Flamed finish granite stone slab Jet Black, Cherry Red, EliteBrown, Cat Eye or equivalent. |
| 97 | Ground Floor |
| 98 | First Floor |
| 99 | Second Floor |
| 100 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 101 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 102 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 103 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 104 | Providing & laying of light cinder filling under floor of toilets & other sunken roofs. |
| 105 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 106 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. |
| 107 | b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs |
| 108 | c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineerin- Charge : |
| 109 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 110 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 111 | Fixing of Door, windows/ventilators chaukhats in position. |
| 112 | Providing and fixing 150 mm bright finished floor stainless steel door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 113 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 114 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 115 | (a) 250 mm x 10mm |
| 116 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 117 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 118 | (a) Single leaf |
| 119 | (b) Extra for double leaf doors |
| 120 | both side laminated |
| 121 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 122 | Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butthinges and necessary S.S screws shall be paid separately) 35 mm thick |
| 123 | Providing and fixing factory made single extruded WPC (Wood Polymer Composite) soliddoor/window/clerestory windows & desertory other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/ cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions |
| 124 | i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made. Frame size 50 x 100 mm |
| 125 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 126 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50 mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. |
| 127 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that ccommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. |
| 128 | The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge. (Material shall confirm to ASTM 6063) Floor Joint of 100 mm gap |
| 129 | Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates asper ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement |
| 130 | and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical isplacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.)Roof Joint of 100 mm gap |
| 131 | Providing and fixing of expansion joint system elated with wall joint (internal/ external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimalexposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063).Wall Joint of 100 mm gap |
| 132 | Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm thick as per design for expansion joints. 200 mm wide. |
| 133 | Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand). |
| 134 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 135 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 136 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 137 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 138 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 139 | Suspended floors, roofs, landings, balconies and access platform. |
| 140 | MID DAY MEAL] |
| 141 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 142 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 143 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 144 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 145 | Construction of drain along with apron. 150X150MM |
| 146 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 147 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 148 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 149 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 150 | Ground Floor |
| 151 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 152 | First Floor |
| 153 | As in item no. 7 above but for slabs (Using 1:1.5:3 Mix concrete). M-20 |
| 154 | Ground Floor |
| 155 | First Floor |
| 156 | As in item 7 but for the lighter beams i.e. having spans upto 6 m. (Using 1:1.5:3 Mix concrete) M-20 |
| 157 | Ground Floor |
| 158 | First Floor |
| 159 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in footing |
| 160 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in column |
| 161 | Ground Floor |
| 162 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) R.C.C.work in column |
| 163 | First Floor |
| 164 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 165 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 166 | Painting on DPC or over roof slab one coat of air blown bitumen 60/70 or 80/100 grade @ one Kg/Sqm including cost of fuel wood other materials, labour T & P etc required for proper completion of work. |
| 167 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 168 | Ground Floor |
| 169 | First Floor |
| 170 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 171 | First Floor |
| 172 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 173 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 174 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 175 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 176 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 177 | Three track three panels sliding door with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, zinc alloy (Zamak) powder coated handle on two panels along with multi-point locking system, adjustable nylon rollers with SS 304 body. |
| 178 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 179 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 180 | Ground Floor |
| 181 | First Floor |
| 182 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 183 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 184 | Ground Floor |
| 185 | First Floor |
| 186 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 187 | Ground Floor |
| 188 | First Floor |
| 189 | 12mm thick plaster in 1:3 cement & coarse sand on ceiling and soffits of stairs upto floor two level. |
| 190 | Ground Floor |
| 191 | First Floor |
| 192 | Making grooves 10 to12mm wide x 8mm deep in plaster of the wal or in ceilng verticalLy or horizonta ly as required |
| 193 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 194 | Supply and fixing of Kota Stone in flooring 25mm thick and joint filled 1:2 cement and coarse sand with approved colouring materials to be given an even shade with 12mm base coat (bedding) of 1:2 cement & coarse sand mortar and polished by hand or machine and finally finished with french manson polish or other approved polish including supply of all materials, labour, tools & plants etc required for proper completion of the work. 25mm thick |
| 195 | Ground Floor |
| 196 | First Floor |
| 197 | Supply and fixing 10 to 12mm thick Kota Stone tiles in skirting or dado laid with 1:2 cement and approved coarse sand mortar finished with in its cement colour slurry, jointing and polished or approved quality complete, including supply of all materials, labour tools & plants etc required for proper completion of teh work. 25mm thick |
| 198 | Ground Floor |
| 199 | First Floor |
| 200 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 201 | Ground Floor |
| 202 | First Floor |
| 203 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 15mm thick cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 204 | Ground Floor |
| 205 | First Floor |
| 206 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 207 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 208 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 209 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 210 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. |
| 211 | b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs |
| 212 | c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineerin- Charge : |
| 213 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 214 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 215 | Fixing of Door, windows/ventilators chaukhats in position. |
| 216 | Door Chaukhats |
| 217 | Windows Chaukhats |
| 218 | Providing and fixing 150 mm bright finished floor stainless steel door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 219 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 220 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 221 | (a) 250 mm x 10mm |
| 222 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 223 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 224 | (a) Single leaf |
| 225 | (b) Extra for double leaf doors |
| 226 | both side laminated |
| 227 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 228 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 229 | Chequered tiles 22 mm thick in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Light shade pigment using white cement. |
| 230 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 231 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 232 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 233 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 234 | Suspended floors, roofs, landings, balconies and access platform. |
| 235 | BAL VATIKA |
| 236 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 237 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 238 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 239 | Construction of drain along with apron. 150X150MM |
| 240 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 241 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 242 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 243 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 244 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 245 | As in item no. 7 above but for slabs (Using 1:1.5:3 Mix concrete). M-20 |
| 246 | As in item 7 but for the lighter beams i.e. having spans upto 6 m. (Using 1:1.5:3 Mix concrete) M-20 |
| 247 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in footing |
| 248 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in column |
| 249 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) R.C.C.work in column |
| 250 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 251 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 252 | Painting on DPC or over roof slab one coat of air blown bitumen 60/70 or 80/100 grade @ one Kg/Sqm including cost of fuel wood other materials, labour T & P etc required for proper completion of work. |
| 253 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 254 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 255 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 256 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 257 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 258 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 259 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 260 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 261 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 262 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 263 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 264 | 12mm thick plaster in 1:3 cement & coarse sand on ceiling and soffits of stairs upto floor two level. |
| 265 | Making grooves 10 to12mm wide x 8mm deep in plaster of the wal or in ceilng verticalLy or horizonta ly as required |
| 266 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 267 | Supply and fixing of Kota Stone in flooring 25mm thick and joint filled 1:2 cement and coarse sand with approved colouring materials to be given an even shade with 12mm base coat (bedding) of 1:2 cement & coarse sand mortar and polished by hand or machine and finally finished with french manson polish or other approved polish including supply of all materials, labour, tools & plants etc required for proper completion of the work. 25mm thick |
| 268 | Supply and fixing 10 to 12mm thick Kota Stone tiles in skirting or dado laid with 1:2 cement and approved coarse sand mortar finished with in its cement colour slurry, jointing and polished or approved quality complete, including supply of all materials, labour tools & plants etc required for proper completion of teh work. 25mm thick |
| 269 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 270 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 15mm thick cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 271 | Supply and fixing 6mm thick china white glazed tiles in flooring or in skirting or dado laid with 1:3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials, labour and tool sand plants etc. |
| 272 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 273 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 274 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 275 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 276 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. |
| 277 | b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs |
| 278 | c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineerin- Charge : |
| 279 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 280 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 281 | Fixing of Door, windows/ventilators chaukhats in position. |
| 282 | Providing and fixing 150 mm bright finished floor stainless steel door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 283 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 284 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 285 | (a) 250 mm x 10mm |
| 286 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 287 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 288 | (a) Single leaf |
| 289 | both side laminated |
| 290 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 291 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 292 | Chequered tiles 22 mm thick in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Light shade pigment using white cement. |
| 293 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 294 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 295 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 296 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 297 | Suspended floors, roofs, landings, balconies and access platform. |
| 298 | MULTI PURPOSE HALL |
| 299 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 300 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 301 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 302 | Sand filling in plinth under floors including watering, ramming, consolidating and dressing complete including lead up to 50m and lift upto 1.5m and including cost of sand. |
| 303 | Providing and injecting chemical emulsion for preconstructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete (plinth area of the building at ground floor only shall be measured as per I.S.6313(PartII 1981)Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 304 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5)Treatment of soil along external perimeter of building 7.5 liters/sqm. (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 305 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Lintel |
| 306 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in slab |
| 307 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Plinth Beam |
| 308 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in Beam |
| 309 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C. work in foundation |
| 310 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C.work in column |
| 311 | Providing and laying in position ready mixed or sitebatched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement..All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum R.C.C.work in column |
| 312 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 313 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 12.5 mm nominal size). |
| 314 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 315 | Same as in item no. 11 above but in super-structure above plinth level up to floor two level ( up to two storeys ) including necessary cutting and moulding of brick work as required and also including honeycombed brick work in thickness of wall more than 12cms. (1:6 cement : Coarse sand). M-150 |
| 316 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. T.M.T. Fe 500 |
| 317 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:4 (1 cement: 4 coarse sand) |
| 318 | 12 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand (2.25 FM) |
| 319 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand |
| 320 | 12mm cement plaster on ceiling & soffits. (1) 1 cement : 3 coarse sand. |
| 321 | Forming groove of uniform size from 12x12 mm and upto 25x15 mm in the top layer of washed stone grit plastered surface as per approved pattern, including providing and fixing aluminum channels of appropriate size and thickness (not less than 2 mm), nailed to the under layer with rust proof screws and nails and finishing the groove complete as per specifications and direction of the Engineer-in-Charge. |
| 322 | 1:2:4 (1 cement : 2 coarse sand (zone-lll) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 323 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete |
| 324 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600x600 mm. |
| 325 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand): 25 mm thick. |
| 326 | Kota stone slabs 25 mm thick in risers of steps, skirting, dado, and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 327 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 328 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: (a) 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 329 | (b) Double leaf |
| 330 | both side laminated |
| 331 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 332 | Fixing of Door, windows/ventilators chaukhats in position. |
| 333 | (a) Door chaukhats |
| 334 | (b) Window chaukhats |
| 335 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 336 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 337 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 338 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 339 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 340 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 341 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Inner walls) |
| 342 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Ceiling) |
| 343 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm) |
| 344 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 345 | Providing and fixing 150 mm bright finished floor stainless steel door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 346 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 347 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 348 | (a) 250 mm x 10mm |
| 349 | (a) 200 mm x 10mm |
| 350 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 351 | Making drain along with the apron. 150X150mm |
| 352 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 353 | Hot finished seamless type tubes([email protected]./sqm |
| 354 | Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per anufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. |
| 355 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 1.0 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin- charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 356 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 357 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 358 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 359 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 360 | Suspended floors, roofs, landings, balconies and access platform. |
| 361 | STAFF RESIDANCE |
| 362 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 363 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 364 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 365 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 366 | Construction of drain along with apron. 150X150MM |
| 367 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 368 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 369 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 370 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 371 | Ground Floor |
| 372 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 373 | First Floor |
| 374 | As in item no. 7 above but for slabs (Using 1:1.5:3 Mix concrete). M-20 |
| 375 | Ground Floor |
| 376 | First Floor |
| 377 | As in item 7 but for the lighter beams i.e. having spans upto 6 m. (Using 1:1.5:3 Mix concrete) M-20 |
| 378 | Ground Floor |
| 379 | First Floor |
| 380 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in footing |
| 381 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in column |
| 382 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 383 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 384 | Painting on DPC or over roof slab one coat of air blown bitumen 60/70 or 80/100 grade @ one Kg/Sqm including cost of fuel wood other materials, labour T & P etc required for proper completion of work. |
| 385 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 386 | Ground Floor |
| 387 | First Floor |
| 388 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 389 | Ground Floor |
| 390 | First Floor |
| 391 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 392 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 393 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 394 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 395 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 396 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 397 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 398 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 399 | Ground Floor |
| 400 | First Floor |
| 401 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 402 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 403 | Ground Floor |
| 404 | First Floor |
| 405 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 406 | Ground Floor |
| 407 | First Floor |
| 408 | 12mm thick plaster in 1:3 cement & coarse sand on ceiling and soffits of stairs upto floor two level. |
| 409 | Ground Floor |
| 410 | First Floor |
| 411 | Making grooves 10 to12mm wide x 8mm deep in plaster of the wal or in ceilng verticalLy or horizonta ly as required |
| 412 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 413 | Supply and fixing of Kota Stone in flooring 25mm thick and joint filled 1:2 cement and coarse sand with approved colouring materials to be given an even shade with 12mm base coat (bedding) of 1:2 cement & coarse sand mortar and polished by hand or machine and finally finished with french manson polish or other approved polish including supply of all materials, labour, tools & plants etc required for proper completion of the work. 25mm thick |
| 414 | Ground Floor |
| 415 | First Floor |
| 416 | Supply and fixing 10 to 12mm thick Kota Stone tiles in skirting or dado laid with 1:2 cement and approved coarse sand mortar finished with in its cement colour slurry, jointing and polished or approved quality complete, including supply of all materials, labour tools & plants etc required for proper completion of teh work. 25mm thick |
| 417 | Ground Floor |
| 418 | First Floor |
| 419 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 420 | Ground Floor |
| 421 | First Floor |
| 422 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 15mm thick cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 423 | Ground Floor |
| 424 | First Floor |
| 425 | Supply and fixing 6mm thick china white glazed tiles in flooring or in skirting or dado laid with 1:3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials, labour and tool sand plants etc. |
| 426 | Ground Floor |
| 427 | First Floor |
| 428 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 429 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 430 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 431 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 432 | Providing & laying of light cinder filling under floor of toilets & other sunken roofs. |
| 433 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 434 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. |
| 435 | b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs |
| 436 | c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineerin- Charge : |
| 437 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 438 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 439 | Fixing of Door, windows/ventilators chaukhats in position. |
| 440 | Door Chaukhats |
| 441 | Windows Chaukhats |
| 442 | Ventilators Chaukhats |
| 443 | Providing and fixing 150 mm bright finished floor stainless steel door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 444 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 445 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 446 | (a) 250 mm x 10mm |
| 447 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 448 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 449 | (a) Single leaf |
| 450 | both side laminated |
| 451 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 452 | Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1mm), with wall thickness 2.0 mm (± 0.2 mm), corners of the door frame to be Jointed with galvanized brackets and stainless steel screws, joints mitred and Plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer’s specification and direction of Engineerin- charge Extruded section size 60x58 mm |
| 453 | After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealent shall be paid separately). Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. |
| 454 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 455 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 456 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 457 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 458 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 459 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 460 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 461 | Suspended floors, roofs, landings, balconies and access platform. |
| 462 | PRINCIPAL RESIDENCE |
| 463 | Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 464 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 465 | Sand filling in plinth under floors including watering, ramming, consolidating and dressing complete including lead up to 50m and lift upto 1.5m and including cost of sand. |
| 466 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 467 | Providing and injecting chemical emulsion for preconstructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete (plinth area of the building at ground floor only shall be measured as per I.S.6313(PartII 1981)Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1)Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters / sqm |
| 468 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5)Treatment of soil along external perimeter of building 7.5 liters/sqm. (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 469 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 470 | R.C.C. Work in Plinth band |
| 471 | R.C.C. work in footing |
| 472 | R.C.C. work in column |
| 473 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 474 | ABOVE PLINTH LVL |
| 475 | R.C.C. Work in Lintel band |
| 476 | R.C.C. work in slab |
| 477 | R.C.C. work in beams |
| 478 | M-150 brick work in 1:4 (one cement and Four coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 479 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 480 | Applying a coat of residual petroleum bitumen of grade of VG 10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 481 | Brick work in super-structure above plinth level up to floor two level (up to two storeys) including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:4 cement & coarse sand) |
| 482 | Ground Floor |
| 483 | First Floor |
| 484 | Terrace /Mumty |
| 485 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 486 | Providing & laying \\"brick bat Coba\\" 120 mm thick laid with M-150 class brick bat coba 7.50 cm thick with gap of 15mm to each other, over 20mm thick base of cement mortar 1:4 cement and coarse sand mixed with water proofing compound spreading cement slurry mixed with acrylic cement concrete water proofing compound filled gaps of |
| 487 | coba & top of coba mortar mixed with water proofing compound in 1:4 cement and coarse sand mortar finished smooth & top mashed false square 30 cm x 30 cm and side wall parapet shall be mono lythic plaster wall upto 30cm higher and junction and corner shall be rounded by brick |
| 488 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 489 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick |
| 490 | (a) Single leaf |
| 491 | both side laminated |
| 492 | Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1mm), with wall thickness 2.0 mm (± 0.2 mm), corners of the door frame to be Jointed with galvanized brackets and stainless steel screws, joints mitred and Plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer’s specification and direction of Engineerin- charge Extruded section size 60x58 mm |
| 493 | After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealent shall be paid separately). Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. |
| 494 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 495 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. |
| 496 | Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 497 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 498 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 499 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 500 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 501 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 502 | Fixing of Door, windows / ventilators chaukhats in position. |
| 503 | (a) Door chaukhats |
| 504 | (b) Window chaukhats |
| 505 | (c) Ventilator chaukhats |
| 506 | 15 mm cement plaster on plinth of mix : 1:4 (1 cement: 4 coarse sand). F.M.-2.25 |
| 507 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1) 1 cement : 6 coarse sand. F.M.-2.25 |
| 508 | 15 mm cement plaster in single coat on rough side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 509 | Ground Floor |
| 510 | First Floor |
| 511 | Terrace /Mumty |
| 512 | Making grooves 10 to 12 mm wide x 8mm deep in plaster of the walls or in ceiling vertically or horizontally as required. |
| 513 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm (Anti skid/mat finished tile) |
| 514 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. |
| 515 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 20 mm thick. |
| 516 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 517 | Supply & fixing 6 mm thick china white glazed tiles in flooring or in skirting or dado laid with 1 :3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials labours & tools etc, required for completion of the work. (size of tiles upto 200x 300 mm). Floor tiles |
| 518 | Supply & fixing 6 mm thick china white glazed tiles in flooring or in skirting or dado laid with 1 :3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials labours & tools etc, required for completion of the work. (size of tiles upto 200x 300 mm). Wall tiles |
| 519 | Painting or varnishing work in small areas or new wood work with one coat upto one square metre of ready mixed priming paint and one coat of approed superior quality ready mixed paint or varnish including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. Paint to be used should fonfirm the ISI no. 103-1950 (M.S. works) |
| 520 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 521 | 40 mm thick 1:2:4 plain cement concrete floor (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement. |
| 522 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade. New work (Two or more coats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm). |
| 523 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Inner walls) |
| 524 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Ceiling) |
| 525 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 526 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 527 | Providing & fixing S.S. sliding door bolts ISI marked to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 528 | Providing and fixing S.S. Steel tower bolts with necessary screws etc. complete |
| 529 | (a) 250mm x 10mm. |
| 530 | (b) 200mm x 10mm. |
| 531 | Providing and fixing S.S. Steel handles with screws etc. complete (a) 125 mm |
| 532 | Construction of drain alongwith apron.(150 x 150)mm |
| 533 | Providing & laying of light cinder filling under floor of toilets & other sunken roofs. |
| 534 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 535 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 536 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 537 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 538 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 539 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 540 | Suspended floors, roofs, landings, balconies and access platform. |
| 541 | DOROMOTARY |
| 542 | Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 543 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 544 | Sand filling in plinth under floors including watering, ramming, consolidating and dressing complete including lead up to 50m and lift upto 1.5m and including cost of sand. |
| 545 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 546 | Providing and injecting chemical emulsion for preconstructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete (plinth area of the building at ground floor only shall be measured as per I.S.6313(PartII 1981)Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1)Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters / sqm |
| 547 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5)Treatment of soil along external perimeter of building 7.5 liters/sqm. (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 548 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 549 | R.C.C. Work in Plinth band |
| 550 | R.C.C. work in footing |
| 551 | STAIR CASE |
| 552 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 553 | ABOVE PLINTH LVL |
| 554 | R.C.C. Work in Lintel band |
| 555 | R.C.C. work in slab |
| 556 | R.C.C. work in beams |
| 557 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 558 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 559 | Applying a coat of residual petroleum bitumen of grade of VG 10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 560 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 561 | Ground Floor |
| 562 | First Floor |
| 563 | Terrace /Mumty |
| 564 | Half brick masonry with (Class M-150 First Class Brick) in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 565 | Ground Floor |
| 566 | First Floor |
| 567 | Providing & laying \\"brick bat Coba\\" 120 mm thick laid with M-150 class brick bat coba 7.50 cm thick with gap of 15mm to each other, over 20mm thick base of cement mortar 1:4 cement and coarse sand mixed with water proofing compound spreading cement slurry mixed with acrylic cement concrete water proofing compound filled gaps of |
| 568 | coba & top of coba mortar mixed with water proofing compound in 1:4 cement and coarse sand mortar finished smooth & top mashed false square 30 cm x 30 cm and side wall parapet shall be mono lythic plaster wall upto 30cm higher and junction and corner shall be rounded by brick |
| 569 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 570 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick |
| 571 | (a) Single leaf |
| 572 | (b) Extra for double leaf doors |
| 573 | both side laminated |
| 574 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 575 | Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1mm), with wall thickness 2.0 mm (± 0.2 mm), corners of the door frame to be Jointed with galvanized brackets and stainless steel screws, joints mitred and Plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer’s specification and direction of Engineerin- charge Extruded section size 60x58 mm |
| 576 | After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealent shall be paid separately). Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. |
| 577 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 578 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. |
| 579 | Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 580 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 581 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 582 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 583 | Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (74 mm & above). (Height upto 2.5 metre). |
| 584 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 585 | Fixing of Door, windows / ventilators chaukhats in position. |
| 586 | (a) Door chaukhats |
| 587 | (b) Window chaukhats |
| 588 | (c) Ventilator chaukhats |
| 589 | 15 mm cement plaster on plinth of mix : 1:4 (1 cement: 4 coarse sand). F.M.-2.25 |
| 590 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1) 1 cement : 6 coarse sand. F.M.-2.25 |
| 591 | 15 mm cement plaster in single coat on rough side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 592 | Ground Floor |
| 593 | First Floor |
| 594 | Terrace /Mumty |
| 595 | Making grooves 10 to 12 mm wide x 8mm deep in plaster of the walls or in ceiling vertically or horizontally as required. |
| 596 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm (Anti skid/mat finished tile) |
| 597 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. |
| 598 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 20 mm thick. |
| 599 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 600 | Supply & fixing 6 mm thick china white glazed tiles in flooring or in skirting or dado laid with 1 :3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials labours & tools etc, required for completion of the work. (size of tiles upto 200x 300 mm). Floor tiles |
| 601 | Supply & fixing 6 mm thick china white glazed tiles in flooring or in skirting or dado laid with 1 :3 cement and approved coarse sand mortar finished with white cement slurry jointing and polishing complete including supply of all materials labours & tools etc, required for completion of the work. (size of tiles upto 200x 300 mm). Wall tiles |
| 602 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 20 mm thick. |
| 603 | Painting or varnishing work in small areas or new wood work with one coat upto one square metre of ready mixed priming paint and one coat of approed superior quality ready mixed paint or varnish including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. Paint to be used should fonfirm the ISI no. 103-1950 (M.S. works) |
| 604 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 605 | 40 mm thick 1:2:4 plain cement concrete floor (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement. |
| 606 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade. New work (Two or more coats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm). |
| 607 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Inner walls) |
| 608 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on ceiling to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost of all materials. (Ceiling) |
| 609 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 610 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 611 | Providing & fixing S.S. sliding door bolts ISI marked to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 612 | Providing and fixing S.S. Steel tower bolts with necessary screws etc. complete |
| 613 | (a) 250mm x 10mm. |
| 614 | (b) 200mm x 10mm. |
| 615 | Providing and fixing S.S. Steel handles with screws etc. complete (a) 125 mm |
| 616 | Construction of drain alongwith apron.(150 x 150)mm |
| 617 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 618 | Providing & laying of light cinder filling under floor of toilets & other sunken roofs. |
| 619 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 620 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 621 | Centering and shuttering including strutting, propping etc. and removal of form for all heights |
| 622 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 623 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 624 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 625 | Suspended floors, roofs, landings, balconies and access platform. |
| 626 | GUARD ROOM |
| 627 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 628 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 629 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 630 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 631 | Construction of drain along with apron. 150X150MM |
| 632 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 633 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 634 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 635 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 636 | Ground Floor |
| 637 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). R.C.C. work in Lintel |
| 638 | As in item no. 7 above but for slabs (Using 1:1.5:3 Mix concrete). M-20 |
| 639 | M-150 brick work in 1:6 (one cement and six coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 640 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 641 | Painting on DPC or over roof slab one coat of air blown bitumen 60/70 or 80/100 grade @ one Kg/Sqm including cost of fuel wood other materials, labour T & P etc required for proper completion of work. |
| 642 | Brick work in super-structure above plinth level including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand). |
| 643 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately) |
| 644 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 645 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 646 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 647 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 648 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 649 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 650 | TMT Fe-500 iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 651 | 15 mm plinth plaster (1 cement :4 coarse sand) F.M.-2.25 |
| 652 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 coarse sand. F.M.-2.25 |
| 653 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 654 | 12mm thick plaster in 1:3 cement & coarse sand on ceiling and soffits of stairs upto floor two level. |
| 655 | Making grooves 10 to12mm wide x 8mm deep in plaster of the wal or in ceilng verticalLy or horizonta ly as required |
| 656 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 657 | 18 mm thick cement plaster in dado/ skirting in 1:3 consisting of one part of cement and 3 part of approved coarse sand laid in panels, finished with 3mm floating coat of neat cement and marble dust in ratio of 5:1 including supply of all materials labour T & P etc. required for proper completion of the work. |
| 658 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. (a) 40 mm wide and 35 mm thick |
| 659 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 660 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 661 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 662 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 663 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. |
| 664 | b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs |
| 665 | c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineerin- Charge : |
| 666 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 667 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 668 | Fixing of Door, windows/ventilators chaukhats in position. |
| 669 | Door Chaukhats |
| 670 | Windows Chaukhats |
| 671 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 672 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete |
| 673 | (a) 250 mm x 10mm |
| 674 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 675 | Supply & fixing of flush doors commercial quality conforming to I.S. 2202 Part 1 (1983) including fixing and adjustment of hinges bolts locks handles springs fitting with necessary screws to be supplied departmentally. (a) 35mm thick |
| 676 | (a) Single leaf |
| 677 | both side laminated |
| 678 | Extra for providing lipping with 2nd class eak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 679 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 680 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 681 | Suspended floors, roofs, landings, balconies and access platform. |
| 682 | SEPTICK TANK & SOAPIT TANK |
| 683 | Excavation in Foundation in ordinary soil (Loam clay, or sand) including lift upto 1.5 metre (5 fts.) and lead upto 30m (100 fts) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-in-charge upto a distance of 30 m. (100 fts) from the foundation trenches. (Rate is including Royality). |
| 684 | From 0.00 mt to 1.50 mt |
| 685 | 1.50mt to 3.0 mt |
| 686 | 3.0 mt to 4.50 mt |
| 687 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 688 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone grit im the proportion of 1:1.5:3 in lintels of doors and windows excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-20. |
| 689 | As in item no. 3 above but for slabs (Using 1:1.5:3 Mix concrete) |
| 690 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 691 | Suspended floors, roofs, landings, balconies and access platform. |
| 692 | M-150 brick work in 1:4 (one cement and four coarse sand sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 693 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 694 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 4 Coarse sand |
| 695 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 696 | Providing and fixing soil, waste and vent pipes : 75mm diameter : Sand cast iron S&S pipe as per IS: 1729 |
| 697 | Providing M.S. foot rests including fixing in manoholes with 20x20x10 cm cement concrete blocks 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as per standard design:(With 20x20mm square bar) |
| 698 | Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 699 | EXTERNAL AND DRANAGE |
| 700 | SUB HEAD - I - (SEWERAGE AND DRAINAGE) |
| 701 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : |
| 702 | All kinds of soil |
| 703 | Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. |
| 704 | Open timbering in trenches including shuttering and shoring complete. (Measurement to be taken of the face area timbered) |
| 705 | Depth not exceeding 1.5 meter |
| 706 | Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto the haunches of pipes including bed concrete as per standard design |
| 707 | 150 mm. dia. RCC Pipes |
| 708 | 250 mm. dia. RCC Pipes |
| 709 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. |
| 710 | 150 mm. dia. RCC Pipes |
| 711 | 250 mm. dia. RCC Pipes |
| 712 | Providing and fixing square-mouth S.W. gully trap SP-1 complete with C.I. grating, brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design |
| 713 | 150 x 100 mm size P type |
| 714 | With common burnt clay FPS (non modular) bricks of class designation 75 |
| 715 | Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete: |
| 716 | 100 mm diameter |
| 717 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design. |
| 718 | Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg). |
| 719 | With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 720 | Extra for depth for manholes: |
| 721 | Size 90x80cm |
| 722 | With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 723 | Providing orange colour safety foot rests of minimum 6 mm thick plastic encapsulated as per IS:10910 on 12 mm dia steel bar conforming to IS:1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm thread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 724 | TOTAL CARRIED TO SUMMARY |
| 725 | SUB HEAD - II - EXTERNAL WATER SUPPLY |
| 726 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :- |
| 727 | All kinds of soil |
| 728 | Pipes, cables etc, not exceeding 80 mm dia. |
| 729 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. |
| 730 | 25 mm dia nominal bore |
| 731 | 32 mm dia nominal bore |
| 732 | 40 mm dia nominal bore |
| 733 | 50 mm dia nominal bore |
| 734 | 80 mm dia nominal bore |
| 735 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :- |
| 736 | 25 mm dia nominal bore |
| 737 | 32 mm dia nominal bore |
| 738 | 40 mm dia nominal bore |
| 739 | 50 mm dia nominal bore |
| 740 | 80 mm dia nominal bore |
| 741 | Providing and filling sand of grading zone V or coarser grade alround the G.I. pipes in external work. |
| 742 | 25 mm dia nominal bore |
| 743 | 32 mm dia nominal bore |
| 744 | 40 mm dia nominal bore |
| 745 | 50 mm dia nominal bore |
| 746 | 80 mm dia nominal bore |
| 747 | Providing and fixing gate valve (with cap complete with bolts, nuts, rubber insertion etc. |
| 748 | 25 mm dia nominal bore |
| 749 | 32 mm dia nominal bore |
| 750 | 40 mm dia nominal bore |
| 751 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required:- |
| 752 | 50 mm dia |
| 753 | 80 mm dia |
| 754 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 75 in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design:- |
| 755 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 756 | Excavation in foundations in ordinary soil (Loam clay or sand) including lift upto 1.5 m (5 fts.) and lead upto 30 mt. (100 fts.) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-Incharges upto a distance of 30mt. (100 fts) from the foundation trenches. |
| 757 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 758 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone ballast in the proportion of 1:1.5:3 (M-20) in Footing excluding supply of reinforcement and its fixing and binding the same with 24 B.W.G.G.I. binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. Binding wire cost being inluded in the item. |
| 759 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.in Column |
| 760 | TMT Fe-500 or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 761 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles not exceeding 80mm in girth and finished even and smooth With water proofing material. (1)1 cement : 6 Coarse sand. |
| 762 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 763 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 764 | Painting two coat over priming coat (but including cost of priming coat) on steel and other metal surfaces up to 10 cm. width or girth or small articles not exceeding 0.10sqm in area white superior synthetic enamel such as LUXOL3, Hi-gloss apcolite superlac, DULUX specified brushing to give an even shade and including cleaning the surface of all dirt, dust and other foreign matter sand papering and stoping including cost of all materials, labour tools and plants etc. required for proper completion of the work. (Steel painting) |
| 765 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 766 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 767 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 768 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 769 | COST OF CATTLE TRAP |
| 770 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil. |
| 771 | Providing and laying in position cement concrete of specified gradeexcluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 772 | Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering-All work upto plinth level. |
| 773 | (a) 1:2:4 (1 cement : 2 course sand : 4 graded stone aggregate 20 mm nominal size ) 4.1.3 |
| 774 | Providing and fixing T-iron frames for doors,windows and ventilators of mild steel Tee-sections,joints mitered and welded with 15*3mm lugs 10 cm long embededded in cement concrete blocks 15*10*10 cm of 1:3:6 ( 1 cement : 3 course sand :6 graded stone aggregate 20 mm nominal size ) or with wooden plugs and screws or rawl plugs and screws or with fixing clips or with bolts and nuts as require including fixing of necessary but hinges and screws and applying a priming coat of approved steel primer. (10.13.1) |
| 775 | G.I. Pipe (80 MM DIA) 18.12.8 |
| 776 | DRAIN |
| 777 | Earth work in excavation |
| 778 | P.C.C. 1:4:8 |
| 779 | B/W in 1:4 Cement Coarse Sand |
| 780 | R.C.C. work |
| 781 | Centering & shuttering |
| 782 | M.S. work in R.C.C. |
| 783 | 12 MM thick plaster (1:3) coarse sand |
| 784 | BOUNDARY WALL |
| 785 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 786 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 787 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.in Plinth band |
| 788 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chaijjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 789 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.in Column |
| 790 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 791 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in footing |
| 792 | TMT Fe-500 or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 793 | Brick work with common burnt clay F.P.S. (non modular) bricks of class 150 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 794 | M-150 Brick work in super-structure above plinth level up to floor two level ( up to two storeys ) including necessary cutting and moulding of brick work as required and also including honeycombed brick work in thickness of wall more than 12cms. (1:6 cement : Coarse sand). |
| 795 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class 150 in foundations and plinth in : cement mortar 1:4 (1 cement : 4 coarse sand) |
| 796 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1)1 cement : 6 Coarse sand. 2.25 F.M. |
| 797 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 798 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 799 | Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-ironframe or to the wall with dash fastener, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge. |
| 800 | Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m height of wall with existing angle iron ‘Y’ shaped placed 2.4 m or 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5mm thick) wire of high tensile strength of 165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) |
| 801 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 802 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 803 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 804 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 805 | INTERLOCKNIG WORK |
| 806 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 807 | Excavation in foundations in ordinary soil (Loam clay or sand) including lift upto 1.5 m (5 fts.) and lead upto 30 mt. (100 fts.) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-Incharges upto a distance of 30mt. (100 fts) from the foundation trenches. |
| 808 | Prepration and consolidation of sub grade with power road roller of 8 to12 tonne capacity after excavating earth to an average of 22.5 cm depth , dressing to camber and consolidating with road roller including making good undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead up to 50 meters. |
| 809 | Class -150 brick work in 1:4 cement and coarse sand mortar in foundation and plinth including supply of all materails , labour tools and plants etc. required for proper completetion of the work. |
| 810 | Providing and laying cement concrete 1:4:8 ( 1 cement : 4 coarse sand : 8 graded stone ballast 40 mm. nominal size ) indcluding supply of all materials , labours and T & P etc. required for proper completion of the work and curing complete , Also including cost of form work in foundation. |
| 811 | Construction of granular sub base by providing close graded material conforming to specifications , mixing in mechanical mix plant at OMC , carriage of mixed material by ippers to work site, For all leads & lifts , spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density , complete as per specification and directions of engineering - charge with material conforming to grade II (size range 53mm to 0.075 mm ) having CBR value 25. |
| 812 | Providing and laying 60 mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 813 | Cement plaster 1:3 (1 cement :3 coarse sand ) finished with a floating coat of neat cement 20 mm cement plaster. |
| 814 | HANDPUMP |
| 815 | Transportation and hire charges of drilling machine, casing pipe and other accessories to site i/c Erection & dismantling of machine as required for proper completion of work as per direction of E/I. |
| 816 | Supply of 110 mm dia casing pipe for boaring 6 Kg./sqcm. ISI approved superior quality (10' length) including jointing including supply of all materials, labour and T&P etc. complete. |
| 817 | Same as item no. 2 above but PVC slotted pipe with end caps covered with nylon jali etc. complete as per direction of the Engineer- in- charge. |
| 818 | Boring charges for 110-125 mm dia PVC pipe by hand or machine and cleaning the bore including lowering etc. till the clear drining water obtained as per satisfaction of the Engineering-in-charge. |
| 819 | Supply & fixing of nylon jali around the slotted pipe complete as required. |
| 820 | Lowering of 110 mm dia Rigid P.V.C. pipe in bore hole including cutting, jointing etc. complete. |
| 821 | Supply & filling of approved coarse sand in bore between bore & PVC casing pipe after lowering of PVC pipe including supply of all materials, labours, T& P |
| 822 | S/F 32mm dia GI pipe B class approved quality ISI mark i/c supply of all materials & specials complete as per direction of E/I. |
| 823 | Supply & fixing of GI India marka II Handpump machine with connecting rods. Chain washer, valve, reducer, cylender etc. Connecting rod being 12 mm dia plain M.S. rod required for proper completion of work to the satisfaction of Engineer-in charge. Complete. |
| 824 | Installation of India marka II Handpump over the bore hole as per direction. |
| 825 | Development of bore by manual labour till discharge of free from turbity. |
| 826 | Making platform as per standard design & drawing approved by Engineer-in- charge. |
| 827 | Making drain as per standard design & drawing approved by Engineer-in- charge. |
| 828 | Supply & fixing of 110 mm OD PVC well plug of heavy quality. |
| 829 | C.C ROAD |
| 830 | Prepration and consolidation of sub grade with power road roller of 8 to12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead up to 50 meters. (DSR 16.1 ) |
| 831 | Earth work in excavation. (DSR-2.6.1) |
| 832 | Providing and laying in cement concrete 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) and curing complete, including cost of form- work, in foundation and floors. |
| 833 | Construction of granular sub base by providing close graded material conforming to specifications , mixing in mechanical mix plant at OMC , carriage of mixed material by ippers to work site, For all leads & lifts , spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density , complete as per specification and directions of engineering - charge with material conforming to grade II (size range 53mm to 0.075 mm ) having CBR value 25. |
| 834 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for thefollowing grades of concrete.Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 835 | Cutting and Making expansion joint size of 8mm width and 18-20 mm deep in R.C.C. road through to heavy duty R.C.C. cutting machine and fitting polysulphide sealent in expansion joint size of 8 mm wide and 3 mm depth including sealent 8 mm x15 mm with debounding strips as per direction of Engineer in -charge |
| 836 | B/W in Toe wall (1 cement : 4 coarse sand ) |
| 837 | Cement plaster 1:3 (1 cement :3 coarse sand ) finished with a floating coat of neat cement 20 mm cement plaster. |
| 838 | HORITECHURE |
| 839 | Uprooting rank vegetation and weeds by digging the area to a depth of 60 cm, removing all weeds and other growth with roots by forking repeatedly, breaking clods, rough dressing, flooding with water, uprooting fresh growths after 10 to 15 days and then fine dressing for planting new grass, including disposal of all rubbish with all leads and lifts |
| 840 | Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly leveling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or / and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure). |
| 841 | Supplying and stacking at site dump manure from approved source including carriage upto 1 km (manure measured in stacks will be reduced by 8% for payment) : Screened through sieve of I.S. designation 4.75 mm. |
| 842 | Spreading of sludge, dump manure or/and good earth in required thickness (cost of sludge dump manure or/and good earth to be paid separately). |
| 843 | Carrigae of manure upto 5 K.M. |
| 844 | Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge. |
| 845 | Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% : one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to 1.5 m complete (cost of sludge, manure or extra earth to be paid for separately) |
| 846 | Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately) |
| 847 | Holes 90 cm dia, and 90 cm deep |
| 848 | Holes 60 cm dia, and 60 cm deep |
| 849 | Holes 45 cm dia, and 45 cm deep. |
| 850 | Anti termite treatment by digging holes 30 cm deep and 4 cm dia, 6 to 7 holes around the tree using chemical emulsion at the rate of 1.5 liter per hole in two time or more application to get the trees free from termite infection chemicals used Chlorpyriphos 20% EC in the ratio of 1% concentration and as per direction of officer-in-charge. |
| 851 | Providing and stacking of Bottle palm of ht. 210-240 cm bottom girth 30-35 cm well developed in big HDPE bags. |
| 852 | Providing and stacking of Adansonia digitata (kalp vricksh) of ht 150-165 cm in bag size of 25 cm as per direction of the officer-in-charge. |
| 853 | Providing and stacking of Fishtail palm of ht. 270-300 cm bottom girth 40-50 cm well developed in big size HDPE bags as per direction of the officer-in-charge. |
| 854 | Providing and stacking of Ficus benjamina (green) of height 150-165 cm., bushy with healthy branches and lush green foliage in big size HDPE bags as per direction of the officer-in-charge. |
| 855 | DRILLING 160 RM & LOWERING 140 MT. PVC PIPE |
| 856 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge. |
| 857 | 400 dia & Upto 90 metre depth |
| 858 | 400 dia & Beyond 90 metre & upto 150 metre depth |
| 859 | Supplying, assembling, lowering and fixing in vertical position in bore well,unplasticized PVC medium well casing (CM) pipe of required dia,conforming to IS: 12818, including required hire and labour charges, fittings& accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. |
| 860 | 200mm nominal size dia |
| 861 | Supplying, assembling, lowering and fixing in vertical position in bore wellunplasticized PVC medium well screen (RMS) pipes with ribs, conformingto IS: 12818, including hire & labour charges, fittings & accessories etc.all complete, for all depths, as per direction of Engineer-in-charge. 200 mm nominal size dia. |
| 862 | Providing and lowering G.I. pipes complete with G.I. fittings including trenchingand refilling etc. 65 mm dia nominal bore (Column pipe). |
| 863 | Transportation, Erection & Dismantling of Rig machine. |
| 864 | Logging of bore hole by departmental / approved electric logger. |
| 865 | Supplying, filling, spreading & leveling pea gravel (Kanpur Zone) |
| 866 | Transportation, Erection & Dismantling of 150 PSI Compressor |
| 867 | Charges for development by 150 PSI Compressor Per Hr. |
| 868 | Transportation, Erection & Dismantling of 1 Cusec O.P. Unit |
| 869 | Charges for development of TW by 1 cusec OP Unit |
| 870 | SITC of Pumping plant including starter, control Panal, cable, complete in all respect with all required material T&P labour etc. [5.0 H.P. ] |
| 871 | Tubewell assembly |
| 872 | Supply and wiring of 3 number 16 sq. mm. FRLSH PVC insulated 1100V grade multistrand single core copper conductor cable in 40mm dia heavy guage rigid steel conduit on surface, with two number 10 SWG copper earth continuity wire etc, complete in all respect |
| 873 | From Transformer to Panel |
| 874 | Water Supply of tanker 5000 litre capacity of boring. |
| 875 | PUMP ROOM |
| 876 | Earth work in excavation in trenches for foundation pipes, cable etc in ordinary soil (Loam clay or sand) inlcuding lift upto 1.5 Mt. lead upto 30mt. and dressing of sides and rammings of bottom and disposal of surplus excavated earth as directed by the engineer. |
| 877 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 878 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 879 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 880 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 881 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 882 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 883 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size) PLLINTH BAND |
| 884 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). |
| 885 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). |
| 886 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 887 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 888 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement :4 coarse sand) |
| 889 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 890 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 891 | Providing & laying \\"brick Coba\\" 120mm thick laid with M-150 class brick bat coba 7.50 cm thick with gap of 15mm to each other, over 20mm thick base of cement mortar 1:4 cement and coarse sand mixed with water proofing compound spreading cement slurry mixed with acrylic cement concrete water proofing compound filled gaps of |
| 892 | coba & top of coba mortar mixed with water proofing compound in 1:4 cement and coarse sand mortar finished smooth & top mashed false square 30 cm x 30 cm and side wall parapet shall be mono lythic plaster wall upto 30cm higher and junction and corner shall be rounded by brick |
| 893 | ballast cement and coarse sand masonry coba with top finished plaster mixed with acetic water proofing compound @ 2% by weight & including S/o all material, labour T & P etc complete for proper completion of work. |
| 894 | Providing and fixing 1 mm thick M.S. sheet sliding-shutters, with frame and diagonal braces of 40x40x6 mm angle iron, 3 mm M.S. gusset plates at the junctions and corners, 25 mm dia pulley, 40x40x6 mm angle and T- iron guide at the top and bottom respectively, including applying a priming coat of approved steel primer. |
| 895 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 896 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 897 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 898 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 899 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 900 | Fixing of Door, windows/ventilators chaukhats in position. |
| 901 | Windows Chaukhats |
| 902 | 15 mm plinth plaster (1 cement :4 coarse sand) |
| 903 | 12mm cement plaster in single coat on fair side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or rounded angles not exceeding 80mm in girth and finished even and smooth no extra for mixing any additive. (1) 1 cement : 6 coarse sand . F.M.-2.25 |
| 904 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand . F.M.-2.25 |
| 905 | Ceiling area |
| 906 | Making grooves 10 to 12mm wide x 8mm deep in plaster of the wall or in ceiling vertically or horizontally as required. |
| 907 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate |
| 908 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick |
| 909 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. (a) 40 mm wide and 4 mm thick |
| 910 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 911 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 912 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC contentless than 50 gram/litre |
| 913 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 914 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 915 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete : 250x16 mm. |
| 916 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete : 10 mm dia and screw. |
| 917 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete : 125 mm. |
| 918 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 919 | Suspended floors, roofs, landings, balconies and access platform. with water proof ply 12 mm thick. |
| 920 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. with water proof ply 12 mm thick |
| 921 | PROPOSED PUMP HOUSE |
| 922 | SUB-HEAD - I : INTERNAL WIRING |
| 923 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 924 | Group - C |
| 925 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 926 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 927 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 928 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 929 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 930 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 931 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 932 | SUB-HEAD II - FANS & LIGHT FIXTURES: |
| 933 | Supply of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 4000K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.9. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 21W (including driver). |
| 934 | Supplying of Bulkhead type light fitting complete with, wire guard, holder, electronic ballast 1 x 10 W lamp including connections etc.Including connection with 1.5 sqmm FRLS PVC insulated copper conductor as required. |
| 935 | SUBHEAD- III: DISTRIBUTION BOARD |
| 936 | Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 937 | 8 way, Double door |
| 938 | Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 939 | 40 amps DP MCB |
| 940 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 941 | Single pole |
| 942 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 943 | SUBHEAD: - IV - EARTHING |
| 944 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each |
| 945 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. |
| 946 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 947 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 948 | EXTERNAL RAIN WATER HARVESTING WORKS |
| 949 | RAIN WATER HARVESTING PIT |
| 950 | RECHARGE PITS |
| 951 | Earth work in exacavation in trenches for foundations and for pipes cables etc. in ordinary soil(loam clay or sand) including lift upto 1.5 m and dressing of sides and ramming of bottom sand disposal of surplus excavated earth as directed by the Engineer i/c with in a lead of 50m. |
| 952 | In all kind of soil upto 1.5m depth |
| 953 | In all kind of soil upto 1.5m to 3.0m. depth |
| 954 | In all kind of soil upto 3.0m to 4.5m. depth |
| 955 | In all kind of soil upto 4.5 m to 6.0m. depth |
| 956 | Providing and laying in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded Stone aggregate 20 mm nominal size) and curing complete,including cost of form- work,in foundation and floors. |
| 957 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 958 | Reinforcement cement concrete work in RCC culvert slab with 1:1.5:3 (1 cement : 1.5 coarse sand and 3 gradded stone aggregate of 20 mm nominal size) excluding centering and shuttering and reinforcement. |
| 959 | Centering and shuttering including strutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform. |
| 960 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 961 | 12mm cement plaster on rough side of single or half brick wall mix |
| 962 | 1:3 (1 cement : 3 Coarse sand) |
| 963 | Providing M.S. foot rests including fixing in manoholes with 20x20x10 cm cement concrete blocks 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as per standard design: |
| 964 | With 20x20mm square bar |
| 965 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. |
| 966 | M.D. -10- Circular shape 500mm internal diameter |
| 967 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. |
| 968 | Drilling of 300mm dia bore hole manually. |
| 969 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. |
| 970 | 150 mm nominal size dia |
| 971 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 972 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 973 | Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -incharge. |
| 974 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 975 | DESILTING CHAMBER |
| 976 | Earth work in exacavation in trenches for foundations and for pipes cables etc. in ordinary soil(loam clay or sand) including lift upto 1.5 m and dressing of sides and ramming of bottom sand disposal of surplus excavated earth as directed by the Engineer i/c with in a lead of 50m. |
| 977 | In all kind of soil upto 1.5m depth |
| 978 | In all kind of soil upto 1.5m to 3.0m. depth |
| 979 | Providing and laying in cement concrete 1:2:4 (1 cement :2 coarse sand:4 graded Stone aggregate 20 mm nominal size) and curing complete,including cost of form- work,in foundation and floors. |
| 980 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 981 | Reinforcement cement concrete work in RCC culvert slab with 1:1.5:3 (1 cement : 1.5 coarse sand and 3 gradded stone aggregate of 20 mm nominal size) excluding centering and shuttering and reinforcement. |
| 982 | Centering and shuttering including strutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform. |
| 983 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 984 | 12mm cement plaster on rough side of single or half brick wall mix |
| 985 | 1:3 (1 cement : 3 Coarse sand) |
| 986 | Providing M.S. foot rests including fixing in manoholes with 20x20x10 cm cement concrete blocks 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as per standard design: |
| 987 | With 20x20mm square bar |
| 988 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality. |
| 989 | M.D. -10- Circular shape 500mm internal diameter |
| 990 | COST OF EACH RAIN WATER HARVESTING |
| 991 | RAIN WATER HARVESTING PIPE & CHAMBER |
| 992 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : |
| 993 | All kinds of soil |
| 994 | Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. |
| 995 | Open timbering in trenches including shuttering and shoring complete. (Measurement to be taken of the face area timbered) |
| 996 | Depth not exceeding 1.5 meter |
| 997 | Providing and laying cement concrete 1:5:10 (1 cement: 5 coarse sand : 10 graded stone aggregate 40mm nominal size) upto the haunches of pipes including bed concrete as per standard design |
| 998 | 150 mm. dia. RCC Pipes |
| 999 | 250 mm. dia. RCC Pipes |
| 1000 | 300 mm. dia. RCC Pipes |
| 1001 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. |
| 1002 | 150 mm. dia. RCC Pipes |
| 1003 | 250 mm. dia. RCC Pipes |
| 1004 | 300 mm. dia. RCC Pipes |
| 1005 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design. |
| 1006 | Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg). |
| 1007 | With common burnt clay FPS (non modular) bricks of class designation 7.5 |
| 1008 | Providing orange colour safety foot rests of minimum 6 mm thick plastic encapsulated as per IS:10910 on 12 mm dia steel bar conforming to IS:1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm thread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. |
| 1009 | GENETOR |
| 1010 | Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 1011 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. |
| 1012 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 1013 | Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 kms. from the site of work and including watering, dressing etc rate to include cost of all materials labour T & P etc required for proper completion of work. |
| 1014 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. |
| 1015 | (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm |
| 1016 | (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 1017 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C. work in Plinth Band |
| 1018 | R.C.C. work with cement approved coarse sand and 2 cm. guage approved stone grit in the proportion of 1:1.5:3 in Slab of excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. including cost of binding wire. The rate excludes making of drip course which shall be paid extra. |
| 1019 | R.C.C. work with cement approved coarse sand and 2 cm. guage approved stone grit in the proportion of 1:1.5:3 in Beam excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. including cost of binding wire. The rate excludes making of drip course which shall be paid extra. |
| 1020 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :. 1:1.5:3 (1 cement : 1.5 coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) R.C.C.work in column |
| 1021 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) R.C.C.work in column |
| 1022 | R.C.C. work with cement approved coarse sand and 2 cm. guage approved stone grit in the proportion of 1:1.5:3 in Footing excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. including cost of binding wire. The rate excludes making of drip course which shall be paid extra. |
| 1023 | Class M-150 brick work in 1:6 cement coarse sand (of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour, tools and plants etc. required for proper completion of the work. |
| 1024 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). |
| 1025 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 1026 | Brick work in super-structure above plinth level up to floor two level (up to two storeys) including necessary cutting and moulding of bricks as required and also including honey comb brick work thickness of wall not to be less than 1.5 brick thick. (1:6 cement & coarse sand) |
| 1027 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 1028 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:3 (1 cement: 3 coarse sand) |
| 1029 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 fine sand |
| 1030 | 12 mm cement plaster in single coat on fair side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 coarse sand. |
| 1031 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 1032 | Mild steel or iron work of small sizes and sections such as holding down bolts, hold fast tierods,gratings etc. (when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work fabrication of holes doors, chaukhats nosing. |
| 1033 | Providing & fixing of hold fast for chaukhats of doors and windows. |
| 1034 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment). |
| 1035 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. |
| 1036 | Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) |
| 1037 | Fixed window / ventilator without mullion / transom. Using R2 series with frame (89 mm & above) x (39 mm & above). (Height upto 1.2 metre) |
| 1038 | Fixing of Door, windows/ventilators chaukhats in position. |
| 1039 | (b) Window chaukhats |
| 1040 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface). |
| 1041 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 1042 | Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger,J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Ceiling) |
| 1043 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 1044 | Providing and laying cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to |
| 1045 | IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. d) Finishing the surface with 20 mm thick |
| 1046 | jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 1047 | Painting or Vanishing two coat on iron work in small areas or new wood work with one coat of ready mixed priming paint and one coat of approved superior ready mixed paint of clear synthetic varnish including supply of all materials, labour, T & P etc. required for proper completion the work. Paint to be used should confirm to the I.S.I. No. 103 1950. |
| 1048 | 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 1049 | Providing and laying 60 mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 1050 | 20mm thick cement plaster in two coats backing cost 17mm and finishing coat 3mm thick of neat cement and marble dust in ratio 5:1 on rough side of single or half brick interior plastering upto floor two level including internal rounded angles. (I) 1cement : 3 coarse sand |
| 1051 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cementslurry, but excluding the cost of nosing of steps etc. complete.25 mm At APRON |
| 1052 | Supply and fixing rolling sutters of approved make of 80 x 125 mm (3\\" x 18gauge) cold rolled MS Lath inter lockedthrough their entire length and joinedtogether at the end by locks and mountedon specially designed pipe shaft with brackets. |
| 1053 | Providing and fixing ball bearing for rollong shutters. |
| 1054 | Providing & fixing of Angle iron frame 40*40*6 mm |
| 1055 | Fencing with R.C.C. post placed at required distance, embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post one side only, provided with horizontal lines and two diagonals of barbed wire weighing 9.38 kg per 100 metres (minimum), between the two posts fitted and fixed with G.I. staples on wooden plugs or G.I. binding wire tied to 6 mm bar nibs fixed while casting the post (cost of R.C.C. posts, struts, earth work and concrete to be paid for separately) :- Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire |
| 1056 | Mild steel or iron work in heavy sizes such as trusses built up gates, door frames, record racks, roof work gates etc. wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work fabrication of holes doors, chaukhats nosing. |
| 1057 | Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm). |
| 1058 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 1059 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 1060 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 1061 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 1062 | Suspended floors, roofs, landings, balconies and access platform. |
| 1063 | GENETOR |
| 1064 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 1065 | Group C |
| 1066 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 1067 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 1068 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 1069 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 1070 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 1071 | 2 x 16 sq.mm. + 1 x 6 sq.mm. earth wire |
| 1072 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 1073 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 1074 | 25 mm |
| 1075 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 1076 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 1077 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 1078 | 1 or 2 Module |
| 1079 | 3 Module |
| 1080 | 4 Module |
| 1081 | 8 Module |
| 1082 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 1083 | 5/6 amps switch |
| 1084 | 15/16 amp switch |
| 1085 | 3 pin 5/6 amp socket outlet |
| 1086 | 6 pin 15/16 amp socket outlet |
| 1087 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 1088 | (a): Up to 450mm sweep |
| 1089 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 1090 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 1091 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 1092 | 1200 mm sweep ceiling fan |
| 1093 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 1094 | Supply of LED Tube Light 40 watt Polycarbonate tube light complete including tube etc suitable for both wall & surface complete in all respects. |
| 1095 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. |
| 1096 | Suuply and fixing of single LED light wall bracket on matching M.D.F.E.G board base etc. complete in all respect. |
| 1097 | Supply of recess/Surface mounting round 12 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. |
| 1098 | Supply and fixing of Angle Holder With 5W Bulb etc suitable for both surface & surface complete in all respects. |
| 1099 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design |
| 1100 | SUBHEAD III-DISTIBUTION BOARD |
| 1101 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 1102 | 8 way, Double door |
| 1103 | 12 way, Double door |
| 1104 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 1105 | 4 way Double door (4 + 12) |
| 1106 | 6 way Double door (4 + 18) |
| 1107 | 8 way Double door (4 + 24) |
| 1108 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 1109 | 4 way Double door (4 + 12) |
| 1110 | 8 way Double door (4 + 12) |
| 1111 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 1112 | For 4 way, Double door TPN MCBDB |
| 1113 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 1114 | For 4 way, Double door TPN MCBDB |
| 1115 | For 6 way, Double door TPN MCBDB |
| 1116 | For 8 way, Double door TPN MCBDB |
| 1117 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 1118 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 1119 | 8 way Double door |
| 1120 | 14 way Double door |
| 1121 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1122 | Single pole |
| 1123 | Supplying and fixing , 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 1124 | 63A DP |
| 1125 | 63A 4P |
| 1126 | 40A 4P |
| 1127 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 1128 | SUBHEAD IV-EARTHING |
| 1129 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 1130 | SUBHEAD V -MISCELLANEOUS |
| 1131 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 1132 | FIRE FIGHTING WORKS: |
| 1133 | SUB HEAD - I (PUMPING EQUIPMENTS) |
| 1134 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 1135 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520. |
| 1136 | Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for nclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 1137 | M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
| 1138 | Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 1139 | 450 lpm at 35 m Head. |
| 1140 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required |
| 1141 | 1.2 Meter high and 250 mm dia. |
| 1142 | Supply, Installation, testing and commissioning of pressure switches for Hydrant / Diesel Engine Driven Pump / Jockey Pumps, diaphragm type, adjustable range from 0-9 bar and a regulation range of 0.1 - 1.5 bar direct mounted SNAP acting type made from die cast aluminium with epoxy powder coated finish and SS316 diaphragm and other wetted parts, including necessary wiring upto control panel & other materials as required as per specifications. |
| 1143 | SLTC of M.S. pipe on surface |
| 1144 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 1145 | 100 mm dia |
| 1146 | 25 mm dia |
| 1147 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 1148 | 100 mm dia |
| 1149 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 1150 | 100 mm dia |
| 1151 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 1152 | Supply, Installation, Testing and Commissioning of 100 mm dia Bourden type, Stainless Steel dial type Pressure Gauge including brass isolation valve and siphon pipe having calibration of 0 - 16 Kg / cm2 . |
| 1153 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange |
| 1154 | 100 mm dia |
| 1155 | Supplying and Fixing of Fire Man's axe with heavy insulated rubber as per standard conforming to IS 926. |
| 1156 | Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications. |
| 1157 | 100 mm dia |
| 1158 | SUB HEAD - III - (HYDRANTS SYSTEM) |
| 1159 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following asrequired. 20 mm nominal internal dia water hose thermoplastic(Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metalvalve & M.S. Pipe and socket |
| 1160 | SITC weather proof M.S Door and glass fire door size 2100 mm x 900 mm or as per arch. |
| 1161 | Supplying, installation, testing and commissioning of weather proof M.S door and glass fire door size 2100 mm x 900mm fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following: - |
| 1162 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 1163 | 2 way-100 mm dia M.S. Pipe |
| 1164 | TOTAL |
| 1165 | SUB HEAD - IV - (FIRE EXTINGUISHERS) |
| 1166 | Supply & fixing of fire extinguisher, ABC Type 6.00 kg. capacity(ISI Marked IS:15683 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.PWD-2018-1131(A) |
| 1167 | Supply & fixing of CO2 type fire extinguisher, 6.5 kg. capacity(ISI Marked IS:2878 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.PWD-2018-1132(A) |
| 1168 | TRANSFORMER |
| 1169 | SITC of 400KVA 11KV/433V Dyn11 Copper Wound Oil Type Transformer with OCTC +5% to -10% in steps of 2.5% , Class of Insulation: A, Temperature rise limits of 40 deg.C over ambient of 50 degrees. Losses (As per IS tolerances) and all accessories and confirming to As per IS 1180 Level 1 & Testing parameter as per IS 2026 complete with all fittings and accessories as per specifications attached etc as required at site. |
| 1170 | Note:Foundation work for transformer is not included in Electrical works it will come on Civil work. |
| 1171 | SITC of H.T. VCB (11KV) |
| 1172 | 11 KV HT VCB FOUR BREAKER PANEL BOARD (INDOOR TYPE) (1 INCOMMING) |
| 1173 | Design, manufacturing, testing at works, supply of HT Panel as per specification and comprising of the following :- |
| 1174 | INCOMER |
| 1175 | a) Incomming - 1 No, 630 Amp, VCB. |
| 1176 | b) 1 No.- 11 KV / 110 Volt PT class 0.5 accuracy and 100 VA burden with 1 No. voltmeter (0-12 KV), digital type, selector switch for voltmeter and protection MCB for HT Metering up to 12 KV on incommer. |
| 1177 | c) 1 No.- (0 - 120 A) dual scale Ammeter, digital type, selector switch for ammeters. |
| 1178 | d) 1 No - Microprocessor based numericak relay with O/C, E/F and S/C protection. |
| 1179 | e) 1 No - set of dual core dual ratio 3 CTs 100/5A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection. |
| 1180 | f) 1 No. electronic type digital energy analyser having 30 days memory and parameters of KW, KWH, Power factor, frequency etc. Suitable for BMS compatible with all accessories. |
| 1181 | g) 1 No. hooter with hooter acceptance and reset push button. |
| 1182 | h) 1 No - Red, Yellow & Blue for phase indication. |
| 1183 | i) 1 No - Amber for Trip indication. |
| 1184 | j) 1 No - Red `ON' Green `OFF'indication. |
| 1185 | k) 1 No - Spring charge indication. |
| 1186 | l) 1 No - Auto trip indication. |
| 1187 | m) 1 No. hooter with hooter acceptance and reset push button. |
| 1188 | n) 1 No. master trip relay. ( Electromechanical Type ) |
| 1189 | o) 1 No.Trip ckt supervision relay. (Electromechanical Type ) |
| 1190 | HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above in item nos.A and B and as per specifications. |
| 1191 | TOTAL OF SUB-HEAD I (NON SCH.) |
| 1192 | SUBHEAD II- DG SETS |
| 1193 | SITC 125 KVA RADIATOR COOLED D.G. SET IN ACOUSTIC ENCLOSURE WITH AMF OR Equivalent & Exhaust System with complete Accessories. |
| 1194 | SUB-HEAD-II (HT CABLES ) |
| 1195 | Supply and laying of 3 core standered aluminium conduktor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098(Part-II with latest amendments) 11 KV grade at a depht of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks in sides and on the top put across. The armouring of cable shall be properly connected with earth condutor by clamps etc. |
| 1196 | 300 sq. mm 3 Core |
| 1197 | Supply and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required. |
| 1198 | Supply and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for 3 core 300 Sq.mm. XLPE aluminium conductor cable of 11 kV grage as required. |
| 1199 | SUBHEAD III-EARTHING AND LOOP EARTHING |
| 1200 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing. |
| 1201 | Supply and burring of Safe Earthing Electrode T-39 AAlloy Coated, Length 3000mm, outer pipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing.d. |
| 1202 | Supply and laying of 50mm x 6mm G.I. strip from earth electrode directly in the ground as required complete in all respects. |
| 1203 | Supply and Laying of 50mm X 6 mm Copper strip from earth electrode directly in the ground as required complete in all respects. |
| 1204 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 1205 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 1206 | SUBHEAD IV- SAFETY EQUIPMENTS |
| 1207 | Providing and fixing MV danger notice plate of 200 mm x 150 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required. |
| 1208 | Providing and fixing HT danger notice plate 250 mm x 200 mm made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required. |
| 1209 | Supplying and Fixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge. |
| 1210 | Supplying & Laying of 1800 mm x 900 mm X 12 mm thick chequered rubber matting of tested quality |
| 1211 | Supply and fixing danger board fabricated from 10 gauge MS sheet as per IE Rules |
| 1212 | S/F of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T & P for proper completion of work. |
| 1213 | Providing & fixing in position 1000 mm wide, Electrical Insulating Mats, 2mm thick, suitable upto 1.1 KV grade including cutting to required length complete as required per specifications or upto the satisfaction of engineer-in-charge. |
| 1214 | Supplying and Laying of Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006 etc. as reqd. |
| 1215 | Supply of Tool & First Aid Box with all necessary tools for maintenance of electrical installation & First aid. |
| 1216 | SUBHEAD V-EXTERNAL LIGHTING |
| 1217 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12 mm thik) having 3mm thikness with Single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. |
| 1218 | Supply and fixing of LED street light fitting having die cast aluminium body and diffuser with driver set suitable for 45 watt to 50 watt. Confirming to IP 66 and above protection complete in all respect. |
| 1219 | Supply and fixing of 20 Amp DP MCB (10KA) (C curve) for poles |
| 1220 | Supply and fixing of Bakelite sheet 3 mm thick of suitable size & connector |
| 1221 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminiumhousing built with dirver set suitable for 65 to 80 Watt. Confirming to IP 66 protection complete in allrespect. |
| 1222 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 1223 | 3.5C x 300 sqmm aluminium conductor, A2XWY. |
| 1224 | 3.5C x 240 sqmm aluminium conductor, A2XWY. |
| 1225 | 3.5C x 150 sqmm aluminium conductor, A2XWY. |
| 1226 | 3.5C x 120 sqmm aluminium conductor, A2XWY. |
| 1227 | 3.5C x 95 sqmm aluminium conductor, A2XWY. |
| 1228 | 3.5C x 70 sqmm aluminium conductor, A2XWY. |
| 1229 | 3.5C x 50 sqmm aluminium conductor, A2XWY. |
| 1230 | 3.5C x 35 sqmm aluminium conductor, A2XWY. |
| 1231 | 3.5C x 25 sqmm aluminium conductor, A2XWY. |
| 1232 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 1233 | 4C x 10 sqmm aluminium conductor, 2XWY. |
| 1234 | 2C x 16 sqmm aluminium conductor, 2XWY. |
| 1235 | 2C x 10 sqmm aluminium conductor, A2XWY. |
| 1236 | 2C x 6 sqmm aluminium conductor, A2XWY. |
| 1237 | Supplying following 1.1kV grade, XLPE insulated, FRLS type control cables,suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 1238 | 2C X 2.5 sqmm copper conductor |
| 1239 | 4C X 2.5 sqmm copper conductor |
| 1240 | 6C X 2.5 sqmm copper conductor |
| 1241 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 1242 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 1243 | Above 35 sq. mm and upto 95 sq. mm (clamped with 1mm thick saddle) |
| 1244 | Above 95 sq. mm and upto 185 sq. mm (clamped with 1mm thick saddle) |
| 1245 | Above 185 sq. mm and upto 400 sq. mm (clamped with 1mm thick saddle) |
| 1246 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 1247 | 3½ X 300 sq. mm (70 mm) |
| 1248 | 3½ X 240 sq. mm (62mm) |
| 1249 | 3½ X 185 sq. mm (57mm) |
| 1250 | 3½ X 120 sq. mm (50 mm) |
| 1251 | 3½ X 95 sq. mm (45 mm) |
| 1252 | 3½ X 70 sq. mm (38mm) |
| 1253 | 3½ X 50 sq. mm (32mm) |
| 1254 | 3½ X 35 sq. mm (32mm) |
| 1255 | 3½ X 25 sq. mm (28mm) |
| 1256 | 4 X 16 sq. mm (28mm) |
| 1257 | 4 X 10 sq. mm (25mm) |
| 1258 | 2 X 16 sq. mm (22mm) |
| 1259 | 2 X 10 sq. mm (19mm) |
| 1260 | 2 X 6 sq. mm (19mm) |
| 1261 | 2C X 2.5 sqmm copper conductor (19mm) |
| 1262 | 4C X 2.5 sqmm copper conductor (19mm) |
| 1263 | 6C X 2.5 sqmm copper conductor (19mm) |
| 1264 | SUBHEAD VI-CIVIL WORKS |
| 1265 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 1266 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 1267 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 1268 | 160 mm dia (OD-200 mm & ID-175 mm nominal) |
| 1269 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
| 1270 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. |
| 1271 | 100 mm dia |
| 1272 | 150 mm dia |
| 1273 | 250 mm dia |
| 1274 | 300 mm dia |
| 1275 | Making of following size of Cable Chamber made of 230 mm thick brick work in cement mortar (1 cement : 6 sand) with PCC 100 mm thick PCC base plastering of inner and outer surface with cement mortar including providing of Heavy Duty C.I Cover complete with digging, refilling and removal of surplus soil complete as required. |
| 1276 | 900 mm x 800 mm x 1000 mm deep |
| 1277 | 600 mm x 600 mm x 800 mm deep |
| 1278 | SITC OF MAIN PANEL FEEDER PILLAR |
| 1279 | Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications etc.complete in all respect so as to fulfill all as required. |
| 1280 | LT Panel |
| 1281 | The minimum clearances between bus bars shall be as follows : |
| 1282 | Phase to phase - minimum 20mm |
| 1283 | Phase to neutral-minimum 15mm |
| 1284 | Incoming : |
| 1285 | 1Nos 630 Amp. 4P MCCB of 36kA Breaking capacity |
| 1286 | Metering : |
| 1287 | 1 Set of CT's one of 630/ 5Amp ratio for Multifunction Meter |
| 1288 | 1 Set of CT's one of 630/ 5Amp ratio for AFCR Relay |
| 1289 | 1 Set of CT's one of 630/ 5Amp ratio for 50,50N,51,51N Relay |
| 1290 | 1 Nos. Set of Phase Indication Lamp. |
| 1291 | 1 Nos. of class-III Type SPD |
| 1292 | Bus Bar : |
| 1293 | 800 Amp.TPN aluminimum bus bar of suitable length.36KA |
| 1294 | Outgoing : |
| 1295 | Phase indication lamps on each outgoing to be provided. |
| 1296 | 03 No. 400 Amp 4P MCCB. (36 KA) |
| 1297 | 03 No. 250 Amp 4P MCCB. (36 KA) |
| 1298 | 01 No. 100 Amp 4P MCCB. (25 KA) |
| 1299 | 01 No. 63 Amp 2P MCB. (10 KA) |
| 1300 | Panel described as above |
| 1301 | EM Panel |
| 1302 | The minimum clearances between bus bars shall be as follows : |
| 1303 | Phase to phase - minimum 20mm |
| 1304 | Phase to neutral-minimum 15mm |
| 1305 | Incoming : |
| 1306 | 1 Nos. 250 Amp. 4P MCCB of 36kA Breaking capacity |
| 1307 | 1 Nos. 250 Amp. 4P ATS |
| 1308 | Metering : |
| 1309 | 1 Set of CT's one of 250/ 5Amp ratio for Multifunction Meter |
| 1310 | 1 Set of CT's one of 250/ 5Amp ratio for 50,50N,51,51N Relay |
| 1311 | 1 Nos. Set of Phase Indication Lamp. |
| 1312 | 1 Nos. of class-III Type SPD |
| 1313 | Bus Bar : |
| 1314 | One (1) No.300 Amp.TPN aluminimum bus bar of suitable length.25KA |
| 1315 | Outgoing : |
| 1316 | Phase indication lamps on each outgoing to be provided. |
| 1317 | 02 No.160 Amp 4P MCCB. (25 KA) |
| 1318 | 02 No.63 Amp 4P MCCB. (25 KA) |
| 1319 | 03 No.40 Amp 4P MCB. (10 KA) |
| 1320 | Panel described as above |
| 1321 | CAPACITOR PANEL-120 KVAR |
| 1322 | SITC APFC Panel of 120 KVAR capacity suitable for operation on 415 + 5% Volt, 3 Phase, 50Hz, AC supply, having MPP type, resin bounded, static 10,15,25 KVAR capacitors (without oil) in tier formation complete with following TPN MCCB as incomer of the panel, 7 step microprocessor based power factor controller relay capable to select the rating from 1 KVAR to multiples thereon up to max rating of the panel, current limiting contactors for each capacitors protected with MCBs, Ammeter (Analogue type) with CTs, Voltmeter (Analogue type) selector switches indicating lights, cooling fans for panel, earthing the panel with 2 Nos. 25mm x 5mm thick GI steel flat from existing earth bar, connection of APFC panel with suitable size 3.5 core aluminium conductor armoured XLPE cable from main LT panel (maximum length of cable 10 mtrs.) and compression glands etc. as reqd. The panel should have provision of timer based circuit in APFC relay to switch ON and OFF the static part automatically as and when requried. Capacity of Static capacitors should be accommodated from the overall rating of the panel and should be designed to switch in independently. The panel should be manufactured with 1.6mm thick CRCA sheet duly powder coated. |
| 1323 | Incoming |
| 1324 | One (1) No 400 Amp. 3P MCCB of 36 KA Breaking capacity |
| 1325 | 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter |
| 1326 | 1 Set of CT's one of 400/ 5Amp ratio 55 |
| 1327 | 1 Nos. Set of Phase Indication Lamp. |
| 1328 | BUS BAR |
| 1329 | 1 Set of 500 Amps TP Aluminium Bus Bars |
| 1330 | OUT GOING |
| 1331 | 02 No. 63 Amps. TP MCCB (25 KA) |
| 1332 | 04 No. 40 Amps. TP MCCB (25 KA) |
| 1333 | 01 No. 25 Amps. TP MCCB (25 KA) |
| 1334 | 01 No. 25 KVAR Capacitor Bank |
| 1335 | 01 No. 15 KVAR Capacitor Bank |
| 1336 | 06 No. 10 KVAR Capacitor Bank |
| 1337 | 02 No. 25 KVAR 7% Duty Reactor |
| 1338 | 06 No. 15 KVAR 7% Duty Reactor |
| 1339 | 01 No. 10 KVAR 7% Duty Reactor |
| 1340 | 02 No. 25 KVAR TSM |
| 1341 | 06 No. 15 KVAR TSM |
| 1342 | 01 No. 10 KVAR TSM |
| 1343 | Panel described as above |
| 1344 | SFP Outdoor Type(IP 65) -1 |
| 1345 | Incoming : |
| 1346 | One (1) No 63 Amp. 4P MCCB of 25KA Breaking capacity |
| 1347 | Metering : |
| 1348 | Multifunction Meter |
| 1349 | One (1) Set of Phase Indication Lamp. |
| 1350 | Bus Bar : |
| 1351 | One (1) No. 150 Amp.TPN aluminimum bus bar of suitable length. |
| 1352 | Outgoing : |
| 1353 | Phase indication lamps on each outgoing to be provided. |
| 1354 | 6 No.20 Amp DP MCB. (10 KA) |
| 1355 | 4 No. Single Phase Timer |
| 1356 | Panel described as above |
| 1357 | TOTAL OF SUB-HEAD VIII |
| 1358 | SUBHEAD IX- DG SETS |
| 1359 | SITC 125 KVA RADIATOR COOLED D.G. SET IN ACOUSTIC ENCLOSURE WITH AMF OR Equivalent & Exhaust System with complete Accessories. |
| 1360 | Providing, installation testing & commissioning of 'Silent Type' Diesel Generating Set along with having prime power rating 125 KVA, 415 Volts at 1500RPM, 0.8 lagging Factor at 415 V suitable for 50 Hz, 3 phase system and for 0.85 load factor and consisting of the following:- |
| 1361 | Diesel Engine |
| 1362 | Diesel Engine 4 stroke radiator cooled, electric start, of suitable bhp (CPCB-2 Compliance) having Six cylinders at 1500 RPM suitable for above output of alternator , 50% RH & at 1000 metre MSL and confirming to BS 5514, BS 649, is 10000, capable of taking 10% overloading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. The DG Set Controller shall be supplied by the same vendor of DG Set OEM. |
| 1363 | Engine Mounted Instrument Panel fitted with and having digital display for following: |
| 1364 | Start- stop switch with key. |
| 1365 | Water Temperature indication |
| 1366 | Lubrication Oil pressure indication |
| 1367 | Battery charging indication |
| 1368 | RPM indication |
| 1369 | Over Speed trip Indication |
| 1370 | Low lubrication oil Pressure trip indication |
| 1371 | Engine Hours Indication |
| 1372 | Alternator: |
| 1373 | Synchronous alternator rated at 125 KVA, 415 Volts at 1500 RPM, 3 phase 50 Hz, AC Supply with 0.8 lagging power factor , 50% RH . The alternator shall be having SPDB enclosure, brushless, continuous duty, self-excited and self-regulated through AVR confirming to IS:4722/ BS 2613 suitable for tropical conditions and with class- H insulation. Alternator shall have end termination cable box on alternator to terminate the 800A Bus Duct. |
| 1374 | Base Frame & Foundation |
| 1375 | Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. |
| 1376 | Fuel Tank: |
| 1377 | Daily service fuel tank of 990 litres capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C pipes of suitable dia. Complete with valves level indication & accessories as required as per specifications. |
| 1378 | Exhaust System : |
| 1379 | Dry exhaust mainfold with hospital grade exhaust silencer / Catalytic Convertor. |
| 1380 | Starting System: |
| 1381 | 24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 2 Nos. of batteries (25 plates, 160 AH lead Acid type) as required as per specifications. |
| 1382 | Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per specifications. The Acoustic Enclosure shall be factory fitted by the OEM. |
| 1383 | Note:Foundation work for DG SETs is not included in Electrical works it will come on Civil work. |
| 1384 | S/F OF GREEN BOARD |
| 1385 | S/F OF SOLAR SYTEM |
| 1386 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1387 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:- |
| 1388 | White Vitreous china Orissa pattern W.C. pan of size580x440 mm with integral type foot rests |
| 1389 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required |
| 1390 | W.C. pan with ISI marked white solid plastic seat and lid |
| 1391 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. |
| 1392 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm or 340x410x265 mmsizes respectively. (Manual) |
| 1393 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. |
| 1394 | White Agaria Marble Stone |
| 1395 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1396 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1397 | Providing and fixing white vitreous china laboratory sink including making all connections excluding cost of fittings : |
| 1398 | Size 450x300x150 mm |
| 1399 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1400 | Semi rigid pipe |
| 1401 | 40 mm dia |
| 1402 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1403 | 30 cm length |
| 1404 | 15 mm nominal bore |
| 1405 | 45 cm length |
| 1406 | 15 mm nominal bore |
| 1407 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1408 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 1409 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1410 | 15 mm nominal bore |
| 1411 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1412 | 15 mm nominal bore |
| 1413 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1414 | 15 mm nominal bore |
| 1415 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1416 | 15 mm nominal bore |
| 1417 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 1418 | Providing & Fixing Stainless Steel dustbin. |
| 1419 | Providing and fixing twin coat hook complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 1420 | RO Plant 40 LPH (Liter per hour) PLANT CAPACITY - 40 LPHTreated Water QualityTurbidity : <1NTUpH : 6.5-7.0Chlorides : < 10 ppmSulphates : < 5 ppmTDS : < 150 ppm |
| 1421 | Supply installation, testing and commissioning of water cooler Cooling Capacity150Ltrs. / Hrs.,Storage Capacity 40 Ltrs |
| 1422 | HANDICAPPED TOILET :- |
| 1423 | Providing and fixing of WB 46 x 36 with one pair mounting brackets, EWC & Cistern complete with fittings & seat cover, one no. hinged rail 76 cm & 4 nos. of grab rails 60 cm. |
| 1424 | TOTAL CARRIED TO SUMMARY |
| 1425 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1426 | RAIN WATER DRAINAGE WORK |
| 1427 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1428 | 110 mm dia |
| 1429 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1430 | 110 mm |
| 1431 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1432 | Coupler |
| 1433 | 110 mm |
| 1434 | Single tee with door |
| 1435 | 110x110x110 mm |
| 1436 | Single tee without door |
| 1437 | 110x110x110 mm |
| 1438 | Bend 87.5 degree |
| 1439 | 110 mm Bend |
| 1440 | Shoe (Plain) |
| 1441 | 110 mm Shoe |
| 1442 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1443 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 1444 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1445 | 110mm dia pipe. |
| 1446 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 1447 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 1448 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 1449 | 110 mm dia. |
| 1450 | 160 mm dia.(For Storm Water in Court yard) |
| 1451 | Cutting holes up to 30x30 cm in walls including making good the same: With With common burnt clay F.P.S. (non modular) bricks |
| 1452 | Cutting holes up to 15x15 cm in R.C.C. floors androofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof |
| 1453 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 1454 | 110mm x 110mmX110mm |
| 1455 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 1456 | Bend without door (45°) |
| 1457 | 110mm |
| 1458 | Y' Fitting without door |
| 1459 | 110mm |
| 1460 | Single Tee without door |
| 1461 | 110 mm |
| 1462 | Coupler |
| 1463 | 110mm |
| 1464 | 160mm |
| 1465 | Clean Out Plug (COP) |
| 1466 | 110mm |
| 1467 | Vent Cowl |
| 1468 | 110mm |
| 1469 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 1470 | For Wash basin & Urinal |
| 1471 | 50mm dia. Pipe |
| 1472 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 1473 | Elbow (90°) |
| 1474 | Elbow (45°) |
| 1475 | T fitting |
| 1476 | Coupler |
| 1477 | SUB HEAD - III - (WATER SUPPLY) |
| 1478 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 1479 | Concealed work, including cutting chases and making good the walls etc. |
| 1480 | 15 mm dia nominal bore |
| 1481 | 20 mm dia nominal bore |
| 1482 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 1483 | 25 mm dia nominal bore |
| 1484 | 32 mm dia nominal bore |
| 1485 | 40 mm dia nominal bore |
| 1486 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 1487 | Internal work - Exposed on wall / Terrace |
| 1488 | 20 mm dia nominal bore |
| 1489 | 25 mm dia nominal bore |
| 1490 | 32 mm dia nominal bore |
| 1491 | 40mm dia nominal bore |
| 1492 | 50 mm dia nominal bore |
| 1493 | 65 mm dia nominal bore |
| 1494 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 1495 | 20 mm dia nominal bore |
| 1496 | 25 mm dia nominal bore |
| 1497 | 32 mm dia nominal bore |
| 1498 | 40mm dia nominal bore |
| 1499 | 50 mm dia nominal bore |
| 1500 | 65 mm dia nominal bore |
| 1501 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 1502 | 20mm dia nominal bore |
| 1503 | 25mm dia nominal bore |
| 1504 | 32mm dia nominal bore |
| 1505 | 40mm dia nominal bore |
| 1506 | 50mm dia nominal bore |
| 1507 | 65mm dia nominal bore |
| 1508 | Providing and fixing MS pipe puddle flanges of required size with 600mm long with 6mm thick MS plate of size 300mm x 300mm of suitable size properly fixed in RCC walls of water tanks, including necessary welding complete in all respect as per details shown on darwings and directions of Engineeer-in-charge for water tanks. |
| 1509 | 25mm dia. |
| 1510 | 40mm dia. |
| 1511 | 50mm dia. |
| 1512 | 65mm dia. |
| 1513 | 80mm dia. |
| 1514 | 100mm dia. |
| 1515 | 150mm dia. |
| 1516 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 75 in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design:- |
| 1517 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 1518 | MID DAY MILE |
| 1519 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1520 | Providing and fixing Stainless Steel AISI 304(18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40mm including painting of fittings and brackets, cutting and making good the walls wherrerever required. |
| 1521 | Kitchen sink with drain board |
| 1522 | 510x1040 mm bowl depth 250mm |
| 1523 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1524 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1525 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1526 | Semi rigid pipe |
| 1527 | 40 mm dia |
| 1528 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1529 | 30 cm length |
| 1530 | 15 mm nominal bore |
| 1531 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1532 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1533 | 15 mm nominal bore |
| 1534 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1535 | 15 mm nominal bore |
| 1536 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1537 | 15 mm nominal bore |
| 1538 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1539 | 15 mm nominal bore |
| 1540 | TOTAL CARRIED TO SUMMARY |
| 1541 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1542 | RAIN WATER DRAINAGE WORK |
| 1543 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1544 | 110 mm dia |
| 1545 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1546 | 110 mm |
| 1547 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1548 | Coupler |
| 1549 | 110 mm |
| 1550 | Single tee with door |
| 1551 | 110x110x110 mm |
| 1552 | Single tee without door |
| 1553 | 110x110x110 mm |
| 1554 | Bend 87.5 degree |
| 1555 | 110 mm Bend |
| 1556 | Shoe (Plain) |
| 1557 | 110 mm Shoe |
| 1558 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1559 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 1560 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1561 | 110mm dia pipe. |
| 1562 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 1563 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 1564 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 1565 | 110 mm dia. |
| 1566 | Cutting holes up to 30x30 cm in walls including making good the same: With With common burnt clay F.P.S. (non modular) bricks |
| 1567 | Cutting holes up to 15x15 cm in R.C.C. floors androofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof |
| 1568 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 1569 | 110mm x 110mmX110mm |
| 1570 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 1571 | Bend without door (45°) |
| 1572 | 110mm |
| 1573 | Y' Fitting without door |
| 1574 | 110mm |
| 1575 | Single Tee without door |
| 1576 | 110 mm |
| 1577 | Coupler |
| 1578 | 110mm |
| 1579 | Clean Out Plug (COP) |
| 1580 | 110mm |
| 1581 | Vent Cowl |
| 1582 | 110mm |
| 1583 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 1584 | For Wash basin & Urinal |
| 1585 | 50mm dia. Pipe |
| 1586 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 1587 | Elbow (90°) |
| 1588 | Elbow (45°) |
| 1589 | T fitting |
| 1590 | Coupler |
| 1591 | TOTAL CARRIED TO SUMMARY |
| 1592 | SUB HEAD - III - (WATER SUPPLY) |
| 1593 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 1594 | Concealed work, including cutting chases and making good the walls etc. |
| 1595 | 15 mm dia nominal bore |
| 1596 | 20 mm dia nominal bore |
| 1597 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 1598 | 25 mm dia nominal bore |
| 1599 | 32 mm dia nominal bore |
| 1600 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 1601 | Internal work - Exposed on wall / Terrace |
| 1602 | 20 mm dia nominal bore |
| 1603 | 25 mm dia nominal bore |
| 1604 | 32 mm dia nominal bore |
| 1605 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 1606 | 20 mm dia nominal bore |
| 1607 | 25 mm dia nominal bore |
| 1608 | 32 mm dia nominal bore |
| 1609 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 1610 | 20mm dia nominal bore |
| 1611 | 25mm dia nominal bore |
| 1612 | 32mm dia nominal bore |
| 1613 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 1614 | Fire Fighting Tank Capacity |
| 1615 | Domestic Tank Capacity |
| 1616 | BAL VATIKA |
| 1617 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1618 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:- |
| 1619 | White Vitreous china Orissa pattern W.C. pan of size580x440 mm with integral type foot rests |
| 1620 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required |
| 1621 | W.C. pan with ISI marked white solid plastic seat and lid |
| 1622 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm or 340x410x265 mmsizes respectively. (Manual) |
| 1623 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1624 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1625 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1626 | Semi rigid pipe |
| 1627 | 40 mm dia |
| 1628 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1629 | 30 cm length |
| 1630 | 15 mm nominal bore |
| 1631 | 45 cm length |
| 1632 | 15 mm nominal bore |
| 1633 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1634 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1635 | 15 mm nominal bore |
| 1636 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1637 | 15 mm nominal bore |
| 1638 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1639 | 15 mm nominal bore |
| 1640 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1641 | 15 mm nominal bore |
| 1642 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 1643 | Providing & Fixing Stainless Steel dustbin. |
| 1644 | Supply installation, testing and commissioning of WATER DISPENSER |
| 1645 | TOTAL CARRIED TO SUMMARY |
| 1646 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1647 | RAIN WATER DRAINAGE WORK |
| 1648 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1649 | 110 mm dia |
| 1650 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1651 | 110 mm |
| 1652 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1653 | Coupler |
| 1654 | 110 mm |
| 1655 | Single tee with door |
| 1656 | 110x110x110 mm |
| 1657 | Single tee without door |
| 1658 | 110x110x110 mm |
| 1659 | Bend 87.5 degree |
| 1660 | 110 mm Bend |
| 1661 | Shoe (Plain) |
| 1662 | 110 mm Shoe |
| 1663 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1664 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 1665 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1666 | 110mm dia pipe. |
| 1667 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 1668 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 1669 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 1670 | 110 mm dia. |
| 1671 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 1672 | 110mm x 110mmX110mm |
| 1673 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 1674 | Bend without door (45°) |
| 1675 | 110mm |
| 1676 | Y' Fitting without door |
| 1677 | 110mm |
| 1678 | Single Tee without door |
| 1679 | 110 mm |
| 1680 | Coupler |
| 1681 | 110mm |
| 1682 | Clean Out Plug |
| 1683 | 110mm |
| 1684 | Vent Cowl |
| 1685 | 110mm |
| 1686 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 1687 | For Wash basin & Urinal |
| 1688 | 50mm dia. Pipe |
| 1689 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 1690 | Elbow (90°) |
| 1691 | Elbow (45°) |
| 1692 | T fitting |
| 1693 | Coupler |
| 1694 | TOTAL CARRIED TO SUMMARY |
| 1695 | SUB HEAD - III - (WATER SUPPLY) |
| 1696 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 1697 | Concealed work, including cutting chases and making good the walls etc. |
| 1698 | 15 mm dia nominal bore |
| 1699 | 20 mm dia nominal bore |
| 1700 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 1701 | 25 mm dia nominal bore |
| 1702 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 1703 | Internal work - Exposed on wall / Terrace |
| 1704 | 20 mm dia nominal bore |
| 1705 | 25 mm dia nominal bore |
| 1706 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 1707 | 20 mm dia nominal bore |
| 1708 | 25 mm dia nominal bore |
| 1709 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 1710 | 20mm dia nominal bore |
| 1711 | 25mm dia nominal bore |
| 1712 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 1713 | Domestic Tank Capacity |
| 1714 | MULTI PROPOSE HALL |
| 1715 | SUB HEAD - I - (RAIN WATER DRAINAGE WORK) |
| 1716 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1717 | 110 mm |
| 1718 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1719 | Coupler |
| 1720 | 110 mm |
| 1721 | Single tee with door |
| 1722 | 110x110x110 mm |
| 1723 | Single tee without door |
| 1724 | 110x110x110 mm |
| 1725 | Bend 87.5 degree |
| 1726 | 110 mm Bend |
| 1727 | Shoe (Plain) |
| 1728 | 110 mm Shoe |
| 1729 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1730 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1731 | 110mm dia pipe. |
| 1732 | STAFF RESIDENCE |
| 1733 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1734 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required |
| 1735 | W.C. pan with ISI marked white solid plastic seat and lid |
| 1736 | Providing and fixing Stainless Steel AISI 304(18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40mm including painting of fittings and brackets, cutting and making good the walls wherrerever required. |
| 1737 | Kitchen sink with drain board |
| 1738 | 510x1040 mm bowl depth 250mm |
| 1739 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1740 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1741 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1742 | Semi rigid pipe |
| 1743 | 40 mm dia |
| 1744 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1745 | 30 cm length |
| 1746 | 15 mm nominal bore |
| 1747 | 45 cm length |
| 1748 | 15 mm nominal bore |
| 1749 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1750 | Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge. (For bath) |
| 1751 | 15 mm nominal bore |
| 1752 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 1753 | Providing and fixing toilet paper holder. |
| 1754 | Vitreous china |
| 1755 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 1756 | 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 1757 | Providing and fixing C.P. brass shower rose with 15 or 20mm inlet |
| 1758 | 150 mm diameter |
| 1759 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1760 | 15 mm nominal bore |
| 1761 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1762 | 15 mm nominal bore |
| 1763 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1764 | 15 mm nominal bore |
| 1765 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1766 | 15 mm nominal bore |
| 1767 | Providing & fixing storage type electric hot water heater 25 Litre made out of heavy gauge steel jacket finished with rust proof baked-on glossy white enamel paint, inside glass lined heavy gauge copper tank, 25 mm thick polyurethane foam insulation, thermostatically controlled immersion heater with pilot neon lamp, replaceable magnesium anode bar, suitable for 8.0 bar maximum working pressure, cold water inlet and hot water outlet pipe, suitable length of electrical cable and 15 amp 3 pin plug top, complete in all respect including testing etc. (Horizontal/Vertical) |
| 1768 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 1769 | Providing & Fixing Stainless Steel dustbin. |
| 1770 | TOTAL CARRIED TO SUMMARY |
| 1771 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1772 | RAIN WATER DRAINAGE WORK |
| 1773 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1774 | 110 mm dia |
| 1775 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1776 | 110 mm |
| 1777 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1778 | Coupler |
| 1779 | 110 mm |
| 1780 | Single tee with door |
| 1781 | 110x110x110 mm |
| 1782 | Single tee without door |
| 1783 | 110x110x110 mm |
| 1784 | Bend 87.5 degree |
| 1785 | 110 mm Bend |
| 1786 | Shoe (Plain) |
| 1787 | 110 mm Shoe |
| 1788 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1789 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 1790 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1791 | 110mm dia pipe. |
| 1792 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 1793 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 1794 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 1795 | 110 mm dia. |
| 1796 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 1797 | 110mm x 110mmX110mm |
| 1798 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 1799 | Bend without door (45°) |
| 1800 | 110mm |
| 1801 | Y' Fitting without door |
| 1802 | 110mm |
| 1803 | Single Tee without door |
| 1804 | 110 mm |
| 1805 | Coupler |
| 1806 | 110mm |
| 1807 | Clean Out Plug |
| 1808 | 110mm |
| 1809 | Vent Cowl |
| 1810 | 110mm |
| 1811 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 1812 | For Wash basin & Urinal |
| 1813 | 50mm dia. Pipe |
| 1814 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 1815 | Elbow (90°) |
| 1816 | Elbow (45°) |
| 1817 | T fitting |
| 1818 | Coupler |
| 1819 | TOTAL CARRIED TO SUMMARY |
| 1820 | SUB HEAD - III - (WATER SUPPLY) |
| 1821 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 1822 | Concealed work, including cutting chases and making good the walls etc. |
| 1823 | 15 mm dia nominal bore |
| 1824 | 20 mm dia nominal bore |
| 1825 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 1826 | 25 mm dia nominal bore |
| 1827 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 1828 | Internal work - Exposed on wall / Terrace |
| 1829 | 20 mm dia nominal bore |
| 1830 | 25 mm dia nominal bore |
| 1831 | 32 mm dia nominal bore |
| 1832 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 1833 | 20 mm dia nominal bore |
| 1834 | 25 mm dia nominal bore |
| 1835 | 32 mm dia nominal bore |
| 1836 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 1837 | 20mm dia nominal bore |
| 1838 | 25mm dia nominal bore |
| 1839 | 32mm dia nominal bore |
| 1840 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : |
| 1841 | 25mm dia nominal bore |
| 1842 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 1843 | Domestic Tank Capacity |
| 1844 | PRICIPLE RESIDENCE |
| 1845 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1846 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required |
| 1847 | W.C. pan with ISI marked white solid plastic seat and lid |
| 1848 | Providing and fixing Stainless Steel AISI 304(18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40mm including painting of fittings and brackets, cutting and making good the walls wherrerever required. |
| 1849 | Kitchen sink with drain board |
| 1850 | 510x1040 mm bowl depth 250mm |
| 1851 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1852 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1853 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1854 | Semi rigid pipe |
| 1855 | 40 mm dia |
| 1856 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1857 | 30 cm length |
| 1858 | 15 mm nominal bore |
| 1859 | 45 cm length |
| 1860 | 15 mm nominal bore |
| 1861 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1862 | Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge. (For bath) |
| 1863 | 15 mm nominal bore |
| 1864 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 1865 | Providing and fixing toilet paper holder. |
| 1866 | Vitreous china |
| 1867 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 1868 | 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 1869 | Providing and fixing C.P. brass shower rose with 15 or 20mm inlet |
| 1870 | 150 mm diameter |
| 1871 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1872 | 15 mm nominal bore |
| 1873 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1874 | 15 mm nominal bore |
| 1875 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1876 | 15 mm nominal bore |
| 1877 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1878 | 15 mm nominal bore |
| 1879 | Providing & fixing storage type electric hot water heater 25 Litre made out of heavy gauge steel jacket finished with rust proof baked-on glossy white enamel paint, inside glass lined heavy gauge copper tank, 25 mm thick polyurethane foam insulation, thermostatically controlled immersion heater with pilot neon lamp, replaceable magnesium anode bar, suitable for 8.0 bar maximum working pressure, cold water inlet and hot water outlet pipe, suitable length of electrical cable and 15 amp 3 pin plug top, complete in all respect including testing etc. (Horizontal/Vertical) |
| 1880 | Providing & fixing C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects. (Angle valve to be provide under item no. 18 and measure with that item.) |
| 1881 | Providing & Fixing Stainless Steel dustbin. |
| 1882 | TOTAL CARRIED TO SUMMARY |
| 1883 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1884 | RAIN WATER DRAINAGE WORK |
| 1885 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1886 | 110 mm dia |
| 1887 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1888 | 110 mm |
| 1889 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1890 | Coupler |
| 1891 | 110 mm |
| 1892 | Single tee with door |
| 1893 | 110x110x110 mm |
| 1894 | Single tee without door |
| 1895 | 110x110x110 mm |
| 1896 | Bend 87.5 degree |
| 1897 | 110 mm Bend |
| 1898 | Shoe (Plain) |
| 1899 | 110 mm Shoe |
| 1900 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1901 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 1902 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 1903 | 110mm dia pipe. |
| 1904 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 1905 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 1906 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 1907 | 110 mm dia. |
| 1908 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 1909 | 110mm x 110mmX110mm |
| 1910 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 1911 | Bend without door (45°) |
| 1912 | 110mm |
| 1913 | Y' Fitting without door |
| 1914 | 110mm |
| 1915 | Single Tee without door |
| 1916 | 110 mm |
| 1917 | Coupler |
| 1918 | 110mm |
| 1919 | Clean Out Plug |
| 1920 | 110mm |
| 1921 | Vent Cowl |
| 1922 | 110mm |
| 1923 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 1924 | For Wash basin & Urinal |
| 1925 | 50mm dia. Pipe |
| 1926 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 1927 | Elbow (90°) |
| 1928 | Elbow (45°) |
| 1929 | T fitting |
| 1930 | Coupler |
| 1931 | TOTAL CARRIED TO SUMMARY |
| 1932 | SUB HEAD - III - (WATER SUPPLY) |
| 1933 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 1934 | Concealed work, including cutting chases and making good the walls etc. |
| 1935 | 15 mm dia nominal bore |
| 1936 | 20 mm dia nominal bore |
| 1937 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 1938 | 25 mm dia nominal bore |
| 1939 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 1940 | Internal work - Exposed on wall / Terrace |
| 1941 | 20 mm dia nominal bore |
| 1942 | 25 mm dia nominal bore |
| 1943 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 1944 | 20 mm dia nominal bore |
| 1945 | 25 mm dia nominal bore |
| 1946 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 1947 | 20mm dia nominal bore |
| 1948 | 25mm dia nominal bore |
| 1949 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : |
| 1950 | 25mm dia nominal bore |
| 1951 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 1952 | DomesticTank Capacity |
| 1953 | DOROMOTARY |
| 1954 | SUB HEAD - I - (SANITARY FIXTURES & C.P. BRASS FITTING) |
| 1955 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:- |
| 1956 | White Vitreous china Orissa pattern W.C. pan of size580x440 mm with integral type foot rests |
| 1957 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm or 340x410x265 mmsizes respectively. (Manual) |
| 1958 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. |
| 1959 | White Agaria Marble Stone |
| 1960 | Providing and fixing Stainless Steel AISI 304(18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40mm including painting of fittings and brackets, cutting and making good the walls wherrerever required. |
| 1961 | Kitchen sink with drain board |
| 1962 | 510x1040 mm bowl depth 250mm |
| 1963 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- |
| 1964 | White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 1965 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. |
| 1966 | Semi rigid pipe |
| 1967 | 40 mm dia |
| 1968 | Providing and fixing uplasticised PVC connection pipe with brass unions : |
| 1969 | 30 cm length |
| 1970 | 15 mm nominal bore |
| 1971 | 45 cm length |
| 1972 | 15 mm nominal bore |
| 1973 | Providing and fixing CP Brass 32mm/40mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 1974 | Providing and fixing CP Brass Single lever telephonic wall mixer of quality & make as approved by Engineer in charge. (For bath) |
| 1975 | 15 mm nominal bore |
| 1976 | Providing and fixing 600 x 450mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete in all respect. |
| 1977 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. |
| 1978 | 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 1979 | Providing and fixing C.P. brass shower rose with 15 or 20mm inlet |
| 1980 | 150 mm diameter |
| 1981 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : |
| 1982 | 15 mm nominal bore |
| 1983 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 1984 | 15 mm nominal bore |
| 1985 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS: 8931. |
| 1986 | 15 mm nominal bore |
| 1987 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 |
| 1988 | 15 mm nominal bore |
| 1989 | Providing & fixing storage type electric hot water heater 25 Litre made out of heavy gauge steel jacket finished with rust proof baked-on glossy white enamel paint, inside glass lined heavy gauge copper tank, 25 mm thick polyurethane foam insulation, thermostatically controlled immersion heater with pilot neon lamp, replaceable magnesium anode bar, suitable for 8.0 bar maximum working pressure, cold water inlet and hot water outlet pipe, suitable length of electrical cable and 15 amp 3 pin plug top, complete in all respect including testing etc. (Horizontal/Vertical) |
| 1990 | Providing & Fixing Stainless Steel dustbin. |
| 1991 | TOTAL CARRIED TO SUMMARY |
| 1992 | SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) |
| 1993 | RAIN WATER DRAINAGE WORK |
| 1994 | Providing and laying cement concrete 1:5:10(1 cement : 5 coarse sand : 10 graded stone aggregate 20mm nominal size) around P.V.C Soil and waste pipe including bed concrete as per standard design(embedded in the flooring / ground) |
| 1995 | 110 mm dia |
| 1996 | Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10mm gap for thermal expansion. |
| 1997 | 110 mm |
| 1998 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 1999 | Coupler |
| 2000 | 110 mm |
| 2001 | Single tee with door |
| 2002 | 110x110x110 mm |
| 2003 | Single tee without door |
| 2004 | 110x110x110 mm |
| 2005 | Bend 87.5 degree |
| 2006 | 110 mm Bend |
| 2007 | Shoe (Plain) |
| 2008 | 110 mm Shoe |
| 2009 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 2010 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. |
| 2011 | Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : |
| 2012 | 110mm dia pipe. |
| 2013 | UPVC SWR SOIL, WASTE & VENT PIPES AND FITTINGS |
| 2014 | Providing, fixing, jointing and testing, uPVC SWR pipes, - type B conforming to IS : 13592 to wall, ceiling and floor, approved quality, complete, for soil, waste & rain water drain including pushfit jointing with seal ring. (i) Single socketed pipes. |
| 2015 | Internal Toilet (Soil, Waste & Rain Water Pipe) |
| 2016 | 110 mm dia. |
| 2017 | Providing and fixing SWR PVC trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 2018 | 110mm x 110mmX110mm |
| 2019 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. |
| 2020 | Bend without door (45°) |
| 2021 | 110mm |
| 2022 | Y' Fitting without door |
| 2023 | 110mm |
| 2024 | Single Tee without door |
| 2025 | 110 mm |
| 2026 | Coupler |
| 2027 | 110mm |
| 2028 | Clean Out Plug |
| 2029 | 110mm |
| 2030 | Vent Cowl |
| 2031 | 110mm |
| 2032 | Providing, fixing, jointing and testing, unplasticized PVC pipes -10 kg/cm2 confirming to IS : 4985 to wall, ceiling and floor, approved quality, complete,for waste water drain including jointing with rubbering/solvent/solution and airtight joints, etc. |
| 2033 | For Wash basin & Urinal |
| 2034 | 50mm dia. Pipe |
| 2035 | 40mm dia. Pipe (for wash basin & sunken toilet spout) |
| 2036 | Elbow (90°) |
| 2037 | Elbow (45°) |
| 2038 | T fitting |
| 2039 | Coupler |
| 2040 | TOTAL CARRIED TO SUMMARY |
| 2041 | SUB HEAD - III - (WATER SUPPLY) |
| 2042 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. |
| 2043 | Concealed work, including cutting chases and making good the walls etc. |
| 2044 | 15 mm dia nominal bore |
| 2045 | 20 mm dia nominal bore |
| 2046 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 2047 | 25 mm dia nominal bore |
| 2048 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc |
| 2049 | Internal work - Exposed on wall / Terrace |
| 2050 | 20 mm dia nominal bore |
| 2051 | 25 mm dia nominal bore |
| 2052 | 32 mm dia nominal bore |
| 2053 | 40mm dia nominal bore |
| 2054 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : |
| 2055 | 20 mm dia nominal bore |
| 2056 | 25 mm dia nominal bore |
| 2057 | 32 mm dia nominal bore |
| 2058 | 40mm dia nominal bore |
| 2059 | Providing and fixing gun metal gate valve with wheel of approved quality. |
| 2060 | 20mm dia nominal bore |
| 2061 | 25mm dia nominal bore |
| 2062 | 32mm dia nominal bore |
| 2063 | 40mm dia nominal bore |
| 2064 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : |
| 2065 | 25mm dia nominal bore |
| 2066 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 2067 | Domestic Tank Capacity |
| 2068 | ELECTRICAL WORK |
| 2069 | MAIN BUILDING |
| 2070 | SUBHEAD I- WIRING POINTS |
| 2071 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2072 | Group C |
| 2073 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2074 | Group C |
| 2075 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2076 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2077 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2078 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2079 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2080 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2081 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2082 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2083 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2084 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2085 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2086 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2087 | 5/6 amps switch |
| 2088 | 2 Way 5/6 amps switch |
| 2089 | 15/16 amp switch |
| 2090 | 3 pin 5/6 amp socket outlet |
| 2091 | 6 pin 15/16 amp socket outlet |
| 2092 | Telephone socket outlet |
| 2093 | TV antenna socket outlet |
| 2094 | DATA outlet |
| 2095 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2096 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2097 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2098 | 2 Pair |
| 2099 | 20 Pair |
| 2100 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2101 | 2 run of cable |
| 2102 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2103 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2104 | (a): Up to 450mm sweep |
| 2105 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2106 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2107 | 25 mm |
| 2108 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2109 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2110 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2111 | 1200 mm sweep ceiling fan |
| 2112 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2113 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2114 | Supply of recess/Surface mounting round 10-15 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2115 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2116 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2117 | Supply of 36W 2'X2' Square light fixture with specification complete as per architectural design. Make: Philips or Equivalent in approved make |
| 2118 | SUBHEAD III-DISTIBUTION BOARD |
| 2119 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2120 | 4 way Double door (4 + 12) |
| 2121 | 6 way Double door (4 + 18) |
| 2122 | 8 way Double door (4 + 24) |
| 2123 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2124 | 4 way Double door (4 + 12) |
| 2125 | 8 way Double door (4 + 12) |
| 2126 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2127 | For 4 way, Double door TPN MCBDB |
| 2128 | For 6 way, Double door TPN MCBDB |
| 2129 | For 8 way, Double door TPN MCBDB |
| 2130 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2131 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2132 | Single pole |
| 2133 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2134 | 63A 4P |
| 2135 | 40A 4P |
| 2136 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. |
| 2137 | 63A 4P |
| 2138 | 100A 4P |
| 2139 | 160A 4P |
| 2140 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2141 | SUBHEAD IV-EARTHING |
| 2142 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2143 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 2144 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 2145 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2146 | SUBHEAD V-CABLES |
| 2147 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2148 | 3.5C x 120 sqmm aluminium conductor, A2XWY. |
| 2149 | 3.5C x 95 sqmm aluminium conductor, A2XWY. |
| 2150 | 3.5C x 70 sqmm aluminium conductor, A2XWY. |
| 2151 | 3.5C x 50 sqmm aluminium conductor, A2XWY. |
| 2152 | 3.5C x 35 sqmm aluminium conductor, A2XWY. |
| 2153 | 3.5C x 25 sqmm aluminium conductor, A2XWY. |
| 2154 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 2155 | 4C x 10 sqmm aluminium conductor, 2XWY. |
| 2156 | 2C x 16 sqmm aluminium conductor, 2XWY. |
| 2157 | Supplying following 1.1kV grade, XLPE insulated, FRLS type control cables,suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2158 | 2C X 2.5 sqmm copper conductor |
| 2159 | 4C X 2.5 sqmm copper conductor |
| 2160 | 6C X 2.5 sqmm copper conductor |
| 2161 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 2162 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2163 | Above 35 sq. mm and upto 95 sq. mm (clamped with 1mm thick saddle) |
| 2164 | Above 95 sq. mm and upto 185 sq. mm (clamped with 1mm thick saddle) |
| 2165 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 2166 | 3½ X 120 sq. mm (50 mm) |
| 2167 | 3½ X 95 sq. mm (45 mm) |
| 2168 | 3½ X 70 sq. mm (38mm) |
| 2169 | 3½ X 50 sq. mm (32mm) |
| 2170 | 3½ X 35 sq. mm (32mm) |
| 2171 | 3½ X 25 sq. mm (28mm) |
| 2172 | 4 X 16 sq. mm (28mm) |
| 2173 | 4 X 10 sq. mm (25mm) |
| 2174 | 2 X 16 sq. mm (22mm) |
| 2175 | 2C X 2.5 sqmm copper conductor (19mm) |
| 2176 | 4C X 2.5 sqmm copper conductor (19mm) |
| 2177 | 6C X 2.5 sqmm copper conductor (19mm) |
| 2178 | SUBHEAD VI -MISCELLANEOUS |
| 2179 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2180 | Supply, Installation, Testing and Commissioning of 300mm size PVC Wall fan suitable for 230V, 50 Hz AC including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2181 | Supply, Installation, Testing and Commissioning of 600mm size PVC Wall fan suitable for 230V, 50 Hz AC including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2182 | S/f of 50 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2183 | LT PANEL |
| 2184 | Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications etc.complete in all respect so as to fulfill all as required. |
| 2185 | LT Panel |
| 2186 | The minimum clearances between bus bars shall be as follows : |
| 2187 | Phase to phase - minimum 20mm |
| 2188 | Phase to neutral-minimum 15mm |
| 2189 | Incoming : |
| 2190 | 1Nos 400 Amp. 4P MCCB of (36 KA) Breaking capacity |
| 2191 | Metering : |
| 2192 | 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter |
| 2193 | 1 Set of CT's one of 400/ 5Amp ratio 50/51 |
| 2194 | 1 Nos. Set of Phase Indication Lamp. |
| 2195 | 1 Nos. of class-III Type SPD |
| 2196 | Bus Bar : |
| 2197 | 500 Amp.TPN aluminimum bus bar of suitable length.25KA |
| 2198 | Outgoing : |
| 2199 | Phase indication lamps on each outgoing to be provided. |
| 2200 | 02 No.160 Amp 4P MCCB. (25 KA) |
| 2201 | 03 No.100 Amp 4P MCCB. (25 KA) |
| 2202 | 02 No.63 Amp 4P MCCB. (25 KA) |
| 2203 | Panel described as above |
| 2204 | Light Panel |
| 2205 | The minimum clearances between bus bars shall be as follows : |
| 2206 | Phase to phase - minimum 20mm |
| 2207 | Phase to neutral-minimum 15mm |
| 2208 | Incoming : |
| 2209 | 1Nos 160 Amp. 4P MCCB of (25 KA) Breaking capacity |
| 2210 | Metering : |
| 2211 | 1 Set of CT's one of 400/ 5Amp ratio for Multifunction Meter |
| 2212 | 1 Set of CT's one of 400/ 5Amp ratio 50/51 |
| 2213 | 1 Nos. Set of Phase Indication Lamp. |
| 2214 | 1 Nos. of class-III Type SPD |
| 2215 | Bus Bar : |
| 2216 | One (1) No.250 Amp.TPN aluminimum bus bar of suitable length.25KA |
| 2217 | Outgoing : |
| 2218 | Phase indication lamps on each outgoing to be provided. |
| 2219 | 08 No.63 Amp 4P MCCB. (25 KA) |
| 2220 | Panel described as above |
| 2221 | Fire Panel |
| 2222 | Pluming Panel |
| 2223 | SUBHEAD VIII-CABLE TRAY & RACEWAY |
| 2224 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 2225 | 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 2226 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 2227 | MID DAY MILE |
| 2228 | SUBHEAD I- WIRING POINTS |
| 2229 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2230 | Group C |
| 2231 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2232 | Group C |
| 2233 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2234 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2235 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2236 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2237 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2238 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2239 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2240 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2241 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2242 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2243 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2244 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2245 | 5/6 amps switch |
| 2246 | 2 Way 5/6 amps switch |
| 2247 | 15/16 amp switch |
| 2248 | 3 pin 5/6 amp socket outlet |
| 2249 | 6 pin 15/16 amp socket outlet |
| 2250 | Telephone socket outlet |
| 2251 | TV antenna socket outlet |
| 2252 | DATA outlet |
| 2253 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2254 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2255 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2256 | 2 Pair |
| 2257 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2258 | 2 run of cable |
| 2259 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2260 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2261 | (a): Up to 450mm sweep |
| 2262 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2263 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2264 | 25 mm |
| 2265 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2266 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2267 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2268 | 1200 mm sweep ceiling fan |
| 2269 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2270 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2271 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2272 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2273 | SUBHEAD III-DISTIBUTION BOARD |
| 2274 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2275 | 8 way Double door (4 + 24) |
| 2276 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2277 | 4 way Double door (4 + 12) |
| 2278 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2279 | For 8 way, Double door TPN MCBDB |
| 2280 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2281 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2282 | Single pole |
| 2283 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2284 | 63A 4P |
| 2285 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. |
| 2286 | 100A 4P |
| 2287 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2288 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2289 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2290 | SUBHEAD V-CABLES |
| 2291 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2292 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 2293 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 2294 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2295 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 2296 | 4 X 16 sq. mm (28mm) |
| 2297 | SUBHEAD VI -MISCELLANEOUS |
| 2298 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2299 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2300 | BAL VATIKA |
| 2301 | SUBHEAD I- WIRING POINTS |
| 2302 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2303 | Group C |
| 2304 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2305 | Group C |
| 2306 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2307 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2308 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2309 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2310 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2311 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2312 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2313 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2314 | 5/6 amps switch |
| 2315 | 2 Way 5/6 amps switch |
| 2316 | 15/16 amp switch |
| 2317 | 3 pin 5/6 amp socket outlet |
| 2318 | 6 pin 15/16 amp socket outlet |
| 2319 | Telephone socket outlet |
| 2320 | TV antenna socket outlet |
| 2321 | DATA outlet |
| 2322 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2323 | 2 run of cable |
| 2324 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2325 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2326 | (a): Up to 450mm sweep |
| 2327 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2328 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2329 | 25 mm |
| 2330 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2331 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2332 | 1200 mm sweep ceiling fan |
| 2333 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2334 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2335 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2336 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2337 | SUBHEAD III-DISTIBUTION BOARD |
| 2338 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2339 | 6 way Double door (4 + 18) |
| 2340 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2341 | For 6 way, Double door TPN MCBDB |
| 2342 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2343 | Single pole |
| 2344 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2345 | 63A 4P |
| 2346 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2347 | SUBHEAD IV-EARTHING |
| 2348 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2349 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2350 | SUBHEAD V -MISCELLANEOUS |
| 2351 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2352 | SUBHEAD VI -FIRE EXTINGUISHERS |
| 2353 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2354 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2355 | MULTI PROPOSE |
| 2356 | SUBHEAD I- WIRING POINTS |
| 2357 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2358 | Group C |
| 2359 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2360 | Group C |
| 2361 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2362 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2363 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2364 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2365 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2366 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2367 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2368 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2369 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2370 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2371 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2372 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2373 | 5/6 amps switch |
| 2374 | 2 Way 5/6 amps switch |
| 2375 | 15/16 amp switch |
| 2376 | 3 pin 5/6 amp socket outlet |
| 2377 | 6 pin 15/16 amp socket outlet |
| 2378 | Telephone socket outlet |
| 2379 | TV antenna socket outlet |
| 2380 | DATA outlet |
| 2381 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2382 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2383 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2384 | 2 Pair |
| 2385 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2386 | 2 run of cable |
| 2387 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2388 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2389 | (a): Up to 450mm sweep |
| 2390 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2391 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2392 | 25 mm |
| 2393 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2394 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2395 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2396 | 1200 mm sweep ceiling fan |
| 2397 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2398 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2399 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2400 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2401 | SUBHEAD III-DISTIBUTION BOARD |
| 2402 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2403 | 8 way Double door (4 + 24) |
| 2404 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2405 | 4 way Double door (4 + 12) |
| 2406 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2407 | For 8 way, Double door TPN MCBDB |
| 2408 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2409 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2410 | Single pole |
| 2411 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2412 | 63A 4P |
| 2413 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. |
| 2414 | 100A 4P |
| 2415 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2416 | SUBHEAD IV-EARTHING |
| 2417 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2418 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2419 | SUBHEAD V-CABLES |
| 2420 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2421 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 2422 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 2423 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2424 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 2425 | 4 X 16 sq. mm (28mm) |
| 2426 | SUBHEAD VI -MISCELLANEOUS |
| 2427 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2428 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2429 | SUBHEAD VII -FIRE EXTINGUISHERS |
| 2430 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2431 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2432 | STAFF RESIDENCE |
| 2433 | SUBHEAD I- WIRING POINTS |
| 2434 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2435 | Group C |
| 2436 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2437 | Group C |
| 2438 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2439 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2440 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2441 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2442 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2443 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2444 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2445 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2446 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2447 | 5/6 amps switch |
| 2448 | 2 Way 5/6 amps switch |
| 2449 | 15/16 amp switch |
| 2450 | 3 pin 5/6 amp socket outlet |
| 2451 | 6 pin 15/16 amp socket outlet |
| 2452 | Telephone socket outlet |
| 2453 | TV antenna socket outlet |
| 2454 | DATA outlet |
| 2455 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2456 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2457 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2458 | 2 Pair |
| 2459 | 10 Pair |
| 2460 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2461 | 2 run of cable |
| 2462 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2463 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2464 | (a): Up to 450mm sweep |
| 2465 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2466 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2467 | 25 mm |
| 2468 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2469 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2470 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2471 | 1200 mm sweep ceiling fan |
| 2472 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2473 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2474 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2475 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2476 | Supply of LED Bracket led light complete suitable for both wall & surface complete in all respects. |
| 2477 | SUBHEAD III-DISTIBUTION BOARD |
| 2478 | Supplying and fixing following way, horizontal type Single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2479 | 8 way Double door |
| 2480 | 12 way Double door |
| 2481 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2482 | 8 way Double door |
| 2483 | 14 way Double door |
| 2484 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2485 | Single pole |
| 2486 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2487 | 63A 2P |
| 2488 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2489 | SUBHEAD IV-EARTHING |
| 2490 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2491 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2492 | SUBHEAD V -MISCELLANEOUS |
| 2493 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2494 | S/f of 20 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2495 | SUBHEAD VI-MAIN L. T. PANELS |
| 2496 | LT PANEL |
| 2497 | Design, Supply, installation, testing and commissioning of indoor/outdoor floor mounted/ wall mounted, IP43/IP65, IEC 61439/IS 8623, factory built, modular, sectionalised, compartmentalized, extendable type HT/LT cubicle panel of suitable size suitable for operation on 33/11/0.433/0.415 kV, 50 Hz AC 3 phase supply system fabricated from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process or better before painting for surface treatment and powder coated in approved shade, with suitable electrolytic grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX 50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing following switch gears as per SLD ,technical specifications etc.complete in all respect so as to fulfill all as required. |
| 2498 | LT Panel |
| 2499 | The minimum clearances between bus bars shall be as follows : |
| 2500 | Phase to phase - minimum 20mm |
| 2501 | Phase to neutral-minimum 15mm |
| 2502 | Incoming : |
| 2503 | 1Nos 100 Amp. 4P MCCB of 25kA Breaking capacity |
| 2504 | Metering : |
| 2505 | 1 Set of CT's one of 100/ 5Amp ratio for Multifunction Meter |
| 2506 | 1 Nos. Set of Phase Indication Lamp. |
| 2507 | 1 Nos. of class-III Type SPD |
| 2508 | Bus Bar : |
| 2509 | 200 Amp.TPN aluminimum bus bar of suitable length.50KA |
| 2510 | Outgoing : |
| 2511 | Phase indication lamps on each outgoing to be provided. |
| 2512 | 08 No.63 Amp 2P MCB. (10 KA) |
| 2513 | 1PHASE Energy Meter Boxes |
| 2514 | Panel described as above |
| 2515 | SUBHEAD VII -FIRE EXTINGUISHERS |
| 2516 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2517 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2518 | PRINICPLE ROOM |
| 2519 | SUBHEAD I- WIRING POINTS |
| 2520 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2521 | Group C |
| 2522 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2523 | Group C |
| 2524 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2525 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2526 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2527 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2528 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2529 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2530 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2531 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2532 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2533 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2534 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2535 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2536 | 5/6 amps switch |
| 2537 | 2 Way 5/6 amps switch |
| 2538 | 15/16 amp switch |
| 2539 | 3 pin 5/6 amp socket outlet |
| 2540 | 6 pin 15/16 amp socket outlet |
| 2541 | Telephone socket outlet |
| 2542 | TV antenna socket outlet |
| 2543 | DATA outlet |
| 2544 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2545 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2546 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2547 | 2 Pair |
| 2548 | 10 Pair |
| 2549 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2550 | 2 run of cable |
| 2551 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2552 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2553 | (a): Up to 450mm sweep |
| 2554 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2555 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2556 | 25 mm |
| 2557 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2558 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2559 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2560 | 1200 mm sweep ceiling fan |
| 2561 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2562 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2563 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2564 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2565 | Supply of LED Bracket led light complete suitable for both wall & surface complete in all respects. |
| 2566 | SUBHEAD III-DISTIBUTION BOARD |
| 2567 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2568 | 6 way Double door (4 + 18) |
| 2569 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2570 | 4 way Double door (4 + 12) |
| 2571 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2572 | For 6 way, Double door TPN MCBDB |
| 2573 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2574 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2575 | Single pole |
| 2576 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2577 | 40A 4P |
| 2578 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. |
| 2579 | 100A 4P |
| 2580 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2581 | SUBHEAD IV-EARTHING |
| 2582 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2583 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2584 | SUBHEAD V-CABLES |
| 2585 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2586 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 2587 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 2588 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2589 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 2590 | 4 X 16 sq. mm (28mm) |
| 2591 | SUBHEAD VI -MISCELLANEOUS |
| 2592 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2593 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2594 | DOROMOTARY |
| 2595 | SUBHEAD I- WIRING POINTS |
| 2596 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2597 | Group C |
| 2598 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2599 | Group C |
| 2600 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2601 | Wiring for light/ Power plug with 2X4 sq. mm FRLS PVC insuleted copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 Nos. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 2602 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 2603 | 2 x 2.5 sq.mm. + 1 x 2.5 sq.mm. earth wire |
| 2604 | 2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2605 | 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire |
| 2606 | 4 x 6 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2607 | 4 x 10 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2608 | 4 x 16 sq.mm. + 2 x 6 sq.mm. earth wire |
| 2609 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2610 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 2611 | Supplying and fixing following modular switch / socket on existing modular plate and switch box including connections but excluding modular plate etc as required. |
| 2612 | 5/6 amps switch |
| 2613 | 2 Way 5/6 amps switch |
| 2614 | 15/16 amp switch |
| 2615 | 3 pin 5/6 amp socket outlet |
| 2616 | 6 pin 15/16 amp socket outlet |
| 2617 | Telephone socket outlet |
| 2618 | TV antenna socket outlet |
| 2619 | DATA outlet |
| 2620 | Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required. |
| 2621 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 2622 | Supplying and drawing telephone wire following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. |
| 2623 | 2 Pair |
| 2624 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 2625 | 2 run of cable |
| 2626 | Installation, testing and commissioning of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 2627 | Installation of exhaust fan in the existing opening , including making good the damage, connection, testing commissioning etc. as required. |
| 2628 | (a): Up to 450mm sweep |
| 2629 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 2630 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 2631 | 25 mm |
| 2632 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 2633 | SUBHEAD II-INSTALLATION OF LIGHT FIXTURES AND FANS |
| 2634 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2635 | 1200 mm sweep ceiling fan |
| 2636 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 2637 | Supply of recess/Surface mounting round 6-8 watt, cut out Min 125mm, Height Min 40mm, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr continuous Operation,complete in all respec. Make: Philips or Equivalent in approved make |
| 2638 | Supply of LED Tube Light 20 watt Polycarbonate tube light complete including tube etc suitable for both surface & surface complete in all respects. Make: Philips or Equivalent in approved make |
| 2639 | Supply of 7W Bulkhead light fixture with specification complete as per architectural design Make: Philips or Equivalent in approved make |
| 2640 | SUBHEAD III-DISTIBUTION BOARD |
| 2641 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 2642 | 8 way Double door (4 + 24) |
| 2643 | Supplying and fixing of following ways surface/ recess mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2644 | 4 way Double door (4 + 12) |
| 2645 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2646 | For 8 way, Double door TPN MCBDB |
| 2647 | Supplying and fixing Cable End Box (Loose wire box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. |
| 2648 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2649 | Single pole |
| 2650 | Supplying and fixing 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 2651 | 63A 4P |
| 2652 | Supplying and fixing 415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCCB 25KA complete with connections, testing and commissioning etc. as required. |
| 2653 | 100A 4P |
| 2654 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 2655 | SUBHEAD IV-EARTHING |
| 2656 | Suplly and burring of safe Earthing Electrode T-39 Cu Copper Coated, Length 2000mm, outer pipe 76.3mm X 3.2 inner pipe 42.4mm X 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50kgs activated soil (BFC) capable of reucing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame withhinged cover & mansonry housing.(From electrode terminal to switch board, cost of 25x3 copper strip will be extra) Make: As approved in U.P.P.W.D & C.P.R.I. all respects. |
| 2657 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 2658 | SUBHEAD V-CABLES |
| 2659 | Supplying following 1.1kV grade, heavy duty XLPE insulated, FRLS type armoured /Unarmured cables suitable for 415V, 50Hz, AC system, with inner and outer PVC sheath, outer sheath provided with FRLS insulation, galvanised steel armouring (round or flat as mentioned) and with all components as mentioned in BOQ, specifications and schedule, complete as required. |
| 2660 | 4C x 16 sqmm aluminium conductor, 2XWY. |
| 2661 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 2662 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 2663 | Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 2664 | 4 X 16 sq. mm (28mm) |
| 2665 | SUBHEAD VI -MISCELLANEOUS |
| 2666 | Supply, Installation, Testing and Commissioning of 250mm size PVC exhaust fan suitable for 230V, 50 Hz AC including modifying and finishing for hole/opening for the size of fan, MS louver/ shutter complete with frame for Ex.fan including its connection with 3x1.5 sq mm FRLS copper conductor wire with PVC sleeve, loop earthing, making the good damage complete as required to do the job in all respect in accordance with laid specification or upto the satisfaction of engineer in charge. |
| 2667 | S/f of 10 pair Telephone Tag Block for Floors and building with Krone connectors , with connection and punching of same |
| 2668 | SUBHEAD VII -FIRE EXTINGUISHERS |
| 2669 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2670 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 2671 | ADD GST 18% Extra Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |