| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 2 | Group C. |
| 3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.FRLS PVC insulated copper conductor single core cable etc as required. |
| 4 | Group C. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required |
| 6 | 2X1.5Sq.mm+1X1.5Sq.mm Earth wire |
| 7 | 2X2.5Sq.mm+1X2.5Sq.mm Earth wire |
| 8 | 2X4Sq.mm+1X4Sq.mm Earth wire |
| 9 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 11 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 12 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 13 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 14 | 3X1.5 Sq.mm |
| 15 | 3X2.5Sq.mm |
| 16 | 3X4Sq.mm |
| 17 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 18 | Supplying and fixing suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 19 | Supplying and fixing Computer board comprising 3 nos 5 amp modular switches & Sockets and G.I Box 12 module for 5 amp switchs and 5 amp sockets comprising frame and cover plate for each 2 module and 12 module metal box including connections etc as required. |
| 20 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 21 | 5/6 amp Modular switch |
| 22 | 3 pin 5/6 amp socket outlet |
| 23 | Supplying and fixing of following sizes of heavy class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 24 | PVC Conduit 25mm dia |
| 25 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 25 amps modular socket outlet and 25 amps modular SP MCB \\"C\\" curve including connection,painting etc. as required. |
| 26 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 27 | Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- |
| 28 | Single pole. Cat-A. |
| 29 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 30 | 40 Amps. Cat-A. |
| 31 | 63 Amps. Cat-A. |
| 32 | Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 33 | 40 Amps. Cat-A. |
| 34 | 63 Amps. Cat-A. |
| 35 | Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required.(But without MCB/RCCB/Isolator). |
| 36 | Double door-8way |
| 37 | Double door-12way |
| 38 | Double door-16 way |
| 39 | Supplying and fixing of following way triple pole and neutral, sheet steel MCB distribution board, 415 volts, on surface / recess, with provision to mount 4 pole MCCB incomer, 2 module sub-incomer and SP MCBs as outgoing, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required. |
| 40 | Double door-12+2 way,MCCB+6+36 modules |
| 41 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubical panel board including drilling holes in the cubical panel,making connections, etc. as required. |
| 42 | MCCB 100 Amps, 18KA |
| 43 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 44 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 45 | Providing and fixing Copper tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(Vertical run) |
| 46 | Providing and fixing Copper tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 47 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, Copper tube, having single prong at top, with 85 mm dia 6 mm thick Copper base plate including holes etc complete as required. |
| 48 | Supplying and fixing Ding dong bell suitable for single phase, 230 volts, complete as required. |
| 49 | Providing and Fixing of IP20 LED fixture of 18 watt +/- 1 W LED Surface/Recess Mounted Downlighter Round/Square Shape with minimum system lumen efficacy of 100 lm/W with Polycarbonate housing,pressure die cast heat sink and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 50 | Surface/Recss mounted Square/Round downlighter 18 Watts |
| 51 | Providing and fixing LED Surface/Recess type 1X1 luminaire to enhance the delight of occupants with comfortable experience through its classic design and glare free soft illumination ,suitable for surface application with the use of the latest technology 24Watts (2400 Lumen) 5700K and it should be compatible with specification i.e. Power Factor > 0.9, Harmonic Distortion <10% and efficacy > 100 Lumens per watt, CRI rating> 80 suitable for input voltage: AC 220-240 V, 50 Hz, complete with all accessories, connections, testing and commissioning etc. as required. Makes-Bajaj/Panasonic/Wipro. (With 5 Years Warranty). |
| 52 | LED Surface/Recess 1X1 Luminaire-24Watts |
| 53 | Providing and Fixing of LED fixture 600mmX600mm 36 Watt +/- 1W Surface/Recess mounted fixture with HET Plastic diffuser with minimum system lumen efficacy of 100 lm/W with CRCA housing having P.F.>0.95 with THD<10% ,CRI 80.The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 5700 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 54 | LED panel 2'X2'-36 Watts |
| 55 | Providing and Fixing of IP20 LED Surface mounted CRCA Powder Coated Box Type Channel with Pro LED Lamp Suitable for mounting 1 X 18 W LED Tube T8 type having minimum system efficacy of greater than 100 lm/W, P.F.>0.95 with THD<10% ,CCT 6500 K,CRI 80,Surge Protection 2 Kv.The LED with Useful life of 50000 Hrs at L70 . The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. (With 5 Years Warranty). |
| 56 | LED Tube Light 18/20 Watts |
| 57 | Providing and fixing of IP65 LED Mirror light fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. (With 5 Years Warranty) |
| 58 | LED Mirror Light 10W |
| 59 | Supplying and fixing of bulk head fitting LED 10 watt+/-1W with minimum system Lumen efficiencyof greater than 100lm/W with and P.F.0.95 with THD,10%,CCT 5700K,CRI 70,Surge protection 4KV. The LED with useful life of 50000 Hrs. at L70. The input voltage range shall be 150V to 270V complete with all accessories, connections, testing & commissioning etc.as required. (With 5 Years Warranty). |
| 60 | LED 10 Watt Bulk Head |
| 61 | Providing, Installation, testing and commissioning of BLDC ceiling fan (5 star rating), including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required: |
| 62 | Ceiling Fan 1200 mm sweep, Category-A |
| 63 | Ceiling Fan 1400 mm sweep, Category-A |
| 64 | Supplying and fixing extra down rod of 60cm length G.I. pipe 15mm dia heavy gauge including painting etc. as required.(Note:-More than 5cm length shall be rounded to the nearest 10cm and 5cm or less shall be ignored.) |
| 65 | Providing and installation exhaust fan of following sizes in the existing opening,including making the hole to suit the size of the above fan, making good thedamages, connections, testing and commissioning etc. as required: |
| 66 | Exhaust Fan, Light duty, (Domestic) 300 mm sweep |
| 67 | Exhaust Fan, Heavy duty, 300 mm sweep |
| 68 | Providing & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 69 | Armoured cable 25 sq. mm (3.5 core) |
| 70 | Armoured cable 120 sq. mm (3.5 core) |
| 71 | Armoured cable 240 sq. mm (3.5 core) |
| 72 | Armoured cable 500 sq. mm (3.5 core) |
| 73 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required,but excluding sand cushioning and protective covering . |
| 74 | Armoured cable 25 sq. mm (3.5 core) |
| 75 | Armoured cable 500 sq. mm (3.5 core) |
| 76 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T. Panel. The Panel shall be compartmentalized type having space and arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 16G/18G CRCA sheet, base frame 50X50X5MM angle duly painted with Siemens Grey Powder Coated paint as per specification Approx size (H)1450mm,(W)1850mmX(D)450mmX(L)450mm, Assembly Charges of 630A 4 Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.0 Amp.) Copper shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black, assembly Charges of Copper solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB/MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVAPower system & control or approved equivalent make). |
| 77 | MATERIAL: |
| 78 | MAIN INCOMER: MCCB-630A 4P 50 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 630 A 4P-2Nos., Digital metering set:-Amp meter,Voltmeter,Ammeter selector switch,voltmeter selector switch,CT-3 No's,Phase indicating Lamp-3 Nos, Control SP MCB -3Nos. |
| 79 | Outgoing: MCCB 400A 4P 36KA TMR with O/l& S/C Protection-1No.,Spreader link MCCB 400A 4P-2 No's,MCCB 250A 4P 36KA TMR with O/l& S/C Protection-1No.,Spreader link MCCB 250A 4P-2 No's,MCCB 100A 4P 25KA TMR with O/l& S/C Protection-2No.,Spreader link MCCB 100A 4P-4 Nos |
| 80 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 81 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc, |
| 82 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T. Panel. The Panel shall be compartmentalized type having space and arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 16G/18G CRCA sheet, base frame 50X50X5MM angle duly painted with Siemens Grey Powder Coated paint as per specification Approx size (H)1600mm,(W)1850mmX(D)450mmX(L)350mm, Assembly Charges of 400A 4 Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.0 Amp.) Copper shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black, assembly Charges of Copper solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB/MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVAPower system & control or approved equivalent make). (400 Amps Light Load Panel) |
| 83 | MATERIAL: |
| 84 | MAIN INCOMER: MCCB-400A 4P 36 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 400 A 4P-2Nos., Digital metering set:-Amp meter,Voltmeter,Ammeter selector switch,voltmeter selector switch,CT-3 No's,Phase indicating Lamp-3 Nos, Control SP MCB -3Nos. |
| 85 | Outgoing: MCCB 100A 4P 25KA TMR with O/l& S/C Protection-8No.,Spreader link MCCB 100A 4P-16 No's. |
| 86 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 87 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc, |
| 88 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T. Panel. The Panel shall be compartmentalized type having space and arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 16G/18G CRCA sheet, base frame 50X50X5MM angle duly painted with Siemens Grey Powder Coated paint as per specification Approx size (H)1300mm,(W)1650mmX(D)350mmX(L)450mm, Assembly Charges of 250A 4 Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.0 Amp.) Copper shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black, assembly Charges of Copper solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB/MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVAPower system & control or approved equivalent make). (250Amps Heat Load Panel) |
| 89 | MATERIAL: |
| 90 | MAIN INCOMER: MCCB-250A 4P 36 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 250 A 4P-2Nos., Digital metering set:-Amp meter,Voltmeter,Ammeter selector switch,voltmeter selector switch,CT-3 No's,Phase indicating Lamp-3 Nos, Control SP MCB -3Nos. |
| 91 | Outgoing: MCCB 100A 4P 25KA TMR with O/l& S/C Protection-6Nos.,Spreader link MCCB 100A 4P-12 Nos. |
| 92 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 93 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc, |
| 94 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type Sub Main LT Panel 100Amps. The Panel shall be compartmentalized type having space and arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, base frame75X40X3MM angle duly painted with Siemens Grey Powder Coated paint, Assembly Charges of 100A 4 Strip Copper Busbar ( Vertical/Horizontal) & Earth strip throughout the length of Panel (current density of Copper Busbar shall be 1mmx1mm=1.0 Amp.) Copper shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. Approximate Size of Panel H- 700mmX W-500mmX D-200mm. The Assembly Charges of 100 Amps 4P Copper solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB/MCB to field side for Cable termination duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control Wiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139 (Part I & II)(EVA or approved make). |
| 95 | MATERIAL: |
| 96 | MAIN INCOMER: MCCB-100A 4P 25 kA TMR with O/L & S/C Protecrtion-1 No., Spreader Link 100 A 4P-1Nos., Selector Switch-1No., Phase indicating Lamp-3 Nos, Control SP MCB -3Nos,Terminal switch -1No. |
| 97 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wire with thimbles, printed sleeves, tie & belt etc; |
| 98 | The prices of complete job as per the specifications above shall be inclusive of gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc, |
| 99 | Supplying and fixing of Electrical Panel Rubber Insulation mat of suiitable size and thickness upto 12.5mm with chequered holes/solid sheet with insulation voltage resistance of 2Kv/sqm etc. as required complete in all respects. |
| 100 | Description |
| 101 | E.I. Work |
| 102 | PVC insulated FRLS copper Conductor Wires:Polycab/Havells/KEI/RR Kabel/Finolex/plaza. |
| 103 | U.G. Cables:Polycab/Havells/KEI/RR Kabel/ Finolex/ plaza. |
| 104 | Modular Switch & Socket, GI Box & Modular Plate, Step Type Regulator / industrial socket i/c Cat 6 I/O Switch:Legrand/Siemens/Schneider/ABB/North West/Lauritz Knudsen (Formerly L&T)/Honeywell |
| 105 | DB, MCB, RCBO, ISOLATOR, LOOSE WIRE BOX:Legrand/Siemens/Schneider/ABB /Lauritz Knudsen (Formerly L&T) |
| 106 | Ceiling Fan/Heavy duty exhaust fan/Ventilation Fan:Crompton/ USHA/Havells/ Orient/bajaj. |
| 107 | Geyser:Havells/AO-Smith/Racold/Bajaj |
| 108 | LED luminaries::Philips/Havells/Wipro /LT/Regent/Bajaj/Jaquar |
| 109 | Octagonal Pole:Valmont/Transrail/Skipper/Bajaj/Philips/Twinkle/Mayfair(lux max). |
| 110 | M.S. Pipe/G.I. Pipe:Jindal (Hissar) /Tata/SAIL/Prakash Surya (duly ISI Marked) |
| 111 | DWC HDPE Pipe:TeleRex/Gemini/Supreme/Duraline (duly ISI Marked) |
| 112 | Double Brass compression gland / Thimbles:Dowells/Action/Gripwell/Comet/Jainson/Braco |
| 113 | MCCB (It should be Ics = Icu = 100%):Lauritz Knudsen (Formerly L&T) (D Sine) /Siemens (3VA) / ABB (Tmax) / Schneider (Compact NSX) / Legrand (DPX3) |
| 114 | SCHNEIDER (NW) / SIEMENS (3WT) / ABB (E-MAX)/ Lauritz Knudsen (Formerly L&T) (U POWER OMEGA) / LEGRAND ( DMX3) |
| 115 | LT Panels / Outdoor Feeder Pillar (Non TTTA Type):Adlec/ Tricolite/Precision/ Advance Panel & Switch Gear / /ASPL/ Milestone/ Pristine/ DSPL/ KSB Electric cxompany/Harc Power |
| 116 | Digital Instruments:AE/ Lauritz Knudsen (Formerly L&T)/Schneider/Siemens/ Trinity/ Conzerve/ ABB |
| 117 | CT & PT:AE/Kappa/Matrix/EPCOS/ Lauritz Knudsen (Formerly L&T) /ABB/ Schneider/Gilberts & Maxwell |
| 118 | Contactors & Overload Relays:Lauritz Knudsen (Formerly L&T) / Siemens /ABB/Schneider |
| 119 | Indicating Lamps:Lauritz Knudsen (Formerly L&T) / Siemens /C&S/ Schneider/ABB |
| 120 | Timer switch:Lauritz Knudsen (Formerly L&T) /Siemens/ ABB / Schneider / Legrand |
| 121 | Connectors/ Terminal Blocks:Elmex / Connectwell / Essen/ SCHNIEDER/ Lauritz Knudsen (Formerly L&T) |
| 122 | RO Water Purification:KENT/Aquaguard/Livpure/Eureka Forbes Please Enable Macros to View BoQ information |