| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C. |
| 2 | Rewiring for light point/ fan point/exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required.Group C. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire. |
| 5 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire. |
| 6 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire. |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 8 | 3x1.5 Sq. mm. |
| 9 | 3x4.0 Sq. mm. |
| 10 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.:-25 mm. dia |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | Supplying and fixing of 1 module UTP cat 6E information outlets toolless system for data and voice complete with connections, testing and commissioning etc. as required. |
| 15 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required..1 run of cable |
| 16 | S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 17 | Wattage of LED fittings-As per following parameter. |
| 18 | Total lumens of the fittings.-as below |
| 19 | Diffuser - Polycarbonate diffuser/PMMA |
| 20 | Operating voltage =140 V to 270 V, AC supply or better. |
| 21 | Input frequency =50 Hz + 1 Hz |
| 22 | Power factor =Minimum 0.90 |
| 23 | Luminaire efficacy =>85 lm/w |
| 24 | Color rendering index=CRI shall be greater than 80 |
| 25 | Working/ operating temperature =0 o to + 45 oc or better |
| 26 | Color temperature =60000K + 10% |
| 27 | Electronic Driver |
| 28 | Drive current (LED)=As per OEM. |
| 29 | Operating voltage =140 V to 270 V, AC supply or better. |
| 30 | Type of driver =Constant current output driver |
| 31 | THD =Less than 10% |
| 32 | Surge Protection =2.5 KV minimum |
| 33 | Efficiency Driver=>85% |
| 34 | Protection=Shall have under voltage and over voltage protection. |
| 35 | Guarantee of LED fittings including LED driver =Five years against manufacturing defect. |
| 36 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 37 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 38 | Life of LED=50000 burning hours at 70% lumen maintenance |
| 39 | Lumen output of the fitting=>1200 Lumens |
| 40 | Lumen output of the fitting=>1500 Lumens |
| 41 | Lumen output of the fitting=>2000 Lumens |
| 42 | Lumen output of the fitting=>2400 Lumens |
| 43 | S/E of LED Panel with PDC body and prismatic diffuser to be mounted in recess The job includes carriage, erection, making connections testing and commissioning of the fittings.2 * 2 feet |
| 44 | Wattage of LED fittings-As per following parameter. |
| 45 | Total lumens of the fittings.-as below |
| 46 | Diffuser - Prismatic multilayer diffuser UGR<19 |
| 47 | Operating voltage =140 V to 270 V, AC supply or better. |
| 48 | Input frequency =50 Hz + 1 Hz |
| 49 | Power factor =Minimum 0.90 |
| 50 | Luminaire efficacy =>120 lm/w |
| 51 | Color rendering index=CRI shall be greater than 80 |
| 52 | Working/ operating temperature =0 o to + 45 oc or better |
| 53 | Color temperature =60000K + 10% |
| 54 | Electronic Driver |
| 55 | Drive current (LED)=As per OEM. |
| 56 | Operating voltage =140 V to 270 V, AC supply or better. |
| 57 | Type of driver =Constant current output driver |
| 58 | THD =Less than 10% |
| 59 | Surge Protection =2.5 KV minimum |
| 60 | Efficiency Driver=>85% |
| 61 | Protection=Shall have under voltage and over voltage protection. |
| 62 | Guarantee of LED fittings including LED driver =Five years against manufacturing defect. |
| 63 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 64 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 65 | Life of LED=50000 burning hours at 70% lumen maintenance |
| 66 | Lumen output of the fitting=>3600 Lumens |
| 67 | Lumen output of the fitting=>4320 Lumens |
| 68 | S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.Specification of LED fittings: |
| 69 | Wattage of LED fittings-As per following parameter. |
| 70 | Total lumens of the fittings.-as below |
| 71 | Diffuser - Polycarbonate diffuser/PMMA |
| 72 | Operating voltage =140 V to 270 V, AC supply or better. |
| 73 | Input frequency =50 Hz + 1 Hz |
| 74 | Power factor =Minimum 0.90 |
| 75 | Luminaire efficacy =>100 lm/w |
| 76 | Color rendering index=CRI shall be greater than 80 |
| 77 | Working/ operating temperature =00 to + 450c or better |
| 78 | Color temperature =60000K + 10% |
| 79 | Electronic Driver |
| 80 | Drive current (LED)=As per OEM. |
| 81 | Operating voltage =140 V to 270 V, AC supply or better. |
| 82 | Type of driver =Constant current output driver |
| 83 | THD =Less than 10% |
| 84 | Surge Protection =2.5 KV minimum |
| 85 | Efficiency Driver=>85% |
| 86 | Protection=Shall have under voltage and over voltage protection. |
| 87 | Guarantee of LED fittings including LED driver =Five years against manufacturing defect. |
| 88 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 89 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 90 | Life of LED=25000 burning hours at 70% lumen maintenance |
| 91 | Lumen output of the fitting=>1000 Lumens |
| 92 | Lumen output of the fitting=>2000 Lumens |
| 93 | S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 94 | Wattage of LED fittings-As per following parameter. |
| 95 | Total lumens of the fittings.-as below |
| 96 | Diffuser - Polycarbonate diffuser/PMMA |
| 97 | Operating voltage =140 V to 270 V, AC supply or better. |
| 98 | Input frequency =50 Hz + 1 Hz |
| 99 | Power factor =Minimum 0.90 |
| 100 | Luminaire efficacy =>80 lm/w |
| 101 | Color rendering index=CRI shall be greater than 80 |
| 102 | Working/ operating temperature =0o to + 45oc or better |
| 103 | Color temperature =60000K + 10% |
| 104 | Electronic Driver |
| 105 | Drive current (LED)=As per OEM. |
| 106 | Operating voltage =140 V to 270 V, AC supply or better. |
| 107 | Type of driver =Constant current output driver |
| 108 | THD =Less than 10% |
| 109 | Surge Protection =2 KV minimum |
| 110 | Efficiency Driver=>85% |
| 111 | Protection=Shall have under voltage and over voltage protection. |
| 112 | Guarantee of LED fittings including LED driver =Five years against manufacturing defect. |
| 113 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 114 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 115 | Life of LED=50000 burning hours at 70% lumen maintenance |
| 116 | Lumen output of the fitting=>800 Lumens |
| 117 | Supply, Installation, Testing and Commissioning of following sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.85, Air delivery minimum 215 CMM, 300 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote/ BLDC electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required with ive year warranty. |
| 118 | Ceiling Fan 1200 mm sweep |
| 119 | Ceiling Fan 1400 mm sweep |
| 120 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 121 | Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC with ive year warranty. |
| 122 | Exhaust Fan, 250 mm sweep |
| 123 | Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Heavy Duty type. |
| 124 | Exhaust Fan, Heavy duty, 300 mm sweep (900/1400rpm) |
| 125 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 126 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 127 | 8 way , Double door |
| 128 | 12 way , Double door |
| 129 | Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required. |
| 130 | 63 A DP |
| 131 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 132 | Single pole |
| 133 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.70 metre long etc. without charcoal/ coke and salt as required. |
| 134 | Providing and fixing 25mm X 5mm G.I. strip on surface or in recess for connections etc. as required. |
| 135 | Providing and fixing 4.00mm dia copper wire on surface or in recess for loop earthing as required. |
| 136 | Supplying and erection of sub- panel 63 Amp. cubical panel enclosure DMC/SMC Insulator supports control wiring with thimble power wiring with thimble terminal block & short links door locks & hings rubber gasket heat shrinkable sleeves colour coded engraved name plate indoor type wall mounted complete with locking arrangement to house 63 Amp. MCCB with 100Amp Copper busbar Phase indication lamps RYB. The cubical panel shall have cable entry at two sides complete in all respects including the cost of switchgears. |
| 137 | Fabrication, supply, lnsallation testing & commissioning Panel conforming to IEC code 61439 part 1& 2 with IP 42 protection control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect as per CPWD specification with following incoming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required . |
| 138 | Incomer |
| 139 | 300 Amp MCCB 36 KA 4 Pole 1 Nos, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300 Amp. |
| 140 | Outgoing:- ( Note : All outgoing feeders should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 141 | Outgoing Section 1 |
| 142 | I )200 Amp FP MCCB 36 KA 1Nos as main switch with 63 Amp FP MCCB 25 KA 6 Nos along with high conductivity aluminium bus bar of suitable capacity,over voltage protection device, VAF Meter Digital, CTs and indicators complete in all respects. |
| 143 | Outgoing Section 2 |
| 144 | 160 Amp FP MCCB 25 KA 1Nos as main switch, change over switch 160 Amp 1 Nos,63 Amp FP MCCB 25 KA 6 Nos along with high conductivity aluminium bus bar of suitable capacity,over voltage protection device, VAF Meter Digital, CTs and indicators complete in all respects. |
| 145 | Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheatthed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc.of the required size. |
| 146 | Armoured cable 25 sq. mm ( 3.5 core) |
| 147 | Armoured cable 185 sq. mm ( 3.5 core) |
| 148 | Approved Makes. |
| 149 | Steel Conduit :-BEC,AKG,RKG, Precision Pipes |
| 150 | PVC Conduit:-Anchor, AKG,RKG, Precision Pipes, Diplast. |
| 151 | FRLS Wires:-Havells, Finolex, RR Kabel, KEI, Plaza, Polycab. |
| 152 | Switches/ sockets (Premium):- Havells, (Athena), Goldmedal (AIR) (GIFA). Anchor (Penta) Legrand (Arteor), L&T (Entice) |
| 153 | MCB’s and Distribution board:- Havells, ABB, Legrand, L&T, Schneider. (Distribution board and MCB has to be of same company). |
| 154 | MCCB’s and switchgear:- Havells, ABB, Legrand, L&T, Schneider. |
| 155 | Bus bars Copper:- Havells, Anchor |
| 156 | Geyser:- Havells, racold, bajaj,Goldmedal, jaguar ( 5 star rated). |
| 157 | Cat 6:- Havells, Legrand, R&M, Systimax, Panduit, Molex |
| 158 | Ceiling fan, BLDC:- Atomberg (Efficio), Havells (Efficia Neo), Orient (hector 500), Gold Medal (Marut), Bajaj (efficial) (5star rated) |
| 159 | Ventilating fans BLDC Plastic body:- Atomberg, Havells, Orient, Gold Medal, Bajaj. |
| 160 | Exhaust fans:- Atomberg, Havells, Orient, Gold Medal, Bajaj. |
| 161 | LED lights polycarbonate body:- Bajaj, havells, Goldmedal,Panasonic, Philips, Wipro, Changi ( If quantity of LED fittings exceeds 50 in number then testing of fittings is mandatory ), L&T. |
| 162 | LED lights PDC/CRCA body:- Bajaj, Havells, Panasonic, Philips, Wipro, L&T, Changi. (If quantity of LED fittings exceeds 50 in number then testing of fittings is mandatory) |
| 163 | LED Lights UGR<19:- Bajaj, Havells, Philips, Wipro, L &T, Changi. |
| 164 | Armoured Cables/ Unarmoured Cables:- Univesal, KEI, Havells, Grandley, Polycab. Please Enable Macros to View BoQ information |