| 1 | S & F Steel tubular swaged poles complete with cast iron plate, finial taper plug, bolt, nuts & screws as specified type 410 SP-55 (11 mtr long) including one coat of red oxide primer and two coats of aluminium paint and making 30 cm wide strips (total -05 Nos) with yellow and black paint alternately on external surface above column/PCC benching including numbering with black paint and painting with bitumenous paint internally and externally for portion embedded complete all as specified and directed. |
| 2 | S & F Air break gang operated switch with 12 Nos insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement consisting of MS chanel HT post type insulator copper alloy, high pressure assembly drop out fuses operating rod of 20 mm dia GI pipe (medium grade) for operating from 1.2 m above GL complete including drop out fuses conforming to IS-9921 Part-I to V (1982 to 1985) of 1972 rated voltage 11 KV and for current rating 200 Amp all as specified |
| 3 | Material and labour for lightning arresters nominal discharge current Peak 65 KA rating, suitable for operation on HT 11000 volts system, comprising of zinc oxide disks, electrodes, fibre re-in forced composite structure, non tracking weather resistant shedded heat shrinked polymeric housing for withstanding from the effects of pollution, rain, heat and with moisture seal , stainless steel bolts and nuts, stainless steel end fitting cups and fixing arrangements complete all as specified and as directed. |
| 4 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e M.S. channel or angle sections etc. including new nuts, bolts, washers as reqd dia/length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of aluminium paint (1st quality ) as reqd complete as specified. |
| 5 | M & L for Cement Concrete 1:3:6 type C1 (using 20 mm graded aggregate) as Lean Concrete for coping of pole, stay foundation etc including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified |
| 6 | Material and labour for cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as Lean Concrete for road finishing even and fair without using extra cement complete all as specified and as directed. |
| 7 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm. |
| 8 | S&F of cable end jointing kit 95 Sqmm, 3 core XLPE 11kV HT Cable Cold shrinkable outdoor type, incl carrying out 5KV megger test after jointing complete all as specified and directed by Engr-in-Charge. |
| 9 | S&F of cable end jointing kit 95 Sqmm, 3 core XLPE 11kV HT Cable Cold shrinkable indoor type, incl carrying out 5KV megger test after jointing ,complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 400 sq mm including aluminium lugs, cable glands ,complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply, laying & testing industral PVC FRLS insulated single core flexible cable, electric power cables (heavy duty) with stranded copper conductor, 1100 volts grade, of size Single core 185 sq mm, including copper cable lugs, cable glands ,complete all as specified and directed by Engr-in-Charge. |
| 12 | Supply and install, testing and commisioning of outdoor transformer as per IS : 1180 Part-I, level-II step down, copper wound 11 KV/433 Volts (at no load) AC 3 Phase 50HZ 500KVA capacity, core type, oil immersed naturally air cooled, oil natural, air natural (ON/AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accorance with vector ground DYn-11 with neutral brought out on secondry sied (LV) and having taping at +5% to -10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap chargege gear. The max temp rise should not exceded 50 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on and ambient temp of 40 degree celsius. Transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeablity prime grade cargo with M4 grade or better, perfectly insulated and clamped to min noise and vibrations. The transformer shall be IS/IEC 60076 and as per IS-1180 Part -I of 2014 marked and shall comprise of the following:-(a) One cable box on HT side (Primary side consisting of three nos porcelain bushing with copper rods, complete with nuts and washer, with cable glands suitable for reception/taking out 3core 95sqmm, HT 11000 volts grade XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. |
| 13 | Srl Item No 12.00 above contd/- (b) One cable box on LT side (secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable grands suitable for reception/taking out single core 400sqmm, LT 1100 volts, grade, LPE insulated and PVC sheathed, heavy duty, armoured cables including jointing material complete.(c) Conservator with filter type drain valve and oil level gauge.(d) De-hydrating breather with first fill of dehydrating agent (Silica Gel).(e) Explosive vent, Thermometer pocket on tank cover, Oil level gauge, Oil drain filter valve, lifting ligs, oil filling hole with cap/plug iwht connection plate complete, air release valve plug and four nos plain solid cast steel detachable rollers.(f) One no 100mm diea, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal gaurd having max perimeter temp rading indicator with re-setting device.(g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earting of body. (h) Rating plate and terminal making plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. (k) First fill of new and unused transformer oil, IS-335 of 1986 marked, filtered and tested upto 50KV dielectric strenght at 2.5mm air gap between testing electrodes, specific resistance at 27 Degree celsius Ohm-om 500x10 the power 12, water content 50PPM, Dielectric dissipation factor (tan Deta at 90degree celsius) 0.005, Neutralisation value mg of KOH/gm of oil 0.03 Inter facial tension N/M at 27 degree celsius - 0.04, flash point 140 degree celsius and sluge 0.1% by wight. |
| 14 | Srl Item No 12.00 above contd/- (l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer.(m) Transformer losses hall not exceed the losses mentioned in Table 6 of IS : 1180 of 2014 Part-I.(n) Oil temperature indicator. |
| 15 | M & L for PCC platform of transformer shall be fixed on platform size 3.00 X3.00 X1.20 meter (as per TD No 699) with PCC 1:3:6 type C-2 using 40mm graded stone aggregate with suitable steps including two inverted rolled steel channel fixed on the top of platform, 15mm thick plaster in CM 1:6 ON external surfaces, earth work form work etc complete with two coat of white wash on platform of approved shade all as directed. The cost of same deemed to be included in the rate of above item. |
| 16 | M&L for providing earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point, providing charcoal and common salt all as shown in electrical plate No. 3 of SSR Part I of 2009 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC (1:3:6) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg/sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 32x6 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified.Note:- (i) Venders are bound to get earthing result upto 5 Ohm for single earthings and 3 Ohm with the grid of two earthing.Any additional work and material required to achive the required result is included in the cost quoted by the tenderer.(ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.(iii) Refill the pit with M&L for black cotton soil 1 cum. |
| 17 | M&L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mm by means of bolts, nuts, checknuts & washers of copper and connecting to test point , providing charcoal and common salt ,all as shown in electrical plate No. 3 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs, including copper earth strip 20 x 3 mm with GI protection pipe of 25 mm medium grade 7.5 meter long, etc complete all as specified.Note-- (i) Vendors are bound to get earthing result upto1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 ohm with single earthing, Any additional work and material required to achive the required result is included in the cost. (ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.(iii) Refill the pit |
| 18 | S&F for Galvanised Iron Strip of size 32mm x 6 mm thick with necessary clamps, bolts nuts and washers of suitable size, for pole mounted 11 KV Lightening arrester, jumpers, LT Panels transforme Body etc |
| 19 | S&F for copper strip of size 25mm x 3 mm thick with necessary clamps, bolts nuts and washers of suitable size, for connecting to Transformer neutral bushing |
| 20 | Supply & fixing of aluminium heavy duty tube of size 32 mm outer dia, 20 mm inner dia, 6 mm thick necessary clamps, bolts nuts and washers of suitable size mounted on 11 KV rated polymer based insulators, connecting jumpers all as directed at site. |
| 21 | Supply & fixing of aluminium heavy duty strip of size 32 mm X6mm thick necessary clamps, bolts nuts and washers of suitable size mounted on 11 KV rated polymer based insulators, connecting jumpers all as directed at site. |
| 22 | Supply install, test and commissioning LT Feeder Pillar / Panel board cubical type outdoor, IP 54 free floor standing factory fabricated TTA Panel made out of 3.00 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate TPN copper bus bars of rating not less 1.5 times the rated cap ACB. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The ACB shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The cubicle shall have a detachable bottom stand made out of equal angle 50mmx50 mmX6mm . A detachable predrilled gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side, The Panel shal be manucatured from CPRI approved manufacturerof makes stipulated. The panel shall comprise of (a) Four pole ACB 630 Amps, 50 KA, Ics = 100% of Icu , adjustable type with spring charging with lever, push button for manul opening/ closing, signal for spring charging, signal for over current, key lock in open position, racking in/ out , sliding contacts, circute braker postion indicator - 1 Nos(b) RYB Indicator - 1 Set(c) CT for RYB - 1 Set(d) Control wiring with Fuse - 1 Set |
| 23 | Supply install, test and commissioning LT Feeder Pillar / Panel board cubical type indoor, free floor standing factory fabricated TTA Panel made out of 3.0 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoing MCCB, MCB and TPN copper bus bars of rating not less 1.5 times the rated cap of incomer MCCB / ACB. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The incoming as well as outgoing MCCBs shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The cubicle shall have a detachable bottom stand made out of equal angle 50mmx50 mmX6mm . A detachable predrilled gland plateof thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side, The Panel shal be manucatured from CPRI approved manufacturerof makes stipulated. The cost is inclusive of taking down of existing panel, disconnecting existing cables, reconnecting the cables with lugs & glands, Excevation, PCC Foundation all as directed.The panel shall comprise of (a) Four pole MCCB 630 Amps, 50 KA ,thermal magnetic adjustable type, Ics= 100% Icu - 1 Nos(b) CT Operated Trivector Type Energy meter - 1 No(c) RYB Indicator - 1 Set(d) CT for RYB - 1 Set(e) Control wiring with Fuse - 1 Set(f) Digital VAPF KWH Meter - 1 No(g) Type B Class SPD Four Pole - 1 Set |
| 24 | Supply install, test and commissioning 11000 Volts HT Bus Bar panel Panel board cubical type out door, free floor standing factory fabricated made out of 3.00 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming, the Bus Bar panel shall be provided wit copper bus bar 600 Amps rating along with bus bar mounting insulator, The bus bar panel shall have a detachable bottom stand made out of equal angle 50mmx50 mmX6mm . A detachable predrilled gland plateof thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side, the panel shall be suitable for connecting 03 nos HT 11000 Volts 185 Sqmm 3 core cable. The Panel shall be manucatured from CPRI approved manufacturerof makes stipulated. |
| 25 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in soft/loose soil etc complete all as specified and directed by Engr-in-Charge. |
| 26 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in hard/dense soil complete all as specified and directed by Engr-in-Charge. |
| 27 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in soft disintegrated rock complete all as specified and directed by Engr-in-Charge.Note - Excevation shall be done manually by deploying manpower |
| 28 | Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-Charge. |
| 29 | Removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as specified and directed by Engr-in-Charge. |
| 30 | Supply & Lay graded coarse stone aggregate 40 mm grade, in transformer yard ,complete all as specified & as directed by Engr-in-charge. |
| 31 | S&F double wall corrugated (DWC) pipe Class SN 4,size 77 mm outer dia,including coupling and lying in trenches for passing cables etc ,complete all as specified & as directed by Engr-in-charge. |
| 32 | S&F double wall corrugated (DWC) pipe Class SN 4,size 110 mm outer dia,including coupling and lying in trenches for passing cables etc ,complete all as specified & as directed by Engr-in-charge. |
| 33 | M & L for GI steel tubing light grade of size 80 mm dia as cable protection across road/along wall/pole etc ,complete all as specified & as directed by Engr-in-charge. |
| 34 | M & L for cutting existing road to depth up to 60 Cm and width 45 CM for laying of pipe/cables etc and refilling, making good the road by PCC 1:2:4 type B 2 of 15 cm thick, watering, curing, well ramming ,complete all as specified & as directed by Engr-in-charge. |
| 35 | S&F cable route markers made out of PCC block (1:3:6) type C-1 using 20 mm graded stone aggregate size (bottom 400mmx 100 mm thick)+Top-300x100mm thick+height-1200mm(60 cm burried in ground ` DANGER/11 KV UG cable MES' embossed on route marker including excavation and earth work and painting the yellow colour above the ground and write the black colour ,complete all as specified & as directed by Engr-in-charge. |
| 36 | Earth work in excavation by mechanical means (Hydraulic excavator)/in all kind of soil for foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan),including dressing of sides and ramming of bottoms,lift upto 1.5m,including getting out the excavated soil and disposal of surplus excavated soil as directed,within a lead of 50 m ,complete all as specified & as directed by Engr-in-charge. |
| 37 | M&L for PCC 1:4:8 type D2 (Using 40mm graded stone aggregate) as in foundation, filling and mass concrete ,complete all as specified & as directed by Engr-in-charge. |
| 38 | M&L for Squarred rubble stone walling Jodhpur type, regular coursed, well bonded, bedded and solidly hearted, built in cement mortar (1:4) ,complete all as specified & as directed by Engr-in-charge. |
| 39 | Extra over to stone walling for hammer dressing to face stones and dressing of the face beds & joints as specified of squarred rubble walling regular coursed, Jodhpur type, with maximum depression of face from straight edge held against the dressede surface n. exc 20mm ,complete all as specified & as directed by Engr-in-charge. |
| 40 | M&L 15mm thick rendering in cm (1:4) on stone masonary surfaces, finishing the surface even & fair ,complete all as specified & as directed by Engr-in-charge. |
| 41 | M & L three coats of white wash on newly plastered wall surfaces including preparation of surfaces ,complete all as specified & as directed by Engr-in-charge. |
| 42 | M&L 75 mm thick PCC 1:3:6 type C2 using 40mm graded stone aggregate laid in panels surface finish even and smooth without using extra cement as in plinth protection complete all as specified and as directed. |
| 43 | M&L forming 12mm thick expansion joint filled with preformed bituminous filler and top 30mm primed and sealed with sealing compound grade 'B' for 100mm thick slab ,complete all as specified & as directed by Engr-in-charge. |
| 44 | M&L 40mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in flooring ,complete all as specified & as directed by Engr-in-charge. |
| 45 | Excavating in post holes Soft/disintegrated rock (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm ,complete all as specified & as directed by Engr-in-charge. |
| 46 | M & L for PCC 1:3:6 type C1 using 20mm graded stone aggregate as in foundation filling and mass concrete ,complete all as specified & as directed by Engr-in-charge. |
| 47 | Supply and fixing mild steel work as in angle iron, flat iron of any size for post and struts as in fencing including, cutting tops to shape as directed, drilling holes, notching for wire etc, flat iron fillets for securing wire mesh ,chain link fencing etc including all necessary drilling bolting or riveting etc and/or fixing with screws, bolts etc. and similar work conforming to Fe-410-0 or Fe-310-0 ,complete all as specified & as directed by Engr-in-charge. |
| 48 | Fixing only Chain link fencing including line wires, any mesh size and type to any type of standards,rails,straining bolts,etc.including provision of binding wire ,complete all as specified & as directed by Engr-in-charge. |
| 49 | Supply only chain link MS galvanised fencing of weight not less than 3.5 Kgs per sqm and size as directed by Engr-in-charge. |
| 50 | M&L pre-cast cement concrete(20mm graded crushed stone aggregate) 1:3:6 type C-1 as in block masonery exc 10cm in width with solid block masonery with solid blocks,exc.10cm in width and setting in cement mortar 1:4 ,complete all as specified & as directed by Engr-in-charge. |
| 51 | M&L for 10mm thick rendering on fair faces of brick works finished even andfair without using extra cement in cement mortar 1: 4 ,complete all as specified & as directed by Engr-in-charge. |
| 52 | M&L Hand rails, grills ,Gates ,half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof ,Brackets for Valley gutters ,including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 410-0 or FE 310-0 ,complete all as specified & as directed by Engr-in-charge. |
| 53 | M & L for preparation of new steel surfaces over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide, zinc chrome primer ,complete all as specified & as directed by Engr-in-charge. Please Enable Macros to View BoQ information |