| 1 | A-Electrical Installation works:- Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group A |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 6 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 7 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 9 | 1 x 1.5 sq. mm |
| 10 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 11 | 25 mm |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in residential buildings). |
| 15 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 16 | TV antenna socket outlet |
| 17 | Supplying and fixing following Modular base & cover plate , modular metal boxes etc. as required. |
| 18 | 1 or 2 Module |
| 19 | S/E of LED Downlighter round type surface with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 20 | Wattage of LED fittings- As per following parameters |
| 21 | Total Lumens of the fittings-as below |
| 22 | Diffuser- Polycarbonate diffuser/PMMA |
| 23 | Operating voltage-140 V to 270 V, AC supply or better. |
| 24 | Input frequency-50 Hz + 1 Hz |
| 25 | Power factor-Minimum 0.90 |
| 26 | Luminaire efficency->100 lm/w |
| 27 | Color rendering index-CRI shall be 80 |
| 28 | Working/ operating temperature-0 to + 45c or better |
| 29 | Color temperature-6000K to 10% |
| 30 | Electronic Driver-As per OEM. |
| 31 | Drive current (LED)-As per OEM. |
| 32 | Operating voltage-140 V to 270 V AC supply or better |
| 33 | Type of driver-Constant current output driver |
| 34 | THD-Less than 10% |
| 35 | Surge Protection-2.5 KV minimum |
| 36 | Efficiency Driver->85% |
| 37 | Protection-Shall have under voltage and over voltage protection. |
| 38 | Guarantee of LED fittings including LED driver-5 years against manufacturing defect. |
| 39 | Fixture-Should comply with LM 79 test from NABL/UL lab. |
| 40 | Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 41 | Life of LED-50000 burning hours at 70% lumen maintenance |
| 42 | LED Panel 600 Lumens. |
| 43 | LED Panel 1200 Lumens. |
| 44 | LED Panel 1500 Lumens. |
| 45 | LED Panel 1800 Lumens. |
| 46 | Providing and installation of following type of LED Batten with PDC/CRCA housing(aluminium extrusion) ,anti glare polycarbonate diffuser,surge protection 4 KV luminaire efficacy > 110lm/Watt with minimum 25000 burning hours,THD<15% in white finish industrial grade IP 40 rated and seprated energy efficient constant current, non-integral, electronic driver;relevent LM 79/80 complaince fromUN/NABL Lab suitable for input voltage: AC 140-270 V, 50/60Hz, complete with all accessories, connections, testing etc. as required of approved Make |
| 47 | Wattage of LED fittings- As per following parameters |
| 48 | Total lumens of the LED fittings- as per individual fittings mention below |
| 49 | Diffuser-polycarbonate diffuser/PMMA |
| 50 | Operating voltage-140V to 270V, AC supply |
| 51 | Input frequency-50 Hz + 1 Hz |
| 52 | Power factor-Minimum 0.90 |
| 53 | Luminaire efficacy->100 lm/w |
| 54 | Color rendering index-CRI shall be greater than 80 |
| 55 | Working/ operating temperature-0 to + 45c or better |
| 56 | Color temperature-6000K to 10% |
| 57 | Electronic Driver |
| 58 | Drive current (LED)-As per OEM. |
| 59 | Operating voltage-140 V to 270 V AC supply or better |
| 60 | Type of driver-Constant current output driver |
| 61 | THD-Less than 10% |
| 62 | Surge Protection-2.5 KV minimum |
| 63 | Efficiency Driver->85% |
| 64 | Protection-Shall have under voltage and over voltage protection. |
| 65 | Guarantee of LED fittings including LED driver-5 years against manufacturing defect. |
| 66 | Fixture-Should comply with LM 79 test from NABL/UL lab. |
| 67 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 68 | Life of LED-25000 burning hours at 70% lumen maintenance |
| 69 | LED Batten Light >2200 Lumens. |
| 70 | Providing and installation of following type of LED Batten with polycarbonate housing ,anti glare polycarbonate diffuser, complete with all accessories, connections, testing etc. as required of Approved Make Philips, havells ,Wipro , Bajaj, Panasonic, Goldmedal & Chengi as per following specification. |
| 71 | Wattage of LED fittings- As per following parameters |
| 72 | Total lumens of the LED fittings- as per individual fittings mention below |
| 73 | Diffuser-polycarbonate diffuser/PMMA |
| 74 | Operating voltage-140V to 270V, AC supply |
| 75 | Input frequency-50 Hz + 1 Hz |
| 76 | Power factor-Minimum 0.90 |
| 77 | Luminaire efficacy->100 lm/w |
| 78 | Color rendering index-CRI shall be greater than 80 |
| 79 | Working/ operating temperature-0 to + 45c or better |
| 80 | Color temperature-6000K to 10% |
| 81 | Electronic Driver |
| 82 | Drive current (LED)-As per OEM. |
| 83 | Operating voltage-140 V to 270 V AC supply or better |
| 84 | Type of driver-Constant current output driver |
| 85 | THD-Less than 10% |
| 86 | Surge Protection-2.5 KV minimum |
| 87 | Efficiency Driver->85% |
| 88 | Protection-Shall have under voltage and over voltage protection. |
| 89 | Guarantee of LED fittings including LED driver-5 years against manufacturing defect. |
| 90 | Fixture-Should comply with LM 79 test from NABL/UL lab. |
| 91 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 92 | Life of LED-25000 burning hours at 70% lumen maintenance |
| 93 | LED Batten Light >1000 Lumens. |
| 94 | S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 95 | Wattage of LED fittings- As per following parameters |
| 96 | Total lumens of the LED fittings- Minimum 800 lumen |
| 97 | Diffuser-polycarbonate diffuser/PMMA |
| 98 | Operating voltage-140V to 270V, AC supply |
| 99 | Input frequency-50 Hz + 1 Hz |
| 100 | Power factor-Minimum 0.90 |
| 101 | Luminaire efficacy->80 lm/w |
| 102 | Color rendering index-CRI shall be greater than 80 |
| 103 | Working/ operating temperature-0 to + 45c or better |
| 104 | Color temperature-6000K to 10% |
| 105 | Electronic Driver |
| 106 | Drive current (LED)-As per OEM. |
| 107 | Operating voltage-140 V to 270 V AC supply or better |
| 108 | Type of driver-Constant current output driver |
| 109 | THD-Less than 10% |
| 110 | Surge Protection-2 KV minimum |
| 111 | Efficiency Driver->85% |
| 112 | Protection-Shall have under voltage and over voltage protection. |
| 113 | Guarantee of LED fittings including LED driver-5 years against manufacturing defect. |
| 114 | Fixture-Should comply with LM 79 test from NABL/UL lab. |
| 115 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 116 | Life of LED-50000 burning hours at 70% lumen maintenance |
| 117 | LED Bulk head >800 Lumens. |
| 118 | Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor,, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 119 | Exhaust Fan, 200 mm sweep |
| 120 | Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Domestic type. |
| 121 | Exhaust Fan, Light duty, (Domestic) 225/230 mm sweep |
| 122 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 123 | 6 way , Double door |
| 124 | 12 way , Double door |
| 125 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 126 | Single pole |
| 127 | Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required. |
| 128 | 50/63 A DP |
| 129 | Supplying and fixing call bell/ buzzer/ding-dong suitable for single phase, 230 V, complete as required. |
| 130 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 131 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
| 132 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 133 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 134 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run) |
| 135 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 136 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 137 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 138 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 139 | Supplying and fixing following rating, follwing pole, 240/415 V( four pole ), residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 140 | 63 A Four Pole |
| 141 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required. |
| 142 | Armoured cable 25 sq. mm (3.5 core) |
| 143 | Armoured cable 120 sq. mm (3.5 core) |
| 144 | Armoured cable 95 sq. mm (3.5 core) |
| 145 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 146 | Armoured cable 120 sq. mm (3.5 core) |
| 147 | Armoured cable 95 sq. mm (3.5 core) |
| 148 | Providing and fixing MCCB Size I Enclosure in built neutral link for 3pole and 4 pole MCCB as complete in all respects.Approved make Schneider, L&T, Siemens, ABB, HAVEL,legrand etc. .63 to 125 Amps. |
| 149 | Providing and Fixing following eating and breaking capacity 4-pole MCCB 25 Ka THERMAL RELEASE HAVING (O/L& S/C) PROTECTION WITH SPREADER TERMINAL & ROH, in the existing cubical panel board including drilling holes in the cubical panel, making connections etc. as required. make: Schneider, L&T, Siemens, ABB, HAVEL,legrand etc. |
| 150 | MCCB 63 Amps. 4 pole |
| 151 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical sub Panel . The Panel shall be compartmentalized type having space and Arrangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall beFabrication in 1.6MM. CRCA Sheet Powder Coating in Siemens Gray Shade, 75x40mm.Channel Base Frame, Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. . Aluminium E-91 Grade Main Bus Bar, Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer ,Hardware etc.250 A. Aluminium E-91 Grade Main Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt, Washer ,Hardware etc. Approximate Size of panel (H ) 2000MM X (W) 2150 MM X (D) 300 MM . All busbar links,copper solid/ copper flexible wire interconnection busbar to MCCB/MCB to field side for cable termination shall be covered/ insulated with heat shrinkable sleeves of coloured coated Red, Yellow, Blue& Black. Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. & labour etc, gasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc,as per specification.The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB, HAVEL,legrand etc. |
| 152 | Main Incomer :-MCCB 200A 4P 36 KA TMR With O/L & S/C Protection(1No.),Spreader Terminal MCCB 200 A 4P (2No.) Current Transformer (3Nos) ,Phase Indicating Lamp R Y B (3Nos) ,Control SP MCB (3Nos) ,Terminal Strip (1No), ( Digital metering set ( detail below) (1No.) Amp. Meter 96x96MM (1No.)Volt Meter 96x96MM (1 No.) Ammeter selector switch (1No.), |
| 153 | Outgoing:- MCCB 63A 3P 25KA TMR With O/L & S/C Protection To Lift (1 No.),Spreader Terminal MCCB 63A 3P (2 No.), Space for KWH Meter Single Phase(13 No.),Space for KWH Meter Three Phase (1 No.), Backalite Sheet 6MM for KWH Meter Fixing (14 No.). |
| 154 | Fabrication/Painting & Assembly |
| 155 | Fabrication charges of cubical type,Indoor type, Single door, Wall mounted, fixed type, free standing single front,dust proof & compartmentalized Distribution Board made out of M.S. CRC Sheet 16G, duly painted with Siemens Grey Pow der Coated Paint as per specification. Approximate Size (H ) 2000MM X (W) 2150 MM X (D) 300 MM. |
| 156 | Assembly Charges of 400A 4Strip Aluminium Busbar (Horizontal/ Vertical) & Earth strud (current density of Aluminium Busbar shall be 1mmx1mm=1.00 Amp.) Aluminium shall be Electric Grade , Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. |
| 157 | Assembly Charges of Aluminium solid/ Copper flexible wire interconnection Busbar to MCCB & MCCB to field side for Cable termination (10 sq mm Copper ) duly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. |
| 158 | Control Wiring with Copper flexible Wire (size of control wire shall be 2.5 sq. mm Copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mm for control Wiring) with thimbles printed sleeves, tie & belt etc. |
| 159 | The cost of panel should be complete with Assembly charges of 250 4 strips Busbar (horizontal/vertical & earth strip throughout the length of panel (current density of aluminium busbar shall not be less than 1.0 amps/ mmsq. .Aluminium shall be electric grade E-91E,busbar supports shall be DMC eposy insulator .All busbars links shall be covered /insulated with heat shrinkable sleeves of coloured coded Red,Yellow,Blue& Black Approximate size of panel. .Assembly charges of aluminium copper solid /copper flexible wire interconnections in ACB/SWITCH & ACB/MCCB to field side for cable termination duly covered/insulated with heat shrinkable sleeves of coloured coded Red,Yellow,Blue& Black.All interconnections offields side are supported by conical L & Fingers type insulators of adequate size to support sustain the weight of cables .control wiring with copper flexible wire (size of control wire shall be 2.5 sqmm copper fexible for CT circuit & 1.0 sqmm for control & 1.0 sqmm for scada wiring) with thumbles printed sleeves,tie & belt etc.Assembly charges of accessories like gasket,doorlocks,copper flexible door earth legend plates etc. and shold be complete with all accessories as detailed above (35.01 to 35.07 )'The Switchgear & accessories, should be of Schneider, L&T, Siemens, ABB, HAVEL,legrand etc. |
| 160 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. including laying the pipe as surface/recess as required complete at site. |
| 161 | DWC pipe 75/ mm. |
| 162 | B- Providing Lifts:- Supply installation Testing and commissioning of 1No 8 Passenger Lift/ 544 Kgs / 1.5 speed/6 Floors/6 Stops (MRL-1.5MPS)with following specification and feature with one year free AMC from the date of handing over the lift. |
| 163 | MAIN SPECIFICATIONS:- |
| 164 | Type:-Gearless Passenger Lift |
| 165 | No. Lifts:- 01 (One) |
| 166 | Capacity :- 544 KGS/ 8 Person |
| 167 | Speed :- 1.5 Meter/sec. |
| 168 | Control:- High Performance Simplex Full Collective Control System |
| 169 | Drive:- AC VVVF drive for more power saving, comfort & safe ride |
| 170 | BUILDING DATA:- |
| 171 | Stop/Opening :- 06 stops/06 openings |
| 172 | Floor:- G,1,2,3,4,5. |
| 173 | Travel:- 18 Meters (approx.) |
| 174 | Shaft Size:-1800 mm wide x 1650 mm deep |
| 175 | Overhead:- 5200 mm |
| 176 | Pit:- 1600 mm |
| 177 | M/C Position :- Gearless machine shall be placed within the lift shaft (MRL) |
| 178 | CAR ENCLOUSURE , LANDING DOOR AND CAR DOOR SPECIFICATIONS:- |
| 179 | CAR AREA INSIDE :-1100 mm wide x 1300 mm deep (1.43 Sq. meter) |
| 180 | CAR ENCLOSURE:- S.S Scratch resistant cabin, Granite flooring on heavy duty M.S. Platform, S.S. handrails at three side of car, decorative false ceiling with LED lighting, blower fan |
| 181 | CLEAR OPENING:-800 mm wide x 2000 mm height. |
| 182 | CAR DOOR :-Center opening automatic door (S.S Scratch Resistant Finish) |
| 183 | LANDING DOOR :- Center opening automatic door (S.S Scratch Resistant Finish) |
| 184 | POWER SUPPLY:-Three Ø 415 V AC, 50 Hz +/- 5% Single Ø 230 V AC, 50 Hz +/- 5% |
| 185 | DESIGN:-These components are generally confirmed as per Indian standard specification for elevators or escalators. |
| 186 | SPECIAL FEATURES:- |
| 187 | Direction arrow with digital position indicators in car and at all landing |
| 188 | Very attractive push buttons with illuminated call registration light in car and all landings |
| 189 | Car emergency light, emergency alarm and emergency stop operation |
| 190 | Intercom communication system from car to ground floor |
| 191 | Voice announcing system for car |
| 192 | Full length Infrared door curtain safety for auto doors |
| 193 | Overload warning device (OLWD) |
| 194 | Automatic rescue device in case of power failure or emergency landing (ARD) |
| 195 | Fireman switch safety device as per elevator & escalator act |
| 196 | The prices of the complete job as per the specification above shall be inclusive of steel items,minor building work,scaffolding etc.All sundry fittings, assemblies, acessories, hardware item, foundation bolt, terminal lugs for electrical connection are required and item which are usefull and necessary for proper assembly and efficient working of various component shall be deemed to have been included in this job,weathersuch item are specifically mentioned in tender documents or not. |
| 197 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/6 Floors/6 Stops (MRL-1.5MPS) 2nd year |
| 198 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/6 Floors/6 Stops (MRL-1.5MPS) 3rd year |
| 199 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/6 Floors/6 Stops (MRL-1.5MPS) 4th year |
| 200 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/6 Floors/6 Stops (MRL-1.5MPS) 5th year |
| 201 | Supply installation Testing and commissioning of 1No 8 Passenger Lift/ 544 Kgs / 1.5 speed/7Floors/7 Stops with Machine Room with following specification and feature with one year free AMC from the date of handing over the lift. |
| 202 | MAIN SPECIFICATIONS:- |
| 203 | Type:-Gearless Passenger Lift |
| 204 | No. Lifts:- 01 (One) |
| 205 | Capacity :- 544 KGS/ 8 Person |
| 206 | Speed :- 1.5 Meter/sec. |
| 207 | Control:- High Performance Simplex Full Collective Control System |
| 208 | Drive:- AC VVVF drive for more power saving, comfort & safe ride |
| 209 | BUILDING DATA:- |
| 210 | Stop/Opening :- 06 stops/06 openings |
| 211 | Floor:- G,1,2,3,4,5,6. |
| 212 | Travel:- 21 Meters (approx.) |
| 213 | Shaft Size:-1900 mm wide x 1650 mm deep |
| 214 | Overhead:- 5200 mm |
| 215 | Pit:- 1600 mm |
| 216 | M/C Position :- Gearless machine shall be placed within the lift shaft (MR) |
| 217 | CAR ENCLOUSURE , LANDING DOOR AND CAR DOOR SPECIFICATIONS:- |
| 218 | CAR AREA INSIDE :-1100 mm wide x 1300 mm deep (1.43 Sq. meter) |
| 219 | CAR ENCLOSURE:- S.S Scratch resistant cabin, Granite flooring on heavy duty M.S. Platform, S.S. handrails at three side of car, decorative false ceiling with LED lighting, blower fan |
| 220 | CLEAR OPENING:-800 mm wide x 2000 mm height. |
| 221 | CAR DOOR :-Center opening automatic door (S.S Scratch Resistant Finish) |
| 222 | LANDING DOOR :- Center opening automatic door (S.S Scratch Resistant Finish) |
| 223 | POWER SUPPLY:-Three Ø 415 V AC, 50 Hz +/- 5% Single Ø 230 V AC, 50 Hz +/- 5% |
| 224 | DESIGN:-These components are generally confirmed as per Indian standard specification for elevators or escalators. |
| 225 | SPECIAL FEATURES:- |
| 226 | Direction arrow with digital position indicators in car and at all landing |
| 227 | Very attractive push buttons with illuminated call registration light in car and all landings |
| 228 | Car emergency light, emergency alarm and emergency stop operation |
| 229 | Intercom communication system from car to ground floor |
| 230 | Voice announcing system for car |
| 231 | Full length Infrared door curtain safety for auto doors |
| 232 | Overload warning device (OLWD) |
| 233 | Automatic rescue device in case of power failure or emergency landing (ARD) |
| 234 | Fireman switch safety device as per elevator & escalator act |
| 235 | The prices of the complete job as per the specification above shall be inclusive of steel items,minor building work,scaffolding etc.All sundry fittings, assemblies, acessories, hardware item, foundation bolt, terminal lugs for electrical connection are required and item which are usefull and necessary for proper assembly and efficient working of various component shall be deemed to have been included in this job,weathersuch item are specifically mentioned in tender documents or not. |
| 236 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/7Floors/7 Stops with machine room 2nd year |
| 237 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/7Floors/7 Stops with machine room 3rd year |
| 238 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/7Floors/7 Stops with machine room 4th year |
| 239 | AMC of 8 Passenger Lift/ 544 Kgs / 1.5 speed/7Floors/7 Stops with machine room 5th year |
| 240 | C. Providing Solar Light.:- Supply and installation of G.I Pipe 2/1/2'' (65MM) (heavy C-Class ) as directed by Engineer-in-charge, complete in all respects as required:-Make-Jindal or any equivalent make. |
| 241 | G.I. Pipe 2/1/2 (65mm) |
| 242 | Supplying and installation of 25W is all in one Solar Street Light having compact and fully integrated design with intelligent features includes a bult in Solar Panel, Lithium Ferro Phosphate (LiFePO4) Battery,Charge controller and Motion Sensor. The solution is available from 25 W to 80W and compatible with Bjaj Citisol Remote Monitoring System. with Temperature 5700K. as required. Make:- Bajaj,Philips and Havells etc. with five year warranty at site. |
| 243 | Supplying and Fixing of G.I. bracket with Double Arm Suitable For 25W is all in one Solar Street Light including Nut-Bolt, Welding,Suitable Paint as required complete in all respect and as per the satisfection of Engineer-in-Charge. |
| 244 | Supplying and Fixing of G.I. bracket with Single Arm Suitable For 25W is all in one Solar Street Light including Nut-Bolt, Welding, Suitable Paint as required complete in all respect and as per the satisfection of Engineer-in-Charge. |
| 245 | Erection of RCC/ PCC pole of following length in brick ballast and ramming the foundation, finishing with 150mm thick cement concrete (1:3:6) layer on top with including excavation and refilling etc as required.Above 3 metre and upto 6 metre |
| 246 | D-Providing Fire Fighting System:- Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/ support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required.Make :- Jindal/TATA/SAIL. |
| 247 | 25 mm |
| 248 | 80 mm |
| 249 | 100 mm |
| 250 | 150 mm |
| 251 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required.Make:- Make:- Minimax /Newage/ceasefire and atassee. |
| 252 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Make:- Minimax /Newage/ceasefire and atassee. |
| 253 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: Make:- Minimax /Newage/ceasefire and atassee. |
| 254 | Providing &fixing fibre glass reinforced Fire Hose Cabinet ( 30\\"x24\\"x10\\") out door type, made out of sheet having glazed door with 6mm thick clear Glass including necessary Locking arrangement with allen Key, powder coating with Post Office Red Paint and for Hoseing 2 Nos .RRL Hose Pipe, 1 No Branch pipe including grounding and suitable inscripting the words\\" Hose Cabinet\\" on the Box complete as requried. Make:- Minimax /Newage/ceasefire and atassee. |
| 255 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required:Make:- Minimax /Newage/ceasefire and atassee. |
| 256 | Four Way |
| 257 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. Make:- Zoloto /Sant/Leader and grundfos. |
| 258 | 80 mm Dia |
| 259 | 100 mm Dia |
| 260 | 150 mm Dia |
| 261 | Providing, installation, Testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts,nuts, washers etc.as required. Make:- Zoloto /Sant/Leader and grundfos. |
| 262 | 80 mm dia |
| 263 | 100 mm Dia |
| 264 | 150 mm Dia |
| 265 | supply, Installing, testing and commissioning of 100mm dial type pressure gauge gate valve with all accessories as requried. Make. .Guru.,System sensor,Fbig. |
| 266 | supply, Installing, testing and commissioning of 25mm dia gate valve with all accessories as requried.Make:- Zoloto /Sant/Leader and grundfos. |
| 267 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 268 | Providing & fixing of IS marked (IS:15683) portable fire extinguisher, carbondioxide type flat base including valve, discharge hose of not less than 10 mm dia. 1 M long & complete in all respects including initial fill with CO2 gas confirming to IS:15222 filled to a filling ratio of not more than 0.667 and wall suspension bracket. (ISI MARKED) ..Make:- Minimax/ceasefire/safex Life Guard. |
| 269 | 4.5kg |
| 270 | Providing & Fixing 4 Kg. ABC MAP-50% Powder type fire extinguishers are manufactured and marked to Indian standard IS: 15683. Hose shall made of EPDM Rubber, CE Marked Valve, Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases.(ISI MARKED) .Make:- Minimax/ceasefire/safex Life Guard and Atasee. |
| 271 | Providing and fixing Water CO2 9 .Litrs type fire extinguishers consisting of seamless cylindrical body, squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS: 15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. (ISI MARKED) .Make:- Minimax/ ceasefire/ safex Life Guard and Atasee. |
| 272 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 273 | Providing and fixing welded mesh 25mm x 25mm X 3mm thick as per approved design by welding with electrical plant complete including applying priming coat of red lead paint as per HP.PWD. Specification 1990 Volume-I including carriage of materials upto all leads and lifts. |
| 274 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.Make:- Sintex,D.Plast five layer. |
| 275 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. 15mm dia nominal bore. Internal work. |
| 276 | Supplying, installation,testing & commissioning of eletric driven terrace pump suitable for automatic operation and consisting of following, 35mtr head 900 LPM complete in all resapcxt, as required:(Terrace Pump)(a) mono block pump of cast iron body & bronze impeller with stainless steel shaft, suitable HP Squirell cageinduction on 415 volts, 3 phase, 50 Hz AC Supply with IP55 class of protection for enclosure, M.S fabricated common base olate, coupling, coupling gaurd complete in all respact. Please Enable Macros to View BoQ information |