Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Pharmacy Department |
| 2 | Fire Fighting System |
| 3 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : DSR 2022 SI No 18.7 |
| 4 | 25 mm dia (18.7.1) |
| 5 | 32 mm dia (18.7.2) |
| 6 | 50mm dia (18.7.4) |
| 7 | 80 mm dia (18.7.6) |
| 8 | 100 mm dia (18.7.7) |
| 9 | 150 mm dia (18.7.8) |
| 10 | 200 mm dia (18.7.9) |
| 11 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. DSR 2022 SI No 18.6.2 |
| 12 | 150 mm dia (18.6.2) |
| 13 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS884 complete with the followingas required. 20mm nominal internal diawater hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20mm nominal internal dia gunmetal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25mm dia stopgunmetal valve & M.S. Pipe and socket.t. DSR No 18.17:1 |
| 14 | Supplying and fixing single headed internal/External hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : as per DSR 2022 S.I. No. 18. 9.1 & 18.10.1 Single Handed Gunmetal |
| 15 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : DSR 2022 SI No. 18.18.1 |
| 16 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : DSR 2022 SI.No.18.16.1 Gun metal |
| 17 | Providing/fixing of Weather proof standard fire hose cabinet (900 mm X 600 mm X 450 mm) Outdoor type made of not les thad 16/18 SWGMS sheet having glassed hinged door (5 mm thick glass ) including necessary locking arrangement with handle for housing hydrant valve, two nos. 15 meter long fire hose pipes , branch pipe as required as per drawings. including brackets for mounting accessories , painting ( one coat primer and two coat of fire red color). The cabined shall be mounted on self standing mounting type painted MS Angle iron frame as required . the words \\"FIRE HOSE\\" to be painted on the box MR |
| 18 | Supplying Installation testing & Commissioning of 25 mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. MR |
| 19 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 20 | 2 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.1 |
| 21 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 22 | 4 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.2 |
| 23 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. DSR 2022 SI No. 18.20 |
| 24 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. 450 Lpm at 35 m Head DSR 2022 SI No. 18.4.2 |
| 25 | PUMP ROOM |
| 26 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainlesssteel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-325. supply , Installation, testing and commissioning of fire Hydrant valve , bearing to IS:5290 marks, S.S. ,IS: 304 Grade, 63mm oblique instantaneous single out let, 75mm N.B. flanged inlet, brass spindles complete with PVC blank cap . G.I. chain etc. guard,foundation bolts etc.as required. supply , Installation, testing and commissioning of Branch pipe . S.S. short type with 63mm male instantaneous inlet, male threaded outlet fitted with 15mm, Bore nozzle,having IS: 903 with anti vibration pads. |
| 27 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.1.8 |
| 28 | P/F weather proof standard fire hose cabinet locing arrangement with handle for housing hydrant valve two nos. 15 mts. Long fire hose pipes, branch pipes as reqd. as per drawing , including bracket for mounting accessories, painting (one coat primer and two coat of fire red color ) the cabinet shall be mounted on self standing mounted type painted M.S. angle iron frame as reqd. diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven supply , Installation, testing and commissioning of 25mm air release valve gunmetal, conforming to IS: 903:1993, having rubber ball and with 25mm BSP. THREADED male inlet including necessory accessories Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 29 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.2.8 |
| 30 | A) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump)(B) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS: 1520.(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS: 325.(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 31 | 180 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.3.2 |
| 32 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with. |
| 33 | INCOMING |
| 34 | 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500A |
| 35 | Outgoings |
| 36 | ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 37 | Main Fire Pump |
| 38 | 160 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 39 | Jockey Pump |
| 40 | 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 41 | Diesel Engine Control |
| 42 | Control for diesel engine comprising - |
| 43 | Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. DSR 2022 SI no. 18.5.2 |
| 44 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of :a) One 63 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA.b)One Volt meter (0-500 V) with selector switch.c) One set including lamps. (MR) |
| 45 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. DSR SI No.18.22 |
| 46 | Providing & fixing of Flow switch in Following sizes in M.S. pipe line including connection etc. as required. DSR SI No.18.23.2150 mm Dia. |
| 47 | Providing and fixing in position the industrial type pressure gauges with gun metal/brass valves complete as required DSR-2022 SI No. 16.8 |
| 48 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. DSR 2022 SI no. 18.13 |
| 49 | Providing, installation, testing and commissioning of stainless steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. DSR 2022 Sl No 18.15 |
| 50 | 100 mm dia (18.15.2) |
| 51 | 150 mm dia (18.15.3) |
| 52 | 200 mm dia (18.15.4) |
| 53 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : DSR 2022 SI No 18.11 |
| 54 | 80 mm dia (18.11.4) |
| 55 | 100 mm dia (18.11.5) |
| 56 | 150 mm dia (18.11.6) |
| 57 | 200 mm dia (18.11.7) |
| 58 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : DSR 2022 SI No. 18.14 |
| 59 | 80 mm dia (18.14.4) |
| 60 | 100 mm dia (18.14.5) |
| 61 | 150 mm dia (18.14.7) |
| 62 | Providing, installation, testing and commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed of FM approved complete as required. DSR 2022 SI No. 18.29 |
| 63 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. DSR 2022 Sl. No. 18.25 |
| 64 | 700 mm (18.25.1) |
| 65 | 1000 mm (18.25.2) |
| 66 | Providing/Fixing Fire man axe. Make. (MR) |
| 67 | Providing, fixing, testing & commissioning of resilient rubber lined single Arch Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 (MR) |
| 68 | 150 mm dia |
| 69 | FIRE EXTINGUISHERS |
| 70 | Supply and fixingof C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1132 |
| 71 | Supply and fixingof fire extinguisher,ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1131(A) |
| 72 | Fire Alarm SystemWork |
| 73 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. DSR 2022 SI No 17.2.1.2 |
| 74 | Two Loop Panel. |
| 75 | Supplying, installation, testing and commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required. DSR 2022 SI No 17.2.4 |
| 76 | Supplying, installation, testing and commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. DSR 2022 SI No 17.2.5 |
| 77 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. DSR 2022 SI No 17.2.11 |
| 78 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. DSR 2022 SI No 17.2.14 |
| 79 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. DSR 2022 SI No 17.2.15 |
| 80 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. DSR 2022 SI No 17.2.10 |
| 81 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. DSR 2022 SI No 17.2.7 |
| 82 | Supply, Installation and commissioning of Annunciator Panel with 7 windows with point, zone & system status used. (MR) |
| 83 | Supply Installation wire for annunciator panel ,(3 core 1.5 sqmm) MR |
| 84 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset ackowledge and silence switches complete as required.DSR 2022 SI No 17.2.3 |
| 85 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required DSR-2022 SI.No.17.3.1 |
| 86 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.DSR-2022 SI.No.17.3.3 |
| 87 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.DSR-2022 SI.No.17.3.6 |
| 88 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.DSR-2022 SI.No.17.3.9 |
| 89 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.. DSR 2022 SI NO. 17.5.2 |
| 90 | Armoured Cables (Cable/Gland/Lug) : |
| 91 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PWD SOR 2024 SI No (20a.1) |
| 92 | 16 Sqmm 4 Core |
| 93 | 35 Sqmm 3.5 Core |
| 94 | 70 Sqmm 3.5 Core |
| 95 | 95 Sqmm 3.5 Core |
| 96 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. PWD SOR 2018 SI No 503 |
| 97 | 16 Sqmm 4 Core |
| 98 | 35 Sqmm 3.5 Core |
| 99 | 70 Sqmm 3.5 Core |
| 100 | 95 Sqmm 3.5 Core |
| 101 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of the Engineer incharge.PWD SOR 2018 SI No 504 |
| 102 | 16 Sqmm |
| 103 | 35 Sqmm |
| 104 | 70 Sqmm |
| 105 | 95 Sqmm |
| 106 | Earthing Work |
| 107 | Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) Make : As approved in U.P.P.W.D. & C.P.R.I. Certified. SOR 2018 Sl No 726 B |
| 108 | Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects. SOR 2018 Sl No 716 |
| 109 | Fire Sand Bucket |
| 110 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. SOR 2018 Sl No 1133 |
| 111 | Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules SOR 2018 Sl No 1136 |
| 112 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. DSR 2022 Sl No. 4.6 |
| 113 | 150 mm width X 50 mm depth X 1.6 mm thickness (4.6.2) |
| 114 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve,with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : (With common burnt clay F.P.S.(non modular) bricks of class designation 7.5) CIVIL DSR 2023 Sl No. 18.33.1 |
| 115 | Providing & Fixing of 1.6 mm thick M.S/Door Frame, Door capable of accommodating fire Hose Reel, Landing Valve, Hose Pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making Recessed type mansoary box (by civil contractor). (MR) |
| 116 | 1500x900 mm (Indoor Cabinet) Only Frame |
| 117 | Supply and fixing of self glow type exit sinage. (LED Type) (MR) |
| 118 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Civil DSR 2023 si no. 18.48 |
| 119 | Providing & laying pipe of required dia including cutting the road & surface dressing complete in all respect as directed by E/I. MR |
| 120 | Cost of minor repair @ repainting of necessary works after installation of fire figting works. |
| 121 | Construction of 50 Kl.underground water tank with pump house |
| 122 | densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of size 595x595 mm of approved texture, design and pattern as per CPWD specification 2019, to be laid in true horizontal level suspended on interlocking medal T-Grid of hot galvanised iron section of 0.33 mm thick(galvanised @ 120 gram per sqm including both sides) comprising of main-T runner of size 24x38 mm of length 3000mm cross-T of size24x32 mm of length 1200 mm and secondary intermediate cross T of size 24x32 mm of length 600 mm to formgrid module of size (600x600 mm, suspended from ceiling using galvanised steel items (galvanising@80 gram per sqm) i.e 12x50 mm long dash fastener, 6 mm dia fully threaded hanger rod upto 1000 mm length and L shape level adjuster of size 72x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6 mm thick of precut hole on both 25 mm flanze to pierce into 12x50mm or even bigger size dash fastener if required, fixed with galvanised iron perimeter wall angle or size 24x24x0.4 mm of length 3000 mm to be fixed on periphery wall/partition with the help of plastic rawl plug at 450 mm centre to centre and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing as per direction of engineer in charge With 15 mm Tegular edged light weight calcium silicate false ceiling tiles Civil DSR 2023 26.22.1 |
| 123 | Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by E/I with in a distance of 60 meters. MR |
| 124 | 25 mm dia (9\\") |
| 125 | 32 mm dia (9\\") |
| 126 | 50 mm dia (9\\") |
| 127 | 80 mm dia (9\\") |
| 128 | 100 mm dia (9\\") |
| 129 | 150 mm dia (9\\") |
| 130 | Grouting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by E/I MR |
| 131 | 25 mm dia |
| 132 | 32 mm dia |
| 133 | 50 mm dia |
| 134 | 80 mm dia |
| 135 | 100 mm dia |
| 136 | 150 mm dia |
| 137 | Burn Ward |
| 138 | Fire Fighting System |
| 139 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : DSR 2022 SI No 18.7 |
| 140 | 25 mm dia (18.7.1) |
| 141 | 32 mm dia (18.7.2) |
| 142 | 50mm dia (18.7.4) |
| 143 | 80 mm dia (18.7.6) |
| 144 | 100 mm dia (18.7.7) |
| 145 | 200 mm dia (18.7.9) |
| 146 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. DSR 2022 SI No 18.6.2 |
| 147 | 150 mm dia (18.6.2) |
| 148 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS884 complete with the followingas required. 20mm nominal internal diawater hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20mm nominal internal dia gunmetal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25mm dia stopgunmetal valve & M.S. Pipe and socket.t. DSR No 18.17:1 |
| 149 | Supplying and fixing single headed internal/External hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :as per DSR 2022 S.I. No. 18. 9.1 & 18.10.1 Single Handed Gunmetal |
| 150 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : DSR 2022 SI No. 18.18.1 |
| 151 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : DSR 2022 SI.No.18.16.1 Gun metal |
| 152 | Providing/fixing of Weather proof standard fire hose cabinet (900 mm X 600 mm X 450 mm) Outdoor type made of not les thad 16/18 SWGMS sheet having glassed hinged door (5 mm thick glass ) including necessary locking arrangement with handle for housing hydrant valve, two nos. 15 meter long fire hose pipes , branch pipe as required as per drawings. including brackets for mounting accessories , painting ( one coat primer and two coat of fire red color). The cabined shall be mounted on self standing mounting type painted MS Angle iron frame as required . the words \\"FIRE HOSE\\" to be painted on the box MR |
| 153 | Supplying Installation testing & Commissioning of 25 mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. MR |
| 154 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 155 | 2 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.1 |
| 156 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. DSR 2022 SI No. 18.20 |
| 157 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. 450 Lpm at 35 m Head DSR 2022 SI No. 18.4.2 |
| 158 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of :a) One 63 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA.b)One Volt meter (0-500 V) with selector switch.c) One set including lamps. (MR) |
| 159 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. DSR SI No.18.22 |
| 160 | Providing & fixing of Flow switch in Following sizes in M.S. pipe line including connection etc. as required. DSR SI No.18. 23150 mm Dia. |
| 161 | Providing and fixing in position the industrial type pressure gauges with gun metal/brass valves complete as required DSR-2022 SI No. 16.8 |
| 162 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. DSR 2022 SI no. 18.13 |
| 163 | Providing, installation, testing and commissioning of stainless steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. DSR 2022 Sl No 18.15 |
| 164 | 100 mm dia (18.15.2) |
| 165 | 150 mm dia (18.15.3) |
| 166 | 200 mm dia (18.15.4) |
| 167 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : DSR 2022 SI No 18.11 |
| 168 | 80 mm dia (18.11.4) |
| 169 | 100 mm dia (18.11.5) |
| 170 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : DSR 2022 SI No. 18.14 |
| 171 | 100 mm dia (18.14.5) |
| 172 | Providing, fixing Testing &commissioning of 15mm dia quartzoid bulb type sprinkler of rating 68 degree centigrade with required accessories DSR 2022 SI No. 18.21 |
| 173 | Pendent Type(18.21.1) |
| 174 | Upright Sprinkler (18.21.2) |
| 175 | Providing, installation, testing and commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed of FM approved complete as required. DSR 2022 SI No. 18.29 |
| 176 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. DSR 2022 Sl. No. 18.25 |
| 177 | 700 mm (18.25.1) |
| 178 | 1000 mm (18.25.2) |
| 179 | Providing/Fixing Fire man axe. Make. (MR) |
| 180 | Providing, fixing, testing & commissioning of resilient rubber lined single Arch Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 (MR) |
| 181 | 150 mm dia |
| 182 | FIRE EXTINGUISHERS |
| 183 | Supply and fixingof C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1132 |
| 184 | Supply and fixingof fire extinguisher,ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1131 (A) |
| 185 | Fire Alarm SystemWork |
| 186 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. DSR 2022 SI No 17.2.1.2 |
| 187 | Two Loop Panel. |
| 188 | Supplying, installation, testing and commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required. DSR 2022 SI No 17.2.4 |
| 189 | Supplying, installation, testing and commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. DSR 2022 SI No 17.2.5 |
| 190 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. DSR 2022 SI No 17.2.11 |
| 191 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. DSR 2022 SI No 17.2.14 |
| 192 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. DSR 2022 SI No 17.2.15 |
| 193 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. DSR 2022 SI No 17.2.10 |
| 194 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. DSR 2022 SI No 17.2.7 |
| 195 | Supply, Installation and commissioning of Annunciator Panel with 7 windows with point, zone & system status used. (MR) |
| 196 | Supply Installation wire for annunciator panel ,(3 core 1.5 sqmm) MR |
| 197 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset ackowledge and silence switches complete as required.DSR 2022 SI No 17.2.3 |
| 198 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required DSR-2022 SI.No.17.3.1 |
| 199 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.DSR-2022 SI.No.17.3.3 |
| 200 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.DSR-2022 SI.No.17.3.6 |
| 201 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.DSR-2022 SI.No.17.3.9 |
| 202 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.. DSR 2022 SI NO. 17.5.2 |
| 203 | Armoured Cables (Cable/Gland/Lug) : |
| 204 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PWD SOR 2024 SI No (20a.1) |
| 205 | 16 Sqmm 4 Core |
| 206 | 35 Sqmm 3.5 Core |
| 207 | 70 Sqmm 3.5 Core |
| 208 | 95 Sqmm 3.5 Core |
| 209 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. PWD SOR 2018 SI No 503 |
| 210 | 16 Sqmm 4 Core |
| 211 | 35 Sqmm 3.5 Core |
| 212 | 70 Sqmm 3.5 Core |
| 213 | 95 Sqmm 3.5 Core |
| 214 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of the Engineer incharge.PWD SOR 2018 SI No 504 |
| 215 | 16 Sqmm |
| 216 | 35 Sqmm |
| 217 | 70 Sqmm |
| 218 | 95 Sqmm |
| 219 | Earthing Work |
| 220 | Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) Make : As approved in U.P.P.W.D. & C.P.R.I. Certified. SOR 2018 Sl No 726 B |
| 221 | Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects. SOR 2018 Sl No 716 |
| 222 | Fire Sand Bucket |
| 223 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. SOR 2018 Sl No 1133 |
| 224 | Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules SOR 2018 Sl No 1136 |
| 225 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. DSR 2022 Sl No. 4.6 |
| 226 | 150 mm width X 50 mm depth X 1.6 mm thickness (4.6.2) |
| 227 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve,with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : (With common burnt clay F.P.S.(non modular) bricks of class designation 7.5) CIVIL DSR 2023 Sl No. 18.33.1 |
| 228 | Supply and fixing of self glow type exit sinage. (LED Type) (MR) |
| 229 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Civil DSR 2023 si no. 18.48 |
| 230 | Providing & laying pipe of required dia including cutting the road & surface dressing complete in all respect as directed by E/I. MR |
| 231 | densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of size 595x595 mm of approved texture, design and pattern as per CPWD specification 2019, to be laid in true horizontal level suspended on interlocking medal T-Grid of hot galvanised iron section of 0.33 mm thick(galvanised @ 120 gram per sqm including both sides) comprising of main-T runner of size 24x38 mm of length 3000mm cross-T of size24x32 mm of length 1200 mm and secondary intermediate cross T of size 24x32 mm of length 600 mm to formgrid module of size (600x600 mm, suspended from ceiling using galvanised steel items (galvanising@80 gram per sqm) i.e 12x50 mm long dash fastener, 6 mm dia fully threaded hanger rod upto 1000 mm length and L shape level adjuster of size 72x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6 mm thick of precut hole on both 25 mm flanze to pierce into 12x50mm or even bigger size dash fastener if required, fixed with galvanised iron perimeter wall angle or size 24x24x0.4 mm of length 3000 mm to be fixed on periphery wall/partition with the help of plastic rawl plug at 450 mm centre to centre and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing as per direction of engineer in charge With 15 mm Tegular edged light weight calcium silicate false ceiling tiles Civil DSR 2023 26.22.1 |
| 232 | Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by E/I with in a distance of 60 meters. MR |
| 233 | 25 mm dia (9\\") |
| 234 | 32 mm dia (9\\") |
| 235 | 50 mm dia (9\\") |
| 236 | 80 mm dia (9\\") |
| 237 | 100 mm dia (9\\") |
| 238 | 150 mm dia (9\\") |
| 239 | Grouting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by E/I MR |
| 240 | 25 mm dia |
| 241 | 32 mm dia |
| 242 | 50 mm dia |
| 243 | 80 mm dia |
| 244 | 100 mm dia |
| 245 | 150 mm dia |
| 246 | Cardiology Department |
| 247 | Fire Fighting System |
| 248 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : DSR 2022 SI No 18.7 |
| 249 | 25 mm dia (18.7.1) |
| 250 | 32 mm dia (18.7.2) |
| 251 | 50mm dia (18.7.4) |
| 252 | 80 mm dia (18.7.6) |
| 253 | 100 mm dia (18.7.7) |
| 254 | 150 mm dia (18.7.8) |
| 255 | 200 mm dia (18.7.9) |
| 256 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. DSR 2022 SI No 18.6.2 |
| 257 | 150 mm dia (18.6.2) |
| 258 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS884 complete with the followingas required. 20mm nominal internal diawater hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20mm nominal internal dia gunmetal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25mm dia stopgunmetal valve & M.S. Pipe and socket.t. DSR No 18.17:1 |
| 259 | Supplying and fixing single headed internal/External hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :as per DSR 2022 S.I. No. 18. 9.1 & 18.10.1 Single Handed Gunmetal |
| 260 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : DSR 2022 SI No. 18.18.1 |
| 261 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : DSR 2022 SI.No.18.16.1 Gun metal |
| 262 | Providing/fixing of Weather proof standard fire hose cabinet (900 mm X 600 mm X 450 mm) Outdoor type made of not les thad 16/18 SWGMS sheet having glassed hinged door (5 mm thick glass ) including necessary locking arrangement with handle for housing hydrant valve, two nos. 15 meter long fire hose pipes , branch pipe as required as per drawings. including brackets for mounting accessories , painting ( one coat primer and two coat of fire red color). The cabined shall be mounted on self standing mounting type painted MS Angle iron frame as required . the words \\"FIRE HOSE\\" to be painted on the box MR |
| 263 | Supplying Installation testing & Commissioning of 25 mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. MR |
| 264 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 265 | 2 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.1 |
| 266 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 267 | 4 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.2 |
| 268 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. DSR 2022 SI No. 18.20 |
| 269 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. 450 Lpm at 35 m Head DSR 2022 SI No. 18.4.2 |
| 270 | PUMP ROOM |
| 271 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainlesssteel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-325. supply , Installation, testing and commissioning of fire Hydrant valve , bearing to IS:5290 marks, S.S. ,IS: 304 Grade, 63mm oblique instantaneous single out let, 75mm N.B. flanged inlet, brass spindles complete with PVC blank cap . G.I. chain etc. guard,foundation bolts etc.as required. supply , Installation, testing and commissioning of Branch pipe . S.S. short type with 63mm male instantaneous inlet, male threaded outlet fitted with 15mm, Bore nozzle,having IS: 903 with anti vibration pads. |
| 272 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.1.8 |
| 273 | P/F weather proof standard fire hose cabinet locing arrangement with handle for housing hydrant valve two nos. 15 mts. Long fire hose pipes, branch pipes as reqd. as per drawing , including bracket for mounting accessories, painting (one coat primer and two coat of fire red color ) the cabinet shall be mounted on self standing mounted type painted M.S. angle iron frame as reqd. diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven supply , Installation, testing and commissioning of 25mm air release valve gunmetal, conforming to IS: 903:1993, having rubber ball and with 25mm BSP. THREADED male inlet including necessory accessories Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 274 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.2.8 |
| 275 | A) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump)(B) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS: 1520.(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS: 325.(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 276 | 180 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.3.2 |
| 277 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with. |
| 278 | INCOMING |
| 279 | 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500A |
| 280 | Outgoings |
| 281 | ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 282 | Main Fire Pump |
| 283 | 160 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 284 | Jockey Pump |
| 285 | 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 286 | Diesel Engine Control |
| 287 | Control for diesel engine comprising - |
| 288 | Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. DSR 2022 SI no. 18.5.2 |
| 289 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of :a) One 63 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA.b)One Volt meter (0-500 V) with selector switch.c) One set including lamps. (MR) |
| 290 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. DSR SI No.18.22 |
| 291 | Providing & fixing of Flow switch in Following sizes in M.S. pipe line including connection etc. as required. DSR SI No.18. 23150 mm Dia. |
| 292 | Providing and fixing in position the industrial type pressure gauges with gun metal/brass valves complete as required DSR-2022 SI No. 16.8 |
| 293 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. DSR 2022 SI no. 18.13 |
| 294 | Providing, installation, testing and commissioning of stainless steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. DSR 2022 Sl No 18.15 |
| 295 | 100 mm dia (18.15.2) |
| 296 | 150 mm dia (18.15.3) |
| 297 | 200 mm dia (18.15.4) |
| 298 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : DSR 2022 SI No 18.11 |
| 299 | 80 mm dia (18.11.4) |
| 300 | 100 mm dia (18.11.5) |
| 301 | 150 mm dia (18.11.6) |
| 302 | 200 mm dia (18.11.7) |
| 303 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : DSR 2022 SI No. 18.14 |
| 304 | 80 mm dia (18.14.4) |
| 305 | 100 mm dia (18.14.5) |
| 306 | 150 mm dia (18.14.7) |
| 307 | Providing, fixing Testing &commissioning of 15mm dia quartzoid bulb type sprinkler of rating 68 degree centigrade with required accessories DSR 2022 SI No. 18.21 |
| 308 | Pendent Type(18.21.1) |
| 309 | Upright Sprinkler (18.21.2) |
| 310 | Providing, installation, testing and commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed of FM approved complete as required. DSR 2022 SI No. 18.29 |
| 311 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. DSR 2022 Sl. No. 18.25 |
| 312 | 700 mm (18.25.1) |
| 313 | 1000 mm (18.25.2) |
| 314 | Providing/Fixing Fire man axe. Make. (MR) |
| 315 | Providing, fixing, testing & commissioning of resilient rubber lined single Arch Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 (MR) |
| 316 | 150 mm dia |
| 317 | FIRE EXTINGUISHERS |
| 318 | Supply and fixingof C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1132 |
| 319 | Supply and fixingof fire extinguisher,ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1131(A) |
| 320 | Fire Alarm SystemWork |
| 321 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. DSR 2022 SI No 17.2.1.2 |
| 322 | Two Loop Panel. |
| 323 | Supplying, installation, testing and commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required. DSR 2022 SI No 17.2.4 |
| 324 | Supplying, installation, testing and commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. DSR 2022 SI No 17.2.5 |
| 325 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. DSR 2022 SI No 17.2.11 |
| 326 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. DSR 2022 SI No 17.2.14 |
| 327 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. DSR 2022 SI No 17.2.15 |
| 328 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. DSR 2022 SI No 17.2.10 |
| 329 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. DSR 2022 SI No 17.2.7 |
| 330 | Supply, Installation and commissioning of Annunciator Panel with 7 windows with point, zone & system status used. (MR) |
| 331 | Supply Installation wire for annunciator panel ,(3 core 1.5 sqmm) MR |
| 332 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset ackowledge and silence switches complete as required.DSR 2022 SI No 17.2.3 |
| 333 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required DSR-2022 SI.No.17.3.1 |
| 334 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.DSR-2022 SI.No.17.3.3 |
| 335 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.DSR-2022 SI.No.17.3.6 |
| 336 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.DSR-2022 SI.No.17.3.9 |
| 337 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.. DSR 2022 SI NO. 17.5.2 |
| 338 | Armoured Cables (Cable/Gland/Lug) : |
| 339 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PWD SOR 2024 SI No (20a.1) |
| 340 | 16 Sqmm 4 Core |
| 341 | 35 Sqmm 3.5 Core |
| 342 | 70 Sqmm 3.5 Core |
| 343 | 95 Sqmm 3.5 Core |
| 344 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. PWD SOR 2018 SI No 503 |
| 345 | 16 Sqmm 4 Core |
| 346 | 35 Sqmm 3.5 Core |
| 347 | 70 Sqmm 3.5 Core |
| 348 | 95 Sqmm 3.5 Core |
| 349 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of the Engineer incharge.PWD SOR 2018 SI No 504 |
| 350 | 16 Sqmm |
| 351 | 35 Sqmm |
| 352 | 70 Sqmm |
| 353 | 95 Sqmm |
| 354 | Earthing Work |
| 355 | Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) Make : As approved in U.P.P.W.D. & C.P.R.I. Certified. SOR 2018 Sl No 726 B |
| 356 | Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects. SOR 2018 Sl No 716 |
| 357 | Fire Sand Bucket |
| 358 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. SOR 2018 Sl No 1133 |
| 359 | Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules SOR 2018 Sl No 1136 |
| 360 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. DSR 2022 Sl No. 4.6 |
| 361 | 150 mm width X 50 mm depth X 1.6 mm thickness (4.6.2) |
| 362 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve,with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : (With common burnt clay F.P.S.(non modular) bricks of class designation 7.5) CIVIL DSR 2023 Sl No. 18.33.1 |
| 363 | Providing & Fixing of 1.6 mm thick M.S/Door Frame, Door capable of accommodating fire Hose Reel, Landing Valve, Hose Pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making Recessed type mansoary box (by civil contractor). (MR) |
| 364 | 1500x900 mm (Indoor Cabinet) Only Frame |
| 365 | Supply and fixing of self glow type exit sinage. (LED Type) (MR) |
| 366 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Civil DSR 2023 si no. 18.48 |
| 367 | Providing & laying pipe of required dia including cutting the road & surface dressing complete in all respect as directed by E/I. MR |
| 368 | Cost of minor repair @ repainting of necessary works after installation of fire figting works. |
| 369 | densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of size 595x595 mm of approved texture, design and pattern as per CPWD specification 2019, to be laid in true horizontal level suspended on interlocking medal T-Grid of hot galvanised iron section of 0.33 mm thick(galvanised @ 120 gram per sqm including both sides) comprising of main-T runner of size 24x38 mm of length 3000mm cross-T of size24x32 mm of length 1200 mm and secondary intermediate cross T of size 24x32 mm of length 600 mm to formgrid module of size (600x600 mm, suspended from ceiling using galvanised steel items (galvanising@80 gram per sqm) i.e 12x50 mm long dash fastener, 6 mm dia fully threaded hanger rod upto 1000 mm length and L shape level adjuster of size 72x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6 mm thick of precut hole on both 25 mm flanze to pierce into 12x50mm or even bigger size dash fastener if required, fixed with galvanised iron perimeter wall angle or size 24x24x0.4 mm of length 3000 mm to be fixed on periphery wall/partition with the help of plastic rawl plug at 450 mm centre to centre and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing as per direction of engineer in charge With 15 mm Tegular edged light weight calcium silicate false ceiling tiles Civil DSR 2023 26.22.1 |
| 370 | Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by E/I with in a distance of 60 meters. MR |
| 371 | 25 mm dia (9\\") |
| 372 | 32 mm dia (9\\") |
| 373 | 50 mm dia (9\\") |
| 374 | 80 mm dia (9\\") |
| 375 | 100 mm dia (9\\") |
| 376 | 150 mm dia (9\\") |
| 377 | Grouting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by E/I MR |
| 378 | 25 mm dia |
| 379 | 32 mm dia |
| 380 | 50 mm dia |
| 381 | 80 mm dia |
| 382 | 100 mm dia |
| 383 | 150 mm dia |
| 384 | Gastrology Department |
| 385 | Fire Fighting System |
| 386 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : DSR 2022 SI No 18.7 |
| 387 | 25 mm dia (18.7.1) |
| 388 | 32 mm dia (18.7.2) |
| 389 | 50mm dia (18.7.4) |
| 390 | 80 mm dia (18.7.6) |
| 391 | 100 mm dia (18.7.7) |
| 392 | 150 mm dia (18.7.8) |
| 393 | 200 mm dia (18.7.9) |
| 394 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. DSR 2022 SI No 18.6.2 |
| 395 | 150 mm dia (18.6.2) |
| 396 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS884 complete with the followingas required. 20mm nominal internal diawater hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20mm nominal internal dia gunmetal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25mm dia stopgunmetal valve & M.S. Pipe and socket.t. DSR No 18.17:1 |
| 397 | Supplying and fixing single headed internal/External hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :as per DSR 2022 S.I. No. 18. 9.1 & 18.10.1 Single Handed Gunmetal |
| 398 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : DSR 2022 SI No. 18.18.1 |
| 399 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : DSR 2022 SI.No.18.16.1 Gun metal |
| 400 | Providing/fixing of Weather proof standard fire hose cabinet (900 mm X 600 mm X 450 mm) Outdoor type made of not les thad 16/18 SWGMS sheet having glassed hinged door (5 mm thick glass ) including necessary locking arrangement with handle for housing hydrant valve, two nos. 15 meter long fire hose pipes , branch pipe as required as per drawings. including brackets for mounting accessories , painting ( one coat primer and two coat of fire red color). The cabined shall be mounted on self standing mounting type painted MS Angle iron frame as required . the words \\"FIRE HOSE\\" to be painted on the box MR |
| 401 | Supplying Installation testing & Commissioning of 25 mm Ball valve PN -1 gunmental as per IS:778 including necessary accessories and connections. MR |
| 402 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 403 | 2 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.1 |
| 404 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 405 | 4 way - 100 mm dia M.S. Pipe DSR 2022 SI No. 18.19.2 |
| 406 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. DSR 2022 SI No. 18.20 |
| 407 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.. 450 Lpm at 35 m Head DSR 2022 SI No. 18.4.2 |
| 408 | PUMP ROOM |
| 409 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainlesssteel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-325. supply , Installation, testing and commissioning of fire Hydrant valve , bearing to IS:5290 marks, S.S. ,IS: 304 Grade, 63mm oblique instantaneous single out let, 75mm N.B. flanged inlet, brass spindles complete with PVC blank cap . G.I. chain etc. guard,foundation bolts etc.as required. supply , Installation, testing and commissioning of Branch pipe . S.S. short type with 63mm male instantaneous inlet, male threaded outlet fitted with 15mm, Bore nozzle,having IS: 903 with anti vibration pads. |
| 410 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.1.8 |
| 411 | P/F weather proof standard fire hose cabinet locing arrangement with handle for housing hydrant valve two nos. 15 mts. Long fire hose pipes, branch pipes as reqd. as per drawing , including bracket for mounting accessories, painting (one coat primer and two coat of fire red color ) the cabinet shall be mounted on self standing mounted type painted M.S. angle iron frame as reqd. diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven supply , Installation, testing and commissioning of 25mm air release valve gunmetal, conforming to IS: 903:1993, having rubber ball and with 25mm BSP. THREADED male inlet including necessory accessories Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 412 | 1620 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.2.8 |
| 413 | A) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump)(B) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS: 1520.(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS: 325.(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 414 | 180 LPM 70 MTR HEAD As Per DSR 2022 Si no. 18.3.2 |
| 415 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with. |
| 416 | INCOMING |
| 417 | Incomings |
| 418 | 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500A |
| 419 | Outgoings |
| 420 | ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 421 | Main Fire Pump |
| 422 | 160 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 423 | Jockey Pump |
| 424 | 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 425 | Diesel Engine Control |
| 426 | Control for diesel engine comprising - |
| 427 | Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. DSR 2022 SI no. 18.5.2 |
| 428 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of :a) One 63 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA.b)One Volt meter (0-500 V) with selector switch.c) One set including lamps. (MR) |
| 429 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. DSR SI No.18.22 |
| 430 | Providing & fixing of Flow switch in Following sizes in M.S. pipe line including connection etc. as required. DSR SI No.18. 23150 mm Dia. |
| 431 | Providing and fixing in position the industrial type pressure gauges with gun metal/brass valves complete as required DSR-2022 SI No. 16.8 |
| 432 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. DSR 2022 SI no. 18.13 |
| 433 | Providing, installation, testing and commissioning of stainless steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. DSR 2022 Sl No 18.15 |
| 434 | 100 mm dia (18.15.2) |
| 435 | 150 mm dia (18.15.3) |
| 436 | 200 mm dia (18.15.4) |
| 437 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : DSR 2022 SI No 18.11 |
| 438 | 80 mm dia (18.11.4) |
| 439 | 100 mm dia (18.11.5) |
| 440 | 150 mm dia (18.11.6) |
| 441 | 200 mm dia (18.11.7) |
| 442 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : DSR 2022 SI No. 18.14 |
| 443 | 80 mm dia (18.14.4) |
| 444 | 100 mm dia (18.14.5) |
| 445 | 150 mm dia (18.14.7) |
| 446 | Providing, fixing Testing &commissioning of 15mm dia quartzoid bulb type sprinkler of rating 68 degree centigrade with required accessories DSR 2022 SI No. 18.21 |
| 447 | Pendent Type(18.21.1) |
| 448 | Upright Sprinkler (18.21.2) |
| 449 | Providing, installation, testing and commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed of FM approved complete as required. DSR 2022 SI No. 18.29 |
| 450 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. DSR 2022 Sl. No. 18.25 |
| 451 | 700 mm (18.25.1) |
| 452 | 1000 mm (18.25.2) |
| 453 | Providing/Fixing Fire man axe. Make. (MR) |
| 454 | Providing, fixing, testing & commissioning of resilient rubber lined single Arch Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 (MR) |
| 455 | 150 mm dia |
| 456 | FIRE EXTINGUISHERS |
| 457 | Supply and fixingof C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1132 |
| 458 | Supply and fixingof fire extinguisher,ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labourfor proper completionof work.PWD SOR 2018 SI No 1131(A) |
| 459 | Fire Alarm SystemWork |
| 460 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. DSR 2022 SI No 17.2.1.2 |
| 461 | Two Loop Panel. |
| 462 | Supplying, installation, testing and commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required. DSR 2022 SI No 17.2.4 |
| 463 | Supplying, installation, testing and commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. DSR 2022 SI No 17.2.5 |
| 464 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. DSR 2022 SI No 17.2.11 |
| 465 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. DSR 2022 SI No 17.2.14 |
| 466 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. DSR 2022 SI No 17.2.15 |
| 467 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. DSR 2022 SI No 17.2.10 |
| 468 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. DSR 2022 SI No 17.2.7 |
| 469 | Supply, Installation and commissioning of Annunciator Panel with 7 windows with point, zone & system status used. (MR) |
| 470 | Supply Installation wire for annunciator panel ,(3 core 1.5 sqmm) MR |
| 471 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset ackowledge and silence switches complete as required.DSR 2022 SI No 17.2.3 |
| 472 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required DSR-2022 SI.No.17.3.1 |
| 473 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.DSR-2022 SI.No.17.3.3 |
| 474 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.DSR-2022 SI.No.17.3.6 |
| 475 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.DSR-2022 SI.No.17.3.9 |
| 476 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.. DSR 2022 SI NO. 17.5.2 |
| 477 | Armoured Cables (Cable/Gland/Lug) : |
| 478 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PWD SOR 2024 SI No (20a.1) |
| 479 | 16 Sqmm 4 Core |
| 480 | 35 Sqmm 3.5 Core |
| 481 | 70 Sqmm 3.5 Core |
| 482 | 95 Sqmm 3.5 Core |
| 483 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. PWD SOR 2018 SI No 503 |
| 484 | 16 Sqmm 4 Core |
| 485 | 35 Sqmm 3.5 Core |
| 486 | 70 Sqmm 3.5 Core |
| 487 | 95 Sqmm 3.5 Core |
| 488 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of the Engineer incharge.PWD SOR 2018 SI No 504 |
| 489 | 16 Sqmm |
| 490 | 35 Sqmm |
| 491 | 70 Sqmm |
| 492 | 95 Sqmm |
| 493 | Earthing Work |
| 494 | Supply and burying of Safe Earthing Electrod T-19 Zn-Zinc Coated,Length 3000mm,outer pipe 48.4mmx3.2mm,inner pipe 26.9mm x 2.6 mm,terminal Dia 12mm,coating 80-100 micron filled with crystalline conductive mixture (CCm) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing.(From electrode terminal to switch board,cost of 25x3 G.I. Strip will be extra) Make : As approved in U.P.P.W.D. & C.P.R.I. Certified. SOR 2018 Sl No 726 B |
| 495 | Supply and laying of 25mm x 3 mm G.I. strip from earth electrode directly in the ground as required complete in all respects. SOR 2018 Sl No 716 |
| 496 | Fire Sand Bucket |
| 497 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. SOR 2018 Sl No 1133 |
| 498 | Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules SOR 2018 Sl No 1136 |
| 499 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. DSR 2022 Sl No. 4.6 |
| 500 | 150 mm width X 50 mm depth X 1.6 mm thickness (4.6.2) |
| 501 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve,with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : (With common burnt clay F.P.S.(non modular) bricks of class designation 7.5) CIVIL DSR 2023 Sl No. 18.33.1 |
| 502 | Providing & Fixing of 1.6 mm thick M.S/Door Frame, Door capable of accommodating fire Hose Reel, Landing Valve, Hose Pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making Recessed type mansoary box (by civil contractor). (MR) |
| 503 | 1500x900 mm (Indoor Cabinet) Only Frame |
| 504 | Supply and fixing of self glow type exit sinage. (LED Type) (MR) |
| 505 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Civil DSR 2023 si no. 18.48 |
| 506 | Providing & laying pipe of required dia including cutting the road & surface dressing complete in all respect as directed by E/I. MR |
| 507 | Construction of 100 Kl.underground water tank with pump house |
| 508 | densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of size 595x595 mm of approved texture, design and pattern as per CPWD specification 2019, to be laid in true horizontal level suspended on interlocking medal T-Grid of hot galvanised iron section of 0.33 mm thick(galvanised @ 120 gram per sqm including both sides) comprising of main-T runner of size 24x38 mm of length 3000mm cross-T of size24x32 mm of length 1200 mm and secondary intermediate cross T of size 24x32 mm of length 600 mm to formgrid module of size (600x600 mm, suspended from ceiling using galvanised steel items (galvanising@80 gram per sqm) i.e 12x50 mm long dash fastener, 6 mm dia fully threaded hanger rod upto 1000 mm length and L shape level adjuster of size 72x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6 mm thick of precut hole on both 25 mm flanze to pierce into 12x50mm or even bigger size dash fastener if required, fixed with galvanised iron perimeter wall angle or size 24x24x0.4 mm of length 3000 mm to be fixed on periphery wall/partition with the help of plastic rawl plug at 450 mm centre to centre and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing as per direction of engineer in charge With 15 mm Tegular edged light weight calcium silicate false ceiling tiles Civil DSR 2023 26.22.1 |
| 509 | Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by E/I with in a distance of 60 meters. MR |
| 510 | 25 mm dia (9\\") |
| 511 | 32 mm dia (9\\") |
| 512 | 50 mm dia (9\\") |
| 513 | 80 mm dia (9\\") |
| 514 | 100 mm dia (9\\") |
| 515 | 150 mm dia (9\\") |
| 516 | Grouting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by E/I MR |
| 517 | 25 mm dia |
| 518 | 32 mm dia |
| 519 | 50 mm dia |
| 520 | 80 mm dia |
| 521 | 100 mm dia |
| 522 | 150 mm dia Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail