| 1 | HYDRANT SYSTEMSupplying, installation testing and commissioning of the following-: ‘C’ class GI Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/SAIL/JINDAL150mm nominal dia |
| 2 | 80mm nominal dia |
| 3 | 25mm nominal dia |
| 4 | Providing and fixing Single headed hydrant having outlet of 63 mm dia (2.1/2”) N.B. hydrant (IS:5290) landing valve in Stainless Steel Morris Pattern instanteous coupling type TAC / LFA approved & ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc.Make-Minimax/Newage/Fireshield/Safex (External+internal hydrant) |
| 5 | Providing and fixing GI standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:.Make-Minimax/Newage/Fireshield/Safex |
| 6 | Providing and fixing TAC approved fire hose cabinet to house fire hydrant & hose, including all other related accerrories fabricated from GI sheet (2mm thick) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 nos. hoses. The hose box size is 750 mm x 600 mm x 300 mm |
| 7 | Providing & fixing 63mm dia RRL hose pipe a 15 mtr length per IS 636 TYPE A TAC/ LFA approved of standard length of approved pattern and size including gun metal male and female Coupling duly bound with copper wire etc. complete.Make-Minimax/Newage/Fireshield/Safex |
| 8 | Supplying & fixing first aid fire hose reel of thermoplast braided suitably reinforced 20 mm size & 30 m standard length with 5 mm tapering branch nozzle, 25mm dia. Pipe to connect to riser with cut off ball valve attachment. Hose to be swinging type wall mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts (Including drum and swivel arrangement) etc complete..Make-Minimax/Newage/Fireshield/Safex |
| 9 | Supplying, installing and commissioning of fire brigade inlet connection of 4 way with each of 63 mm dia. built - in Gun metal instantaneous coupling type arranged on 150 mm dia. Make-Minimax/Newage/Fireshield/Safex |
| 10 | Supply and installation, testing and commissioning of CI Butterfly valves ( heavy ) conforming to BS 5155 ,PN1.6 tested to 1.5 times working pressure with necessary companion flanges, bolts, nuts, gasket packing, support and any other spares, including indicator for open and shut position as per fire practice etc complete..Make-Zoloto/Audco/Leader150 mm |
| 11 | Supplying and fixing approved make of 25mm dia automatic air release valve spring loaded type complete with unions etc. complete. |
| 12 | AUTOMATIC SPRINKLER SYSTEM Supplying, installation testing and commissioning of the following-: ‘C’ class GI Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pipe coat (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.Make-TATA/SAIL/JINDAL150mm nominal dia |
| 13 | 100mm nominal dia |
| 14 | 80mm nominal dia |
| 15 | 65mm nominal dia |
| 16 | 50mm nominal dia |
| 17 | 40mm nominal dia |
| 18 | 32mm nominal dia |
| 19 | 25mm nominal dia |
| 20 | Supply and installation, testing and commissioning of CI Butterfly valves ( heavy ) conforming to BS 5155 ,PN1.6 tested to 1.5 times working pressure with necessary companion flanges, bolts, nuts, gasket packing, support and any other spares, including indicator for open and shut position as per fire practice etc complete..Make-Zoloto/Audco/Leader150mm nominal dia |
| 21 | 50mm nominal dia |
| 22 | Supplying, installing, testing and commissioning of conventional Sprinkler quartzoid bulb type with 15mm screwed end connection of 68 deg. C. temperature rating, K 80 and orifice shall not be less than 12.7mm.Sprinklers shall be UL Listed / FM approved with Chrome finished.Make-Tyco/HD/ViakingPendent sprinkler |
| 23 | Sidewall sprinkler |
| 24 | Supplying, installing, testing and commissioning of hydralically operated Sprinkler control valve complete with water motor gong bell, basic trims as required, pressure gauges, pressure switch, drain valves, ball valves etc. complete. Alarm valve shall be UL Listed / FM approved.Make-system sensor/siemens150mm dia. |
| 25 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader 150 mm nominal dia |
| 26 | Providing and fixing of Stainless steel corrugated flexible pipe(hose) for dropping sprinklers below false ceiling, pipe shall be 16 bar pressure rating and 1000 mm long 25 mm dia with union / reducer collar, clamps etc. as required. Make-Tyco/HD/Viaking |
| 27 | Supplying, installing, testing and commissioning of UL/EN approved sight glass unit with required size orifice plate, test valve, and complete accessories like tees,elbows flanges etc.as per the tender drawing. Make-Zoloto/Audco/Leader/Newage |
| 28 | Providing and fixing of electric flow switch with mechanical time delay feature capable of sensing a minimum of flow of one sprinkler , including making electrical cable termination through input module & integrated with Fire Alarm System.Make-Honeywell/eq. |
| 29 | AUTOMATIC FIRE DETECTION AND ALARM SYSTEMFire detection system-Supply, installing, testing and commissioning of of 2 Loop Network Panel Micro processor based 2 wire fault tolerant loop,with inbuilt network port (each loop accessing 99 or more detectors and 99 or more modules ) fire alarm/detection control panel. The Panel shall have 10000 or more event log history . Panel shall be capable of having 1600 or more configurable zones .The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module when ever any alarm is triggered. The panel shall have 7 Inch Touch Screen unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects.The Panel Shallbe Sheet Steel Painted, selaed to IP30. The Panel Shall have provision for 40 or more Zones with Individual LED Indicators expdable upto 200 Zones or higher. The panel shall have a built in power supply and battery charger along with maintenance free 7 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required.and as per specifications. conforming to BS5839 Standards and Duly Approved by EN54 The panel shall support detection logics like coincidence & verification detections for the false alarm management. The Panel shall adjust the sensitivity between day and night to maintain the better detection/reponse time. The Panel shall be capabale of programming through PC ; Touch Screen of USB .This panel having facility of MODBUS protocol over TCP/IP for BMS integration.The panel should have provision for inbuilt RJ45 connection terminal for connecting to the LAN with inbuilt BACNET Protocol. Make- Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 30 | Supplying, installing, testing and commissioning of OEM make ( 2 loop )Cloud based service through universal gateway, which shall be enabled through internet. Remote health monitoring solution shall utilize cloud-based software-as-a-service web application & supplementary network gateway hardware. System shall provide secure web access to cloud-based web application using any of the web browsers like Google Chrome (preferable), Internet Explorer etc. from any computer/ tablet/ smartphone connected over internet via defined credentials – username and password. It shall also have the facility to monitor the cloud service over the mobile apps. The cloud-based web application shall capture all fire alarm system data points as received from the system via supplementary gateway hardware of the same make as Fire Alarm Panel. The software shall display real time view of fire system effectiveness, multi-location unified view, custom dashboard, device level information, scheduled reporting, e-mail of critical alarms. The cloud service shall be capable of monitoring 250000 datapoints scattered across multiple install bases spread across multiple geographical locations. The Gateway Card shall be UL Listed.It should have 5 nos. or more user license. Internet/Wi-Fi Connectivity Required.The cost is inclusive of 2 years subscription charges.Software and panel shall be of same make. |
| 31 | Supplying, installing, testing and commissioning of addressable Manual call point with built in Monitor Module with all accessories complete. The device shall be UL/EN/FM approved..Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 32 | Supplying, installing, testing and commissioning of addressable Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 33 | Supplying, installing, testing and commissioning of adressable multi sense smoke detector with inbuilt isolator module/isolator base,base, junction box and other accessories.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 34 | Supplying, installing, testing and commissioning of rate of rise heat detector with inbuilt isolator module/isolator base,base, junction box and other accessories.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 35 | Supplying, installation, testing & commissioning of addressable fire control module complete as required.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 36 | Supply and fixing of response indicator for all the detectors above false ceiling. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |
| 37 | Supply and fixing of response indicator for all the detectors above false ceiling. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |