| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group - C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 2 x 10 sq.mm + 1 x 6 sq.mm. earth wire |
| 8 | 2 x 16 sq.mm + 1 x 6 sq.mm. earth wire |
| 9 | 4 x 10 sq.mm + 2 x 6 sq.mm. earth wire |
| 10 | 4 x 16 sq.mm + 2 x 6 sq.mm. earth wire |
| 11 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 12 | 3 x 1.5 sq. mm |
| 13 | 3 x 2.5 sq. mm |
| 14 | 3 x 4 sq. mm |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 17 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required |
| 18 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 19 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 20 | 5/6 A switch |
| 21 | 3 pin 5/6 A socket outlet |
| 22 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 23 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 24 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 25 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 26 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 27 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required |
| 28 | Upto 450 mm sweep |
| 29 | Extra for fixing the Louvers/ shutters complete with frame for exhaust fans of all sizes. |
| 30 | Supply of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 4000K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.9. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 21W (including driver). Make:- Philips, Havells, Wipro or EQ. |
| 31 | Supplying of Bulkhead type light fitting complete with, wire guard, holder, electronic ballast 1 x 10 W lamp including connections etc. |
| 32 | Supply of 9W to 15 W 3 Star LED Wall Light Blub complete in all respect. |
| 33 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan |
| 34 | Supplying of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required. .Make:- Bajaj, Havells or EQ. |
| 35 | 300mm EXHAUST FAN |
| 36 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 40Watt. to 45 Watt and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 4000-5000 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70,fitting itself suitable for 60-65mm OD pipe |
| 37 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. Make :- L&T, Legrand, Havells or Eq. |
| 38 | 63 A,25KA,FP MCCB |
| 39 | 100 A,30KA,FPMCCB |
| 40 | Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 41 | 8 way, Double door |
| 42 | 12 way, Double Door |
| 43 | Supplying and fixing following way surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.(Note : Vertical type MCB TP DB is normally used where 3 phase outlet are required.) |
| 44 | 4 way , (4+12) Double door |
| 45 | 8 way (4 + 24), Double door |
| 46 | Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 47 | 40 amps SP MCB |
| 48 | 63 amps SP MCB |
| 49 | Supplying and fixing following rating, Double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 50 | 40 amps |
| 51 | 63 amps |
| 52 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 53 | Single pole |
| 54 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 55 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 56 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required |
| 57 | Supply installation testing and commissioning of LT panel Board for the extension of existing panel as per the following specification with proper copper earthing as recommended. The panel should be Designed as per the latest standard IEC 61439. The panel should have Bus bar clearance of 25 mm for Ph to Ph and 19 mm for Ph to neutral, Zero Stray voltage doors and panels, polyester glass support for insulation. The cable alleys should be 300 mm wide and it should be fitted with hinged door that open up to and angle of 95 Deg. The provision of cable entry should be from Bottom. The IP protection of panel should be IP-42 for external and IP2X for internal with 3B as Form of separation. The panel should be equipped with suitable size of CT and display meter for VAF measurement. The panel should be suitable for seismic zone V. Make of panel: L&T (Ti), ABB (ArtuK), Schneider (OkEN) |
| 58 | LT Outgoing should be IP 54 and should have switchgears as below. Make of LV switchgear : L&T (Lauritz & Knudsen), Schneider or Siemens. |
| 59 | Building Main LT Panel |
| 60 | INCOMER:- |
| 61 | 1 No 160 Amp. 4P MCCB of 25KA (Ics=Icu) Breaking Capacity |
| 62 | 1 No 63 Amp. 4P MCCB of 25KA (Ics=Icu) Breaking Capacity |
| 63 | 1 No 160 Amp. 3P Contractor |
| 64 | 1 No 63 Amp. 3P Contractor |
| 65 | 2 No. Multi Function Meter. |
| 66 | 2 Set of phase indicating lamps with Single Pole MCB. |
| 67 | 2 Set of ON / OFF indicating lamps with Single Pole MCB. |
| 68 | BUS BARS:- |
| 69 | 250 Amps. TP&N aluminium bus bars |
| 70 | OUT GOINGS:- |
| 71 | 2 Nos. 100 Amps. FP MCCB |
| 72 | 1 Nos. 63 Amps. FP MCCB |
| 73 | 2 Nos. 40 Amps. 4P MCCB |
| 74 | 3 Nos. 32 Amps. DP MCB |
| 75 | 2 Nos. Space & Spare |
| 76 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each |
| 77 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. |
| 78 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 79 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 80 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 81 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 82 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 83 | Above 95 sq.mm. and upto 185 sq.mm. |
| 84 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required |
| 85 | Up to 35 sq.mm. |
| 86 | Above 95 sq.mm. and upto 185 sq.mm. |
| 87 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required |
| 88 | Upto 35 sq. mm (clamped with 1mm thick saddle |
| 89 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp |
| 90 | Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment |
| 91 | 3.5 x 185 sq.mm |
| 92 | 3 x 4 sq.mm, |
| 93 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required. |
| 94 | 2 X 6 sq. mm (19mm) |
| 95 | 3½ X 185 sq. mm (57mm) |
| 96 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. |
| 97 | 100mm dia |
| 98 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 99 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 100 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 101 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 102 | 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 103 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 104 | 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 105 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 106 | 100 mm wide x 50 mm depth x 1.6 mm thickness. |
| 107 | SITC of 25 Ltr. Glass line Geyser with all accessories Make- Havells/Bajaj or Eq |
| 108 | Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- |
| 109 | a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. |
| 110 | b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate ACPower with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. |
| 111 | c) Data Monitoring System complete with accessories. |
| 112 | d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugsand other accessories etc. as required. |
| 113 | e) Lightning and surge voltage protection. |
| 114 | f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required. |
| 115 | SUB-HEAD -X- EPABX & LAN SYSTEM |
| 116 | Supplying, drawing, connecting and testing of 0.5 mm dia annealed copper conductor PVC insulated PVC sheathed telephone wire in existing conduit/wire way duct etc. as required of following sizes: |
| 117 | 2 Pair (4 core) |
| 118 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required |
| 119 | 1 or 2 Module (75mmX75mm) |
| 120 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Make:- Polycab, Havells, L&T or Eq |
| 121 | Telephone socket outlet |
| 122 | TV antenna socket outlet |
| 123 | RJ-45 Data Socket outlet |
| 124 | Supply and Installation of telephone Patch cord 1.5 meter . Make- Singhtel,Panasonic,Alcatel |
| 125 | Supply and Installation of CLI based push button telephone set.Make- Singhtel,Panasonic,Alcatel |
| 126 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.1 run of cable |
| 127 | SITC of UTP CAT 6 UTP Patch Cord 3 Mtr.Make- RIT/Schinder/R & M/Comrax |
| 128 | Providing, laying, connecting and testing of unarmoured TV cable RG-6 PVC insulated cable along wall or ceiling or through existing pipe. |
| 129 | Supply and Fixing of 25 mm Sizes of Medium class PVC conduit along with accessories in surface /recess including cutting the wall and making good thw same in case of recessed conduit as requried.Make-Polycab/AKG |
| 130 | SUBHEAD - XI: EXTERNAL LIGHTING |
| 131 | Supply and fixing of hot dip galvanised steel OCTAGONAL POLE, Height=7m, Top OAF= 70 mm, Bottom OAF-130, Thickness - 3 mm,Base Plate - 220x220x12 mm , PCD - 220 mm. |
| 132 | Supply and fixing of foundation accessories for 7 mtr pole set-Each set consists of 4 nos. of M20x700 J bolts plus 10% templates |
| 133 | Supply and fixing of 1000 mm Galvanized SINGLE Arm bracket , Standarad Type made of 48.3/32 mm OD pipe |
| 134 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 40Watt. and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 4000-5000 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70. |
| 135 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 136 | Above 4.5 metre and upto 6.5 metre |
| 137 | Supplying, installation, testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 138 | 1 output per phase and suitable for single phase supply |
| 139 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 140 | Single pole |
| 141 | Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required |
| 142 | 32 mm dia |
| 143 | SUB HEAD-XII: FIRE FIGHTING WORKS |
| 144 | Excavating trenches of required width for pipes cables etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m ncluding getting out the excavated soil , and then returning the soil as required , in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed , within a lead of 50 m. |
| 145 | Pipes, cables etc. exceeding 80 mm dia . But not exceeding 300mm dia. |
| 146 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 147 | 100 mm nominal bore (pipe in pump room & pump room to FFTG shaft) |
| 148 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904as required : |
| 149 | 2 way - 100 mm dia M.S. Pipe |
| 150 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in allrespects, as required: (Terrace Pump) |
| 151 | (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 |
| 152 | b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 153 | (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
| 154 | (d) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 155 | 450 lpm at 35 m Head |
| 156 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. (for terrace booster pump) |
| 157 | Providing and fixing in position the industrial type pressuregauges with gun metal / brass valves complete as required (for terrace booster pump) |
| 158 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 159 | 100 mm dia. |
| 160 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 161 | 100 mm dia. |
| 162 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 163 | 80 mm nominal bore |
| 164 | 100 mm nominal bore |
| 165 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 166 | Single headed Gunmetal |
| 167 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. |
| 168 | 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 |
| 169 | 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 170 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 171 | Gun metal |
| 172 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : |
| 173 | Gun metal |
| 174 | Providing and fixing standard fire mans axe with heavy duty insulated rubber handle. |
| 175 | Providing of FHC Door made of 16 gauge MS Sheet with frame of size 105x70mm complete door and frame assembly including all hardwares (Concealed Flush handle,Allen Key Lock, MS Hinges, 5mm Thick Float glass) & accesories . The door to be painted with fire resistance paint. The scope shall also include the painting of the frame with the same paint as the shutter or complete as per direction of Engineer-in-charge.(Approx. size of door: 900mm Wide & 1500mm Height) |
| 176 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 177 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 178 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 179 | Providing, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as described below: |
| 180 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 181 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 182 | Providing and fixing Fire related signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects as directed by Engineer-in-charge. |
| 183 | Fabricating & Supply, installing, testing and commissioning of sheet steel clad floor mounting control panel having suitable size for control of 1 nos. booster pumps 5.5 KW/7.5HP each having suitable incoming MCCB, incoming voltmeter with selector switch and fuses. DOL Starter with hand reset overload cum single phase preventor type relay, Ammeters to read current in any one phase, alarm with reset push button which will automatically reset for the next cycle. (As per the Technical Specifications) (At Terrace floor) |
| 184 | Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 185 | 150 mm width x 50mm depth x 1.6 mm thickness. |
| 186 | Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment |
| 187 | 3 x 4 sq.mm, Please Enable Macros to View BoQ information |