| 1 | BUILDINGS & STRUCTURE (Sch 'A' PART-I) |
| 2 | Lump sum price worked out by the Contractor for “BUILDINGS & STRUCTURE” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 15,16,00000.00 inserted by the MES in Schedule ‘A’ Part-I. |
| 3 | EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT (Sch 'A' PART-II) |
| 4 | Lump sum price worked out by the Contractor for “EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 50,82,870.91 inserted by the MES in Schedule ‘A’ Part-II. |
| 5 | INTERNAL WATER SUPPLY (Sch 'A' PART-III) |
| 6 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 55,41,073.26 inserted by the MES in Schedule ‘A’ Part-III. |
| 7 | INTERNAL ELECTRIFICATION (Sch 'A' PART-IV) |
| 8 | Lump sum price worked out by the Contractor for “(INTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.1,62,62,016.68 inserted by the MES in Schedule ‘A’ Part-IV. |
| 9 | ROAD, PATH, CULVERT & HARDSTANDING (Sch 'A' PART-V) |
| 10 | Lump sum price worked out by the Contractor for “(ROAD, PATH, CULVERT & HARDSTANDING)” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.1,02,82,748.25 inserted by the MES in Schedule ‘A’ Part-V. |
| 11 | SEWAGE DISPOSAL (Sch 'A' PART-VI) |
| 12 | Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 12,50,723.45 inserted by the MES in Schedule ‘A’ Part-VI. |
| 13 | AREA DRAINAGE (Sch 'A' Part-VII) |
| 14 | Lump sum price worked out by the Contractor for “(AREA DRAINAGE)” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.2014304.67 inserted by the MES in Schedule ‘A’ Part-VII. |
| 15 | EXTERNAL WATER SUPPLY (Sch 'A' Part-VIII) |
| 16 | Lump sum price worked out by the Contractor for “(EXTERNAL WATER SUPPLY)” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.6,10,893.52 inserted by the MES in Schedule ‘A’ Part-VIII. |
| 17 | LIFT (Sch 'A' Part-IX) |
| 18 | Lump sum price worked out by the Contractor for “(LIFT)” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,74,66,035.48 inserted by the MES in Schedule ‘A’ Part-IX |
| 19 | DG SET (Sch 'A' Part-X) |
| 20 | Lump sum price worked out by the Contractor for “DG SET” as listed in Schedule ‘A’ Part-X. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,21,166.40 inserted by the MES in Schedule ‘A’ Part-X. |
| 21 | FIRE FIGHTING (Sch 'A' Part-XI) |
| 22 | Lump sum price worked out by the Contractor for “(FIRE FIGHTING)” as listed in Schedule ‘A’ Part-XI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 20,43,614.00 inserted by the MES in Schedule ‘A’ Part-XI. |
| 23 | EXTERNAL ELECTRIC SUPPLY (Sch 'A' Part-XII) |
| 24 | Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part-XII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.1,81,09,218.93 inserted by the MES in Schedule ‘A’ Part-XII. |
| 25 | FENCING & GATE (Sch 'A' Part-XIII) |
| 26 | Lump sum price worked out by the Contractor for “FENCING & GATE” as listed in Schedule ‘A’ Part-XIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.3,40,109.82 inserted by the MES in Schedule ‘A’ Part-XIII. |
| 27 | LIGHTNING PROTECHTION AND OBSTRACTION OF LIGHT (Sch 'A' Part-XIV) |
| 28 | Lump sum price worked out by the Contractor for “(LIGHTNING PROTECHTION AND OBSTRACTION OF LIGHT” as listed in Schedule ‘A’ Part-XIV Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,32,204.10 inserted by the MES in Schedule ‘A’ Part-XIV. |
| 29 | MISCELLANEOUS ITEMS REQUIRED FOR B/R & E/M SERVICES (Sch 'A' Part-XV) |
| 30 | Internal Water Supply:18S/F 15mm bore 2way Bib taps with wall flange, cast copper alloy with crutch or butterfly handle, screwed for iron pipe or for brass ferrule complete all as specified |
| 31 | S/F 15mm bore Brass CP wall mixer with provision for overhead shower system for mixing hot & cold water screwed for iron pipe complete all as specified |
| 32 | S/F 15mm bore Brass CP centre hole wash basin/sink mixer complete all as specified. |
| 33 | INTERNAL ELECTRIFICATION: Supplying and fixing of Modular type TV Co-axial socket (RJ-9) outlet-1 Module in the modular MS / GI sheet box and cover plate including concealed 40mm PVC conduit in wall/ceiling/fixed to roof, connections etc complete all as specified and as directed |
| 34 | Supplying and fixing of Modular type RJ-11 telephone socket outlet in the modular MS/GI sheet box and cover plate including concealed 25 mm PVC conduit in wall/ceiling/fixed to roof, connections etc complete all as specified and as directed |
| 35 | S & F Decorative wall light fixture made up of high grade engineering plastic material suitable for 9W/10W LED Lamp B22 base including connecting up with twin core twisted flexible copper conductor cable with suitable size, 230V, 50Hz, complete all as specified and directed. |
| 36 | Supply and fix 10 watt LED bulb, complete all as specified and directed. |
| 37 | Fabrication, supply & fixing of Gl pipe bracket up to 32 mm dia- 0.9m long & 2 set of clamps made out of 30x5mm MS flat & fixed with anchor bolt suitable for 1x35W LED security light fitting complete all as specified and directed |
| 38 | S & F DB with sheet metal enclosure 240 volts, 6 way Single phase double door with copper bus bar neutral link, earth link, earthing studs, without MCBs complete all as specified and directed |
| 39 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-182 LT Panel (MLTP, Offrs Bldg), indoor type LT Panel Box by CPRI Approved manufacturer of size 1650mm (H) x 1300mm (L) X 3750MM(D) With comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 500Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed |
| 40 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps (LED) - 03 No. |
| 41 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete all as specified and directed. |
| 42 | Incoming complete all as specified and directed;(a) MCCB 400Amp, 36kA, rating 415 Volts, 4pole-01 NoOutgoing complete all as specified and directed.(b) MCCB FP 400 Amp, 36 KA- 02No.(b)MCCB FP 16 Amp, 16 KA- 04No.(c) Multi-functional Meter CL. 1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection-01 Set.(e) 500/5A CT CL.1.0,10VA (f)Misc electrical assessories ( wires, sockets, terminals, channels, nuts, and bolts etc). |
| 43 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-182 LT Panel (Main DB Panel, Offrs' Bldg), indoor type LT Panel Box by CPRI Approved manufacturers of size 1400MM (H) X 1200MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 400Amp rated, 32kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. Item Contd as 16.15 to 16.17 |
| 44 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Panel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps (LED) - 03 No. |
| 45 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete. |
| 46 | Incoming complete all as specified and directed;(a) MCCB 320Amp, 415V, 50Hz, 36kA, 4P-01 NoOutgoing complete all as specified and directed.(8) MCB 32 Amp, 415V, 50Hz, 10kA, 4P-21 Nos(b) Housing for 3-Phase Energy Meter, 10-60Amp-20 Nos(c) Multi-functional Meter CL. 1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection-01 Set.(e) 400/5A CT CL.1.0,10VA (f)Misc electrical assessories ( wires, sockets, terminals, channels, nuts, and bolts etc). |
| 47 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-182 LT Panel (MLTP, JCOs Bldg), indoor type LT Panel Box by CPRI Approved manufacturers of size 1650MM (H) X 1200MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 200Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. |
| 48 | Painting Detais :Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps (LED) - 03 No. |
| 49 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete all as specified and directed. |
| 50 | Incoming complete all as specified and directed;(a) MCCB 160Amp, 25kA, rating 415 Volts,4 pole-01 NoOutgoing complete all as specified and directed,(a) MCCB FP 125 Amp 25 KA-1 No.(b) MCCB FP 16 Amp 16 KA-04 No.(c) Multi-functional Meter CL.1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection-01 Set.(e) 200/5A CT CL.1.0,10VA(f) Misc electrial assessories (wires, sockets, terminals, channels, nuts & Bolts etc). |
| 51 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-182 LT Ea 400 /Panel (Main DB Panel, JCOs Bldg), indoor type LT Panel Box by CPRI Approved manufacturers of size 1200MM (H) X 1050MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 200Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. |
| 52 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps(LED) - 03 No. |
| 53 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete. |
| 54 | Incoming complete all as specified and directed;(a) MCCB 125Amp, 415V, 50Hz, 25kA, 4P-01 NoOutgoing complete all as specified and directed.(a) MCB 40 Amp, 230V, 50Hz, 10kA, 2P-21 Nos(b) Housing for 1-Phase Energy Meter, 10-60Amp-20 Nos(c) Multi-functional Meter CL.1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection - 01 Set.(e) 200/5A CT CL.1.0,10VA(f) Misc electrial assessories (wires, sockets, terminals, channels, nuts & Bolts etc) |
| 55 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-1 & 2 LT panel (Main DB Panel, JCOs Bldg), indoor type LT Panel Box by CPRI Approved manufacturers of size 1650MM (H) X 1850MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 650Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. |
| 56 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps(LED) - 03 No. |
| 57 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete. |
| 58 | Incoming complete all as specified and directed;(a) MCCB 400Amp, 415V, 50Hz, 36kA, 4P-01 NoOutgoing complete all as specified and directed.(a) MCCB 125 Amp, 415V, 50Hz, 25kA, 4P-03 Nos(b) MCCB 16Amp, 415V, 50Hz, 16kA, 4P-04 Nos(c) Multi-functional Meter CL.1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection - 01 Set.(e) 630/5A CT CL.1.0,10VA(f) Misc electrial assessories (wires, sockets, terminals, channels, nuts & Bolts etc) |
| 59 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-1 & 2 LT panel (Main DB Panel, ORs Bldg Side- A), indoor type LT Panel Box by CPRI Approved manufacturers of size 1200MM (H) X 1050MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 200Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. |
| 60 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps(LED) - 03 No. |
| 61 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete. |
| 62 | Incoming complete all as specified and directed;(a) MCCB 125Amp, 415V, 50Hz, 25kA, 4P-01 NoOutgoing complete all as specified and directed.(a) MCB 40Amp, 230V, 50Hz, 10kA, 2P-25 Nos(b) Housing for 1 phase energy meter, 10-60Amp-25 Nos(c) Multi-functional Meter CL.1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection - 01 Set.(e) 200/5A CT CL.1.0,10VA(f) Misc electrial assessories (wires, sockets, terminals, channels, nuts & Bolts etc) |
| 63 | Supply, fixing and commissioning and Design verified as per IS /IEC-61439-1 & 2 LT panel (Main DB Panel, ORRs Bldg Side- B), indoor type LT Panel Box by CPRI Approved manufacturers of size 1200MM (H) X 1050MM (L) X 375MM (D) with comprising of the following and complete all as specified and directed.Fabrication Details:Main frame 2 mm thick CRCA sheet, partition sheets / covers / doors of 1.5 mm thick CRCA sheet, gland plates 1.5 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom for installation, seperate chambers for Main Bus Bars, switch Gears and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for doors and locking arrangements with Aldrops at front and Back complete all as specified and directed.Bus bar details:Material shall be Copper bus bar 200Amp rated, 25kA, 3L+N, sleeving heat shrinkable type, with bus bar sizes for phase of rated capacity and bus bar shall extended type be support of epoxy type insulators for connection, earthing of 40x6 mm GI Flat complete all as specified and directed. |
| 64 | Painting Detais:Painting shall be 7 tank processed powder coated/ epoxy coated shall be a dry finishing process that uses finely ground particles of pigment and resin based polymer that are electrostatically charged and sprayed onto electrically grounded parts complete all as specified and directed.Wiring:Pannel wiring shall be of 2.5 sq mm copper standard with 5A MCB wiring for controll wiring and indication lamps complete all as specified and directed.Accessories for Panel Box:Multi Functional Meters CT/PT programmable with RS 485 communicatio port CL1 with direct acess to basic power and Energy parameters and Indication Lamps(LED) - 03 No. |
| 65 | NOTE: Rate quoted includes for necessary PCC foundation / steel angulars/ channels to LT pannel and includes the cost of all Accessories and switch gears, necessary cable connections with Lugs, washers nut bolts and cable glands as per site requirement complete. |
| 66 | Incoming: (a) MCCB 125Amp, 415V, 50Hz, 25kA, 4P-01 NoOutgoing: (a) MCB 40Amp, 230V, 50Hz, 10kA, 2P-25 Nos(b) Housing for 1 phase energy meter, 10-60Amp-25 Nos(c) Multi-functional Meter CL.1 RS 485-01 No(d) Indicator lamps (R, Y. B) with individual fuse protection - 01 Set.(e) 200/5A CT CL.1.0,10VA(f) Misc electrial assessories (wires, sockets, terminals, channels, nuts & Bolts etc) |
| 67 | ROAD/ PATH/ CULVERT/ HARDSTANDINGS & F Solar studs of size 125 mmx125mmx25mm with shank of 58.80 mm waterpoof, energy saving and eco friendly, made out of solid aluminium alloy shell comprising of solar panel mono crystalline solar 2.4V/0.30 Watt one no., Ni-Mn or Ni-Cd rechargeable battery six nos supper bright LEDS(yellow, blue, green, and white) suitable for working time 50 to 60 hours succesfully after the battery is full charged(Charging time five to six hours/day with solar energy based power supply) with brightness sensitive auto-sensitive auto switch for automatic turn on at night and turn of at day, fixed on existing road surfaces, complete all as specifed and directed. |
| 68 | Supply and fix road stud (100x100x20mm-76 grms) made of ABS materials with two reflector fitted dynamically and designed to bear load up to 25 tonne with impact strength 253 KN of weight 130 gms(approx) and color as approved by GE complete all as directed. |
| 69 | S & F Convex mirror used for traffic control and road safety purpose made for heavy quality glass and weather proof easy to mount convex mirror with stand with 100 mm dia MS Pipe with impact resistance, bright reflection of 100 cm including excavation in post holes with filling of PCC 1:3:6 and removing the debris to premises of MD land complete all as specified and directed |
| 70 | SEWAGE DISPOSALSupply , laying, joining and testing of 150mm internal diameter of double wall corrugated(DWC) high density polyethyline pipe(hdpe) and stiffness classes-8(SN-8) with ISI marked (with CML no) and including all fitting of pipe & 16098-2013 part -2 complete all as specified and directed. |
| 71 | M&L for SRFC factory made manhole cover to manholes cover square/ rectangular/ circular shape for using cover to manholes complete as directed. |
| 72 | EXTERNAL WATER SUPPLYsupply, construction, erection, testing and commissioning of water treatment plant of capacity 10000 GPH to bring down raw water parameters with in drinkable permissible limit comprising of oxidation chamber, ACF, MGF & pressure filter cum Iron removal plant, air compressor with back wash facility, alum mixture, dosing pump, tank and agitator, soda ash dosing pump,, pre and post chlorination dosing pump and tank & agitator complete including connecting all piping work with heavy duty MS pipe of suitable size for filters and CPVC pipe for alum, soda ash and pre and post chlorine plant with all fittings, sulice valves, check valves and non return valves (all butterfly type), gate valves as required on site and as per OEM recommendation. |
| 73 | Supply, fixing, testing and commisioining of Monoblock pump set suitable for 415 V, 3 phase system having discharge capacity 750 LPM at 40 mtr head of 20 HP/15 KW, with chrome steel impeller, electric driven 415 V, TP complete all as per specified and directed. Please Enable Macros to View BoQ information |
| 74 | Supply, fixing, testing and commisioining of Monoblock pump set suitable for 415 V, 3 phase system having discharge capacity 750 LPM at 40 mtr head of 20 HP/15 KW, with chrome steel impeller, electric driven 415 V, TP complete all as per specified and directed. Please Enable Macros to View BoQ information |