| 1 | Lump sum price worked out by the tenderer for “BUILDING WORK\\" as listed in Schedule ‘A’ Part - I |
| 2 | Subtotal |
| 3 | Lump sum price worked out by the tenderer for “AREA DRAINAGE WORKS\\" as listed in Schedule ‘A’ Part -II |
| 4 | Subtotal |
| 5 | Lump sum price worked out by the tenderer for “Fencing works\\" as listed in Schedule ‘A’ Part - III |
| 6 | Subtotal |
| 7 | Lump sum price worked out by the tenderer for “ROAD , PATH & CULVERTS WORKS\\" as listed in Schedule ‘A’ Part - IV |
| 8 | Subtotal |
| 9 | Lump sum price worked out by the tenderer for “Sewage disposal worksY\\" as listed in Schedule ‘A’ Part -V |
| 10 | Subtotal |
| 11 | Lump sum price worked out by the tenderer for “SITE CLEARANCE & DEVELOPMENT, EXCAVATION AND EARTHWORK WORKS\\" as listed in Schedule ‘A’ Part -VI |
| 12 | Subtotal |
| 13 | Lump sum price worked out by the tenderer for “Fire fighting and fire alarm WORKS\\" as listed in Schedule ‘A’ Part -VII |
| 14 | Subtotal |
| 15 | Lump sum price worked out by the tenderer for “LIGHTENING PROTECTION WORKS\\" as listed in Schedule ‘A’ Part -VIII |
| 16 | Subtotal |
| 17 | Lump sum price worked out by the tenderer for “ EXTERNAL WATER SUPPLYWORKS\\" as listed in Schedule ‘A’ Part -IX |
| 18 | Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIC SUPPLY WORKS\\" as listed in Schedule ‘A’ Part -X |
| 19 | Subtotal |
| 20 | Lump sum price worked out by the tenderer for “DEMOLITION AND DISMANTLING WORKS\\" as listed in Schedule ‘A’ Part -XI |
| 21 | Subtotal |
| 22 | Schedule ‘A’ Part -IX MISCELLANEOUS WORKS |
| 23 | M&L for DWCPE (SN8) 150 (OD)/125(ID) mm pipe conforming to IS-16098 complete laid in trenches and jointed alongwith necessary jointing materials etc complete laid complet all as specified. |
| 24 | M&L for DWCPE (SN8) 200 (OD)/175(ID) mm pipe conforming to IS-16098 complete laid in trenches and jointed alongwith necessary jointing materials etc complete laid complet all as specified. |
| 25 | M&L for DWCPE (SN8) 300 (OD)/275(ID) mm pipe conforming to IS-16098 complete laid in trenches and jointed alongwith necessary jointing materials etc complete laid complet all as specified. |
| 26 | Disconnecting and taking up serviceable HT underground cable of any type from the ground, wall, floor etc and resifting the same HT cable complete all as specified and as directed. |
| 27 | Supply, installation, testing and commissioning of distribution net work, 11 kv outdoor compact Sub Station totally factory assembled, consisting of 3 Way (2Nos.Isolators+1No. Breaker))- 1 set. 11KV/433V, 1000 KVA with Oil type transformer, 1 set of LT device as under. Approved Makes - Schneider, Siemens, ABB |
| 28 | MV COMPARTMENT 11 KV, 800A, 25KA/1Sec indoor type non-extensible, SF6 gas insulated Ring Main unit with sealed pressure system criterion in accordance with the IEC: 60298,62271 - 202.IAC category Iac-AFLR .The Switchgear includes the following HV cubicles |
| 29 | The indoor non -extensible SF6 insulated RMU fully motorised consist of 3 Way ((2Nos.Isolators+1No. Breaker) with self powered relay for protection of transformer . Rated for Voltage 12kV, 800A, 25 KA for 1 sec. |
| 30 | Rated voltage should be - 12 KV |
| 31 | Rated power frequenecy voltage - 28 KV |
| 32 | Rated lightening withstand voltage - 75 KV |
| 33 | Rated current for Ring main feeder - 800 amps |
| 34 | Rated current for VCB feeder - 800 amps |
| 35 | Rated short time current - 25 KA / 1sec |
| 36 | Rated short time making current -50 KA |
| 37 | Ambient temp ( 0 deg C to +40 deg C) |
| 38 | Rated internal arc rating - 20 KA for 1 sec for tank and cable box category IAC-AFL |
| 39 | RMU shall be provided with protection CTs rated for 30 / 1amps, class - 10P10 accuracy , 2.5 VA burdan for circuit breaker |
| 40 | The circuit breaker feeder shall be self powered/powered by external source and shall be provided with OC+EF protection for transformer and shall have serial port for communication on modbus protocol. |
| 41 | Dead short Circuit life of VI - 40 no |
| 42 | Transformer (Oil Type) Three phase, Approved Makes- Schneider, Siemens, BHEL, Hitachi |
| 43 | LT switchgear and Transformer should be of same make for better co-ordination and safety. |
| 44 | Standard: IS : 2026, IS 1180 |
| 45 | Vector group : Dyn11 |
| 46 | Rating : 1000 KVA |
| 47 | Cooling System: ONAN |
| 48 | Winding: Copper |
| 49 | Magnetic Core: Prime grade of M4 or better |
| 50 | High voltage : 11KV - 50 Hz |
| 51 | System highest voltage : 12kV at the HV side |
| 52 | H.V. Power Frequency (KV rms): 28 kV |
| 53 | H.V. Impulse withstand voltage (KV peak): 75 kVp |
| 54 | The Losses of Transformer should be as per IS 1180 part 1 Eff level 2 norms |
| 55 | Transformers shall be designed for 110% continuous overfluxing withstand capability |
| 56 | Temperature rise as per IS1180 |
| 57 | OTI & WTI,Pressure relief valve (without auxiliary contacts),Skids,Earthing terminal,Lifting lugs,Rating plate,Dehydrating breather |
| 58 | LV COMPARTMENT The LV compartment with Degree of protection-IP54 designed for a 50 degree C ambient temperature. The panel is modular, dead front, freestanding, floor mounted and comprises the following equipment |
| 59 | 433 V Air Insulated Aluminium busbar having capacity 800A, 50Hz,50KA withstand fault level capacity, MFM - EM6400NG in incomer |
| 60 | Incomer - 2nos - 4 Pole, 800A, Microporcessor based ACB, rated operational voltage of 415V AC, rated insulation voltage of 1000 volts AC, rated impulse voltage of 12kV, 50 KA Icu=Ics=Icw for 1 sec @440V with LSIG Protection, % load indication of each phase display on the release, No-derating upto 50 Degree Celsius and with Inbuilt ZSI feature. (Schneider,Siemens, L&T ) |
| 61 | Inbuilt 350KVAR, APFC Panel |
| 62 | Outdoor Enclosure :- The enclosure shall be made of 2.0 mm thickness Galvanized Sheet Steel tropicalised to meet Indian weather conditions including all the partition sheets & doors.The base of the enclosure shall be of 4.0 mm thickness Hot Dip Galvanized Sheet Steel to ensure rigidity for easy transport & installation. The entire Package Substation shall be Factory Assemble & Factory Fitted. The enclouser shall have IP54 degree of protection for HT & LT switchgear compatment IP34 degree of protection for Transformer compartment. The Enclosure to be tested for Internal Arc fault test to the tune of atleast 21 KA for 1 second A&B, adhering to as per latest IEC 62271-202.The temperature rise test on enclosure for K10class.The enclosure exterior shall be powder coated.Only OEM make of CSS is accetable.The compartment illumination lamp with door operated switch shall be provided for MV & LV comparatment. The encloser, RMU and LV Breaker should be of same make for better co-ordination and services. HT/LT Switchgear should be of same make for better co-ordination. |
| 63 | Supply Install Testing and commissioning of 11 KV, 630 Amps, HT vacuum circuit breaker indoor panel shall be constructed from Aluminium Zinc coated sheet steel of 2mm thickness, for 1 Incomer and 2 outgoing conforming to IEC 62271-200, 25 KA for 1 Sec, LSC2B-PM class front accessed comprising of Indoor Vacuum Circuit Breaker all as specified and directed with Electrical & Mechanical interlock. Enclosed panel shall consisits of following :- (a) 800A continuous ratedelectrolytic copper bus bar, droppers and bus bars should be insulated with full system voltage sleeves (b) VCB shall be of horizontally draw out type . VCB shall have provision of spring Charging Handle, Trip Road and VCB have Rack in & Rack out mechanism. Vacuum circuit breaker should have vacuum bottles of the same manufacturer as of circuit breaker. The Vacuum Bottle should be type tested for 100 full short circuit operations. (c) Motorized spring charging mechanism with integral spring charging handle for manual spring charge.(d) Panel separation with every department like VCB, Metering , Cable Chamber & Bus Bar Chamber (e) Cast resin Current Transformer 11KV, 300-150/5+5A, core 1: class 0.5, 15 VA, Core 2: 5P10, 15 VA with metering and protection core including necessary control wiring & PotentialTransformer 11 kV,Core I : CL 3P,Core II : Cl 0.5,VA Burden : 50 VA OVF 1.9 for 30 Sec. for metering & protection for incomer and outgoing backed by HT & LT MCB's. Line PT should be mounted only in the rear side ( Top or Bottom)of the Panel |
| 64 | (f) Accessories like local remote switch, breaker control switch (T-N-C), space heater with thermostat, DC & AC control circuit through MCB, indicating lamps for RYB, spring charge, DC supply healthy, breaker ON/OFF, breaker in SERVICE/TEST.(g) Multifunction meter with RS 485 port ( EM6400 ng). (h) Digital Ammeter and Digital Voltmeter. (i) Separate master trip Relay and anti-pumping relay. (j) Wireless thermal sensor will be provided in each bus & each cable termination per panel, along with Zig- B concentrator and the data of the same should be display on HMI, other necessary arrangement to be consider. (k) Battery bank 24 Volts DC-12 Nos tubular maintenance free batteries 2 Volts 100AH including charger (k) Comprehensive numerical protecting relay( ABB- REL series/Schneider-Easergy Series, SIEMENS-Siprotech series) should have built-in integrated mimic compatible with IEC 61850 for non-directional O/C, E/F, U/V, O/V protection type having followed additional facilities :-(i) Trip ckt supervision.(ii) Distribution recorder. (iii) Event log with date and time. (iv) Conformal coating for harsh environment. (v) Suitable to operate on24 volts DC for auxiliary and control supply. (l) Panel should also have additional facilities :-(i) Only OEM panels are to be supplied. Partner or franchises are not accepted. (ii) Fullyinternal arc type tested (25 KA for 1 Sec-AFLR) as per latest IEC 62271-200. (iii) Vacuumbottles should be tested for 100 full short circuit operations.(iv) Manual closing/ tripping of CB with compartment door closed. (v) The panel shall be provided with power pack battery backup for not less than 10 minutes.(vi) Arc Flash Relay should be in each way to detect and rapidly clear arc faults in electrical systems. (vii) Breaker shall be provided with following contacts.(a) Auxiliary switch with 6NO+6NC mounted on the draw out portion of the switchgear.(b) Position switches with 3 NO+1NC contacts for each position in SERVICE and TEST. |
| 65 | Make of HTPanels are ABB- ZS1, BHEL, SCHNEIDER-PIX , SIEMENS - NX-AIRNote : The panel shall be SCADA Compatible system. The Vacuum Interrupter, Breaker &Panel along with Relay should of same make for better coordination. and better SCADAcompatibility. Bus Coupler compartment doesn’t carry numerical protection relay, PT,Voltmeter & arc flash relay in their compartment and a bus rises is required with bus coupler.Outgoing compartment don’t carry PT & Voltmeter |
| 66 | Suppyling, installing, testing and commissioning of factory made Indoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 2 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (Main LT Panel No-1) |
| 67 | INCOMINGS |
| 68 | (a) ACB 415 Volts,800 Amp rating,50 KA, 4 Pole - 01 No |
| 69 | (b) 1200 Amps Copper bus bar 6way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 70 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 71 | (d) Digital Ampere meter 0-800 amps range with selector switch and including CTs |
| 72 | OUTGOINGS |
| 73 | (a) MCCB Adjustable thermal and fixed magnetic 415 Volts,160 Amp rating,36 KA, 4 Pole - 06 Nos( 1 no spare ) (for BlockNo-1,2,3,6 & 7) |
| 74 | Suppyling, installing, testing and commissioning of factory made Indoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 2 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (Main LT Panel No-2) |
| 75 | INCOMINGS |
| 76 | (a) ACB 415 Volts,630 Amp rating,50 KA, 4 Pole - 01 No |
| 77 | (b) 1000 Amps Copper bus bar 6way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 78 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 79 | (d) Digital Ampere meter 0-630 amps range with selector switch and including CTs |
| 80 | OUTGOINGS |
| 81 | (a) MCCB Adjustable thermal and fixed magnetic 415 Volts,315 Amp rating,36 KA, 4 Pole - 03 Nos( 1 no spare ) (for BlockNo-4,5 & Lift panel) |
| 82 | Suppyling, installing, testing and commissioning of factory made Indoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 2 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (Main LT Panel No-1) |
| 83 | INCOMINGS |
| 84 | (a) Micro processor based MCCB 415 Volts,315 Amp rating,36 KA, 4 Pole - 01 No |
| 85 | (b) 500 Amps Copper bus bar 6way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 86 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 87 | (d) Digital Ampere meter 0-315 amps range with selector switch and including CTs |
| 88 | OUTGOINGS |
| 89 | (a) MCCB Adjustable thermal and fixed magnetic 415 Volts,63 Amp rating,16 KA, 4 Pole - 08 Nos( 1 no spare ) (for BlockNo-1 to 7 Lift panel) |
| 90 | (b) MCCB Adjustable thermal and fixed magnetic 415 Volts,40 Amp rating,16 KA, 4 Pole - 01 No(for Mono block pump set 15 HP) |
| 91 | (c) MCB TPN 415 Volts,16 Amp rating,10 KA, 4 Pole - 01 No(for Street light) |
| 92 | (d) Street light timer 5 KW including all accessories(MCB,Contactor,timer etc) nature switch type |
| 93 | Suppyling, installing, testing and commissioning of factory made Outdoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 3.15 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (LT Panel near block No 4 & 5) |
| 94 | INCOMINGS |
| 95 | (a) Micro processor based MCCB 415 Volts,315 Amp rating,36 KA, 4 Pole - 01 No |
| 96 | (b) 500 Amps Copper bus bar 3 way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 97 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 98 | (d) Digital Ampere meter 0-315 amps range with selector switch and including CTs |
| 99 | OUTGOINGS |
| 100 | (a) MCCB Adjustable thermal and fixed magnetic 415 Volts,160 Amp rating,16 KA, 4 Pole - 03 Nos( 1 no spare ) (for Block No-4 & 5 ) |
| 101 | Suppyling, installing, testing and commissioning of factory made Indoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 2 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (Main LT Panel of lift) |
| 102 | INCOMINGS |
| 103 | (a) Micro processor based MCCB 415 Volts,63 Amp rating,16 KA, 4 Pole - 01 No |
| 104 | (b) 100 Amps Copper bus bar 3 way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 105 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 106 | (d) Digital Ampere meter 0-63 amps range with selector switch and including CTs |
| 107 | OUTGOINGS |
| 108 | (a) MCCB fixed thermal and fixed magnetic 415 Volts,32 Amp rating,16 KA, 4 Pole - 02 Nos( 1 no spare ) (for Block No-1Lift panel) |
| 109 | (b) MCCB fixed thermal and fixed magnetic 415 Volts,20 Amp rating,16 KA, 4 Pole - 01 No |
| 110 | Suppyling, installing, testing and commissioning of factory made Outdoor type LT cubical panel board suitable for operation on 415 volts, 3 phase, 4 wire 50Hz supply system inlcluding bus bar chamber in centre ( vertically) and cable alley either side, outer shell shall be made out of 3.15 mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the following mentioned fittings and inner shell shall be made out of 2mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half nob type locking, inlcuding provision for taking out incoming and outgoing cables duly marked with reveted letter plated of appropriate size for each feeder / block cable, danger board, detachable plate at bottom for cable entry etc including double compression type cable gland with bottom frame made out of angle iron 40mm x 40mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over and including 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body with and including following accesories :- (LT Panel for existing 3 block OR Qtr) |
| 111 | INCOMINGS |
| 112 | (a) Micro processor based MCCB 415 Volts,160 Amp rating,36 KA, 4 Pole - 01 No |
| 113 | (b) 250 Amps Copper bus bar 8 way for phases and Neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in seprate compartment and internally prewired - 01 Set |
| 114 | (c) Digital volt meter 0-500 Volts with selector switch digital type-01 No |
| 115 | (d) Digital Ampere meter 0-250 amps range with selector switch and including CTs |
| 116 | OUTGOINGS |
| 117 | (a) MCCB Adjustable thermal and fixed magnetic 415 Volts,40 Amp rating,16 KA, 4 Pole - 08 Nos( 1 no spare ) for existing 3 block OR Qtr) |
| 118 | S&F Hot Dip Galvanized octagonal pole (7 Mtr long) Top dia -70 mm , Bottom Dia -130 mm, Thick -3mm , base plate -220 mm x 220 mm x 12 mm with 1.5 mtr single Arm HDG OD-48.3 F.Bolt 4 Nos. 20x 600 mm. including foundation as per coy standard specification and approved Drg including suitable three phase bus bar connection with 6 Ams MCB complete all as specified & directed by Engineer-in-Charge. |
| 119 | Supply & fixing copper cable multistrand PVC insulated PVC sheathed 2.5 Sqmm 3 core all as dircted by Engineer-in-Charge. |
| 120 | S&F cable route indicator of size 100mmX100mmX05mm thick GI plate with insertion there on bolted welded to 35mm X 35mmX 6mm angle iron 60 cm long and frouting the sae in ground with PCC as required for LT/HT cable incl necessary earth work all as specified and directed. |
| 121 | Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI strip 32X6 mm (upto the body of equipment) by means of GI bolts/nuts/washers, protected by 40 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, RCC cover in 1:2:4 type B1using 20mm graded crushed stone aggregate and reinfircement (TMT) with 8mm dia @ 100 c/c bothways & frame, PCC (1:3:6) type C2 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, complete all as specified & shown in electrical plate No. 3 of MES schedule Part-I.Note:(i) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate.(ii) PCC chamber shall be construced at least 1.50 m away from the earth electrode and pipe for watering shall be provided in slanting manner. |
| 122 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure. |
| 123 | Supply and laying DWC pipe of size 50 mm bore (ID), ISI marked,laid in trenches, under road, insert under holes for cable protection complete all as specified and as directed.(Note:- Excavation and earthwork as required shall be measured and paid separately under respective item of Sch.) |
| 124 | Supply and laying DWC pipe of size 76 mm bore (ID), ISI marked,laid in trenches, under road, insert under holes for cable protection complete all as specified and as directed.(Note:- Excavation and earthwork as required shall be measured and paid separately under respective item of Sch.) |
| 125 | Supply and laying DWC pipe of size 103.5 mm bore (ID), ISI marked,laid in trenches, under road, insert under holes for cable protection complete all as specified and as directed.(Note:- Excavation and earthwork as required shall be measured and paid separately under respective item of Sch.) |
| 126 | Taking out/down unserviceable, defective any Type/size cable including disconnecting/dismantling all the electrical connections all as required at site and all as directed. |
| 127 | Design, Installation, Testing, Commissioning including Integration and Maintenance of theAdvanced Metering Infrastructure (AMI) with procurement of all necessary software,programming licenses, and documentation with having specifications and comprising of following :- Please Enable Macros to View BoQ information |
| 128 | Design, Installation, Testing, Commissioning including Integration and Maintenance of theAdvanced Metering Infrastructure (AMI) with procurement of all necessary software,programming licenses, and documentation with having specifications and comprising of following :- Please Enable Macros to View BoQ information |