| 1 | 25 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate |
| 2 | ST poles 9 m long ST-410 SP -33 with base plate & cap weight 164kg |
| 3 | 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 4 | 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 5 | 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 6 | 35 mm² (1Ckt for 25 KVA) single core Cable,1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type |
| 7 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 8 | GI Channel/Angle/Flat of sizes including clamps |
| 9 | Galvinized Nuts and Bolts. |
| 10 | Danger Plates with Clamps |
| 11 | GI Barbed wire for Anti-Climbing |
| 12 | Supply and painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) |
| 13 | Spike Earthing Rod 20mm 2,5 Mtr long with GI strip (25x3)mm |
| 14 | 3 phase 4 -wire Trivector Meter( Prodigy) with suitable type CT 200 Amp. |
| 15 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 16 | Sundry items like Aluminium lugs, Jumpers, Binding Tape |
| 17 | Cement bottoming 1:2:4 mix as per Standards 0.48 cum/pole |
| 18 | 35 mm2 AB (HT ) cable (3x35+1x70 insulated) mm2 XLPE (11KV 3C +earth) |
| 19 | Cable teermination kits |
| 20 | Suspension/Tension clamp with eye hook 20.51 Please Enable Macros to View BoQ information |