| 1 | Supply of steel tubular pole 11 mtrs long designated at 410-sp 56 in 1:3:6 cement concrete foundation including excavation back filling etc complete in all respects UPERC P-30 |
| 2 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 metre and upto 12.00 metre DSR Electrical 2018/I.No. 11.3.4 |
| 3 | Supply of Top MS Channel 100x50x2240mm as per design complete in all respects UPERC P-39 |
| 4 | Supply of required clamp made of MS Nut and bolt etc. as per direction of E/I complete in all respects UPERC P-39 |
| 5 | S/F of 6\\" dia G.I. pipe B class for cable duly duly clamped with support by 1 no. with clamps for 20x3mm MS flat, bolt, nuts and washer required for proper completion of work (UPERC P-47) |
| 6 | S/E of over head line with ACSR Conductor on pole/service braket including binding etc. Complete in all respects as per PS No. 627 |
| 7 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 3000 mm, Outer Dia 50mm, inner Dia 25, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with food mixture of retaining capacity one earth lead of 25mm x 3mm G.I. Strip upto switch board (from apron to switch board, the cost of G.I. strip will be extra.) along with 30 cm squrare C.I. frame with hinged cover masonry housing. PS No. 725 (B) |
| 8 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respects. PS No. 716 |
| 9 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. DSR 2018 13.4 |
| 10 | S/F of 11 KV pin 12\\" long with insulator of Jai Shree/BHEL on cross arm fixed on HT pole including all T/P etc UPERC Pg-39 |
| 11 | S/F of 11 KV Disc insulator 70 KN and fitting B&S heavy duty with clamp of cross arm fixed on HT Pole UPERC P-43 |
| 12 | Painting of the electric pole with 2 coat of AI paint over red oxide primer complete in all respects As per PS No. 634 |
| 13 | Numbering of poles with combination of yellow and black colour paint etc complete in all recpects as per direction of E/I (AOR) |
| 14 | S/E of Stay set atleast 3.5 M away the pole Complete with galvan ished 19mmdiax 1.80m long stay rod, 30cmx30cmx6.3mm anchor plate thimble, Stay clamps, Stay insulator, 19mmx600mm stay double screw tightner 7/3.5mm of G.I. Wire etc. 1:3:6 (cement concrete) PS No. 631 |
| 15 | S/Laying of heavy density poly ethylene pipes ISI marked anti rediant grade OD 160mm dia PN-8 PE 100 (PE 400) grade as per IS code 4984 with excavation at a depth of 1.20 Mtr below ground level i/c the cost of cutting of pipes for making up to length and making joints complete all respects as per direction of E/I. (AOR) |
| 16 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. PS No. 501 240 sqmm x 3.5 core |
| 17 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making onnection etc. complete in all respect as per direction of the Engineer-Incharge. PS No. 504. 185 Sqmm |
| 18 | 240 Sqmm |
| 19 | Supply and laying 120 mm dia DWC ( Double wall corrugated pipe across the road by Trenchless method (Manual). Complete in all respect as per direction of E/I. (AOR) |
| 20 | S/F of 11 KV TPMO Relco/Rama make 9 nos insulator of Jai shree/BHEL make complete in all respects as per direction of E/I UPERC P-48 |
| 21 | S/F of 11 KV, 100 Amp, Drop fuse set channel type (3 nos) (AOR) |
| 22 | Design, Manufacturing, Supply, Receiving, Unloading, Shifting, Installation, Testing & commissioning L.T. Breaker Panel suitable for 415 Volts 3 phase, 4 wire, 50 Hz A/C supply totally enclosed type with free standing floor mounted dust and vermin proof indoor type fabricated from 2mm thick CRCA sheet complete with Digital AVF Meter with builtin selector switch, phase indicating lamps, ON/Off indication lamp, protection SP MCB for each cubicle suitable for incoming & outgoing for bus duct termination etc complete as required. ACB shall have overload, earth fault & short circuit protection. (Fault level of panel shall be 50 KA.) 800 Amp FP ACB (AOR) |
| 23 | FRP fencing (6 feet height including civil work) as per UPERC 2019 Page 53 |
| 24 | Plinth of Transformer as per UPERC 2019 Page 53 |
| 25 | Cable Trench as per UPERC 2019 page 53 |
| 26 | Interlocking tiles inside Transformer fencing as per UPERC 2019 page 53 |
| 27 | Dis/Re-fixing of 63/100/250 kva transformer with connection loading & unloading, cartage charge from site to repairing at worshop complete in all respects as per direction of E/I (AOR) |
| 28 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. DSR Electrical 2018/ I. No. 12.42 |
| 29 | Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required. DSR Elect 2018/I-12.40 |
| 30 | Demolisihing cement concrete manually/ by mechanical means including disposal of material within 50 maters lead as per direction of Engineer- in- charge Nominal concrete 1.3.6 or richer mix (i/c equivalent design mix) (AOR) |
| 31 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means over areas exceeding 30 cm in depth, 1.5 m, in width as well as 10 sqm on plan) including getting out and disposal of excvated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil.(AOR) |
| 32 | Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer of compacted earth (Soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer if filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer-in-charge, including compacting each layer by rolling/ ramming and watering, all complete as per drawing and direction of Engineer-in-charge. (Civil AOR) P-20 |
| 33 | Cement Concrete with 2 cm gauge approved stone ballast, coarse sand & cement in the proportion of 4:2:1 including supply of all mlaterials, labour, tools & plants etc. required for proper completion of the work. SOR 5.07 Schedule Item no. 279 (a) |
| 34 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required.(AOR) |
| 35 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required.bituminous portion.(AOR) |
| 36 | Hire Charges of Mobile Hydraulic Crane 35 tonne Capacity (173HP) (Based on DAR-2018 & Latest Material/Labour Rate of UPPWD BSR) Please Enable Macros to View BoQ information |