| 1 | 1.0) RMO of various E & M services like DG sets, lifts , Internal light fittings of Common Area of Pkt -9A , Jasola 3 Nos. Operator cum Technician Gr-II for 3 shift (each of 8 hrs shift) i.e. 6.00 AM to 2.00 PM and 2.00 PM to 10.00 PM & 10 PM to 6 AM daily for 368 days. |
| 2 | 2.0) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80,Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initialLumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trademark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm |
| 3 | 2.1) 18- 22 watt |
| 4 | 3.0) Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in recessed steel/ PVC conduit as required. the existing surface |
| 5 | 3.1) 1 x 1.5 sq. mm |
| 6 | 3.2) 3 x 2.5 sq. mm |
| 7 | 3.3) 3 x 4 sq. mm |
| 8 | 4.0) Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and ommissioning etc. as required. |
| 9 | 4.1) Single pole |
| 10 | 5.0) Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 11 | 5.1) 63 A |
| 12 | 6.0) Rewinding of Exhaust fan/48\\" ceiling fan oiling, greasing, servicing, cleaning, dismantling and re-assembling along with testing, commisioning etc. as required. |
| 13 | 7.0) Servicing of existing installed 250 KVA capacity of 3 phase, 440 volt DG set along with supply and replacement of following worn out parts such as Air filter , oil filter, engine oil, Lub Oil Filter, Koel Care Coolant,Radiator Descaling i/c testing, commissioning and cartage etc. complete as required. Please Enable Macros to View BoQ information |