Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | HT Metering Panel (SEB's) Supplying / Receiving, Installation, Testing and Commissioning of Powder coated, 14 SWG CRCA sheet steel enclosed 11KV H.T. Metering Panel complete with the following: 1set of 11/ √3KV / 110/ √ 3 Volt, 100 VA burden & accuracy class 0.5, single phase construction, dry type cast resin PT. 3 Nos. of dual core 50/5A, 15 VA burden, accuracy class CL 0.5, 11 KV cast resin CTs One Set of Phase Indicating Lamps. ,2 Sets of HRC fuses with fuse base (H.T. Fuse - 1A & LT fuse 2-6A). 2 Nos. indoor cable end box suitable for 3C x 240 sq.mm. 33 KV(E), aluminium conductor XLPE Ar. cable (Incoming & Outgoing cable).1 No. SEB approved digital Trivector meter with MDI in KVA of accuracy class - 0.5.(Accuracy class shall be as per local board) Note: The contractor shall get the Trivector meter, CTs' & PT tested by SEB and the charges for liasioning for the same will be paid extra. SITC Rate for Metering Panel as described above Note: The contractor shall ensure that the above panel meets the requirement as insisted by State/Local authorities(As per SEB) for satisfactory operation and as per the Drawings |
| 2 | 11kV 2 POLE STRUCTURE Supply,installation,testing and commissioning of two pole structure with required arrangement for terminating 11KV overhead conductor on one side and 11KV, 2R x 3 x 300 sq.mm. Al conductor XLPE cable on the other side including providing triple pole ,mechanically operated mounted on insulators and steel frame with operating mechanism worked from ground level,expulsion fuses of 33KV ,required rating along with 11KV 200 amp air break isolator suitable for outdoor application ,earth switch, Metal oxide type Lightning arrester complete with all fittings and discharge capacity 50 KA complete as required. 11 kV HT 'H' pole as per specification & as described above |
| 3 | 11kV/0.433kv Compact Sub-StationDesign, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site and supervising the testing & commissioning of 11kV compact secondary substation suitable for Outdoor installation with natural cooling, having type tested equipments comprising of oil-type distribution transformer and SF-6 insulated compact switchgear enclosed in robotically sealed stainless steel tank, low-voltage switchboard, interconnection between HT switchgear and transformer using cables and transformer to LT-switchgear using aluminium busbars, factory built ready for connection type, internal GI earthing provided complete with other associated equipments etc. complete as required conforming to IEC 62271-202 and relevant IS or international specifications, as regards to design, manufacturing, type-testing, routine-testing and operator safety (IAC AFLR). The enclosure shall have modular construction using G.I. Sheet and shall be powder-coated from exterior. The Transformer compartment will have IP-23 ingress protection, whereas the HT/LT compartment will have IP-54 protection. The 11kV Outdoor Compact Sub-Station shall be consisting of following |
| 4 | 11kV 630Amps 20kA for 3 sec. & tested for 20kA/ 1 sec internal arc , SF6 insulated Non-Extensible Compact switchgear consisting of One No. Direct Module for Incomer and one No. of Fixed Manual Vacuum Circuit Breaker in SF6 insulated Stainless steel enclosure with series trip,self powered microprocessor based numerical over current and Earth Fault (IDMT+Inst.) relay protection along with. Interconnection between HT switchgear and transformer shall be using 3Cx240 sq.mm Al. armorured XLPE Cable.....1 Set ,TRANSFORMER 1no. 500KVA 11KV/433V Dyn11 Oil filled hermatically sealed transformer without conservator type of design having corrugated tank & Top normal porcelein Bushings for HT & LT with OLTC and RTCC switch of rating +5% to -15% @2.5%. Temp Rise - Oil/Winding 40/50 deg cel, NL/FL Losses = 1.4/14 KW (Subject to IS Tol.), Impedanace 5% (Subject to IS Tol.) .....1 Set Oil temperature Indicator, Winding Temperature indicator with Alarm and Trip Contact…..1 Set |
| 5 | 1 Nos. 800A, 50KA 4 pole microprocessor based EDO, ACB with integral protection Outdoor type enclosure with slanted roof & having construction of Galvanised Sheet Steel of thickness 1.5/2mm. The enclosure shall be type tested for IAC 20 kA/ 1 sec AB class as well as impact test as per IEC 62271-202 or international standards with reports not later than 5 years. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment with transformer compartment thermal class of K-20 as per latest IEC. The enclosure shall be Powder Coated (Colour Light Gray & D.A.Gray ). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for each compartment.....1 Set |
| 6 | INTERCONNECTION AND EARTHING Interconnection Between HT switchgear & Transformer using 3Cx240Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using Aluminium Busbars. Internal earthing connections by using 50x6 mm GI strips…...1 Set Supply of 11kV Compact Substation including Receiving,unloading , shifting at designated place, fixing, testing & commissioning as per specifications described above. |
| 7 | Supply and fixing in position the approved \\"shock treatment charts\\" framed in teak wood frame and covered with glass in front as required in two languages (Hindi & English) |
| 8 | Supply & fixing of Mimic diagram for overall schematic of power distribution complete as required. |
| 9 | Supply and fixing in position the best quality \\"Danger Boards\\" of approved shape and size as specified by Local Electricity Authorities written in English and Local languages. a. 11 KV (250mm X 200mm) |
| 10 | Supply and fixing in position the best quality \\"Danger Boards\\" of approved shape and size as specified by Local Electricity Authorities written in English and Local languages. b. 440V (150mm X 100mm) |
| 11 | Supply & Laying of non skid Electro mat 1 mtr wide and 3.0 mm thick 11 KV grade conforming to IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities. |
| 12 | Supply of fire buckets 5 nos. 15 litre capacity duly filled with fine sand and fixed on an angle iron frame as per requirement of local authorities. The fire buckets shall be painted red from outside and white from inside, including lettered as FIRE with white colour with extra handle at bottom. |
| 13 | Supply & Laying of non skid Electro mat 1mtr wide and 2.0 mm thick 11 KV grade IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities. |
| 14 | Supply of Rubber hand gloves 33 KV grade, as per IS 4770-1968. |
| 15 | Supply of standard first aid box as approved by Indian red cross society/ St.John Ambulance Brigade and conforming to IS 2217-1963. |
| 16 | Supply & Installation of Earthing Trucks (Casette type) of same Make as HT Panel complete as required. |
| 17 | Supply, Receiving, shifting, laying, testing and commissioning of following 1100V grade PVC insulated armoured copper conductor control cables on existing cable tray/ trench as per specifications including of all clamps/ saddles/screw and cable identification tags etc. complete as required including termination of the following sizes of PVC insulated Copper conductor cable including providing terminal lugs,single compression gland , crimping the joints ,providing insulation tape,effecting terminal connections to the equipment.(For HT Panel controls, Transformer Protection, PLC controls. a. 2C X 2.5sq.mm Cu. Cable |
| 18 | b. 10C X 2.5sq.mm Cu. Cable |
| 19 | c. 2C X 1.5sq.mm Cu. Cable |
| 20 | d. 12C X 1.5sq.mm Cu. Cable |
| 21 | Supplying, Receiving, shifting, and commissioning of following sizes of 11 KV grade XLPE insulated aluminium conductor armoured power cables conforming to IS : 7098 (Part-II) laid buried in ground / trench / existing Hume pipe / PVC pipe / GI pipe in an approved manner complete as required and as per specifications including excavation of trench in all classes of soil, including supply and provision of sand bed above the cable and below the cable with supply and laying of 1st class brick protection back filling of the trench with excavated earth free from boulders after laying and dressing of the cable in an approved manner complete as required as per IS1255 and as per drawing. b. 3 core X 300 sq. mm |
| 22 | Laying of one number XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. a. Above 120 sq. mm and upto 400 sq. mm |
| 23 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq. mm |
| 24 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq. mm |
| 25 | APPROVAL / LIASIONING WORK WITH STATUTORY AUTHORITIES : (i) Charges for Liasioning with State Electricity Board for getting approvals, clearances for load sanction and obtaining connection etc. Complete for energising the installation with State Electricity Board power as required. The charges shall broadly include but not limited to following and as per SCC.(ii) Load application, load sanction, drawing / scheme approval by CEIG / any other statutory bodies, inspection and approval of installation by CEIG / any other statutory bodies, demand notice & estimate, service connection order, permanent connection and energization. |
| 26 | LT PANELS & DISTRIBUTION PANELS, The contractor shall consider the following details in their item rates, wherever required: Supporting rigid steel framework. Cubicle type, 14 gauge CRCA sheet steel enclouser. Complete with interconnections and distribution bus bars. Proper bonding to earth. Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram. Providing cable clamps / supports within distribution boards cable alley. TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link. All MCB 10KA C Curve’s shall be of minimum 10 KA breaking capacity. All motor feeders MCCBs shall be of motor duty. Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5 Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.. IP 42 for indoor panels. IP 54 for kitchen and laundry panels. IP 55 for outdoor panels All MCCB’s shall be provided with operating mechanism for door interlock. Current density of aluminium shall be 1 sq mm for 1.0 amps for rated current of bus bars and current density of copper shall be 1 sq.mm for 1.25 amps for rated current of bus bars.Tinned copper earth bus shall be provided through out the length of each board. All measuring instruments (Meters) shall be of digital electronic with LED of approved make and compatible with BAS. All hinged door shall be earthed through 4.0 sq mm tinned braided copper wire. All panels shall have provision of the following: Pad locking of Switch board doors. Pad locking of MCCB’s handles in “OFF” Position. Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in Main Switch Board sections. Only transducers shall be supplied by BAS contractor. |
| 27 | All MCB 10KA C Curve’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation. All PTs / control transformer shall be provided with centre tap earth secondary. All DOL & Star-Delta Starters shall be provided with SPPR (single phase preventor relay) and 2 nos. of Aux.Contacts for Remote operation/monitor.The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of cables are terminated in the breakers. Readymade 16 SWG Sheet steel Enclosure with cutout For MCB 10KA C Curves The equipment shall be designed to conform to the requirements of Low Voltage switchgear Assemblies IEC61439-1& 2 The switchboard along with ACBs and connections should have been type tested design as per IEC 61439 1 & 2 for short circuit, temperature rise, protective earth short circuit test and dielectric tests of the ratings required, As specified in the BOQ the switchboard shall be form 4B, For form of separation only metallic covers shall be used , Hylem / PVC sheets shall not be allowed Frame of Switchboard shall be made of GI 275GSM Zinc coated metal with mimumum of 9 fold design structure. No welding frame to be considered All bus bar support shall be of material Glass Reinforced polyamide, this is required to have better strength & insulation properties Switchboard shall have finger touch proof design with rear Terminals for MCCB feeders. Rear stud terminals shall be used directly on MCCB to avoid any direct touch in the front. Metal based Polyurethane gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust and vermin proof to provide required degree of protection as stipulated in schedule of quantities . The unused openings within the switchboards shall be closed using suitable grommets Panel shall be tested for Internal arc as per IEC61641 – 50Ka for 0.3 sec Panel shall be tested for Seismic withstand of Zone-IV |
| 28 | Busbars shall be made of high conductivity, 99.9% purity, high strength Aluminium of ETP grade Busbars shall be of rectangular cross sections , suitable for full load current for phase bus bars and half/ full rated current for neutral bus bar or as stipulated in schedule of quantities. Busbar shall be suitable to withstand the stresses of fault level as specified in schedule of quantities. All incomer ACBs of Main LT Panel, Capacitor Panels & DG Panels shall be with microprocessor based releases (O/C, S/C & E/F), display of current/voltage and inbuilt onboard Ethernet Modbus TCP/IP communication port (Ics=100%Icu=Icw for 1 Sec ) All ACB release shall be suitable for communication between breakers to enable zone selective interlocking. This feature shall be provided for both short circuit and ground fault protection zones to offer total discrimination between breakers. This feature enables the clearance of fault conditions, thereby reducing the thermal and dynamic stresses produced during fault conditions and thus minimizes the damage to the system. To implement ZSI manufacturer should supply all related equipment like power supply, wiring etc. All ACB protection release shall be suitable for communication on TCP/IP Ethernet The release should have the following measurement functions such as Current, Voltage, Power, Power factor, frequency and peak factor, Phase Sequence, Energy, includes current and voltage both The release shall have wide touch screen LCD display with possibility to view the maximum parameters and bar graph display for % loading of phases. It shall also have bar graph to indicate individual phase loading and identify whether all phases are evenly loaded The protection release shall be able to provide information about the last 20 trips with interrupted fault value and last 200 events (for eg. Open/close of breaker, alarm, editing setting, time stamp etc). The release should have the following measurement functions such as Current (class 1), Voltage (Class 0.5), Power (Class 2) The protection release shall be able to provide information Number of operations (mechanical and electrical), Contact Wear, Load profile and the last maintenance carried out – Locally as well as on communication network connected with EMS/BMS/EDCS/SCADA. |
| 29 | Total Discrimination – There shall be total discrimination between upstream circuit breaker to downstream circuit breaker for the complete project. Panel manufacturer /Switchgear manufacturer shall submit the complete study report generated through software’s reports. Manufacturer shall also submit published discrimination tables during drawing approvals. The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic releases upto 250 amps and miroprocessor based above 250 amps capacity, unless specified otherwise. All the ACBs must be equipped with features like ZSI, Thermal Memory, last 20 trip histories, current & Voltage Metering, % loading Bar graph, LED fault Indication, contact wear, display of per phase energy & Total Harmonics Distortion All the MCCBs in Main Panel to communicate ON/OFF/TRIP status on Ethernet. ( MODBUS TCP/IP) ACB shall comply with standards IS/IEC 60947-1 & 2 ACB shall have a rated operational voltage of 415V AC, rated insulation voltage of 1000 volts AC, rated impulse voltage of 12kV. ACB shall have a Ready to close mechanism preferably having a ready to close mechanical indication on front of ACB. All EDO ACBs ready to close indication contact MCCB shall have a rated operational voltage (Ue) of 415V, insulation voltage (Ui) of 800V (AC 50/60 Hz) & impulse voltage (Uimp) of not less than 8kV. Panel Makes -ABB (ARTUK)/Schneider (Blokset)/Siemens (Sivacon) OEM or their authoised Channel partner for TTA panels. ACB, MCCB, TVSS, Meter, ATS makes & Panels Accessories - ABB/Schneider/Siemens MCCBs shall be current limiting type having a double break design (above 250A) Protection Releases Microprocessor based (PRMB) & (upto 250A) Thermal magnetic (PRTM) shall be as described below . |
| 30 | Protection Release Microprocessor Based (PRMB-1) For ACB, Over-current/long time protection range 40% - 100 % with Time setting short circuit /short time protection range 60% - 1000 % with Time setting Instantaneous short circuit Protection range 150% - 1500 % with Time setting Earth Fault Protection range 10% - 100 % with Time setting ZSI(Zone Selectivity Interlocking) Measurements Voltage: phase-phase, phase-neutral currents of the three phases (L1, L2, L3) and of neutral (Ne) with 1% accuracy Energy Power factor ACBs must be equipped with features like ZSI, Thermal Memory, last 20 trip histories and 200 event , current & Voltage Metering, % loading Bar graph, LED fault Indication, contact wear, display of per phase energy & Total Harmonics Distortion with embeded communcaiation MODBUS TCP/IP port for fast communcation. ACBs must be equipped with features like ZSI, Thermal Memory, last 20 trip histories and 200 event , current & Voltage Metering, % loading Bar graph, LED fault Indication, contact wear, display of per phase energy & Total Harmonics Distortion with embeded communcaiation MODBUS TCP/IP port for fast communcation. Protection Release Microprocessor Based (PRMB-3) For MCCB Overload protection setting 40% to 100% short circuit protection Protection Release Thermal-Magnetic Based (PRTM) For MCCB Over-current protection setting 70% to 100% Short circuit |
| 31 | Design, fabrication, assembly, wiring and supply of front operated dead front cubicle type compartmentalised as per Form 4B, rear access free standing, dust and vermin proof (IP 42 ingress protection) main switchboards suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level of 50 kA at 415 volts, fabricated from 2 mm thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below.(Note:The contractor may select the next higher fault rating of MCCB if it is not readily available ,without any extra cost ,as the figure indicated within the bracket are required maximum fault level of the panel). Note:- Panel above 250Amp shall be TTA Type |
| 32 | SITC of Main LT Panel IP:42 Bus Section-01 From 500 KVA Compact Substation 1 No. 800A 4 pole microprocessor based EDO, ACB (35kA) with integral protection as per PRMB-1 mentioned in Premable 1 set of 800/5A, 15 VA, class-1 CTs for APFC relay 1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCB 10KA C Curves. 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB 10KA C Curve 1 No. (0-800A) Ammeter with ASS with 3 nos. 800/1A CT's 1Set- of ON/OFF/Trip/ Spring Charged/ Supply On & Trip circuit healthy indicating lamps. 240 V AC Motor wound spring closing mechanism 1 - 24 volts DC shunt trip coil 6 nos NO/NC contacts for remote opening & closing Terminals to receive XLPE insulated Aluminium cables Class – B transient voltage surge suppression devices suitable for 3 phases as per specification. Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port OV Relay/ UV Relay/ Master Trip Relay/ Trip Circuit Supervision Relay/ Circuit Breaker Failure Detection Relay & Negative Phase Sequence Over Current Relay Emergency Push Button |
| 33 | From Solar Panel 1 Nos. 100A 4 pole microprocessor based MCCB (35kA) with integral protection as per PRMB 1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCB 10KA C Curves. 1Set- of ON/OFF/Trip indicating lamps. 6 nos NO/NC contacts for remote opening & closing Terminals to receive XLPE insulated Aluminium cables Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port Busbar Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 1000 amps having a maximum current density of 0.8 amp per sq mm suitable to with stand symmetrical fault level of 50 kA at 433 volts. The neutral busbar is to be of 50% capacity. |
| 34 | Outgoings:Bus Section-1 3 No. 500A FP MCCB(35 KA) complete with: 3 nos 500/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. 3 No. 160A FP MCCB(35 KA) complete with: 3 nos 160/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. 1 No. 125A FP MCCB(35 KA) complete with: 3 nos 125/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. |
| 35 | 1 No. 100A FP MCCB(35 KA) complete with: 3 nos 100/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. 2 No. 63A FP MCCB(35 KA) complete with: 3 nos 63/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection.Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified.Buscoupler1 No. 1000Amps, 50KA, 433 volt 4-P EDO ACB without release complete with following: 6 Nos. NO/NC contacts for remote opening & closing Red/Green / Amber / ON/OFF / Trip indicating lamps with 2A SP MCB 10KA C Curve as backup protection. Backup MCB 10KA C Curve and terminal blocks as required. TNC Breaker Control switch Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme. Bus Section-02 From 380 KVA DG Set Buscoupler1 No. 1000Amps, 50KA, 433 volt 4-P EDO ACB without release complete with following: 6 Nos. NO/NC contacts for remote opening & closing Red/Green / Amber / ON/OFF / Trip indicating lamps with 2A SP MCB 10KA C Curve as backup protection. Backup MCB 10KA C Curve and terminal blocks as required. TNC Breaker Control switch Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme. |
| 36 | 1 Nos. 630A 4 pole microprocessor based MCCBB (35kA) with integral protection as per PRMB mentioned in Premable 1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCB 10KA C Curves. 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB 10KA C Curve 1 No. (0-630A) Ammeter with ASS with 3 nos.630/1A CT's 1Set- of ON/OFF/Trip/ Spring Charged/ Supply On & Trip circuit healthy indicating lamps. 240 V AC Motor wound spring closing mechanism 1 - 24 volts DC shunt trip coil 6 nos NO/NC contacts for remote opening & closing Terminals to receive XLPE insulated Aluminium cables Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port Class – B transient voltage surge suppression devices suitable for 3 phases as per specification. Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port OV Relay/ UV Relay/ Master Trip Relay/ Trip Circuit Supervision Relay/ Circuit Breaker Failure Detection Relay & Negative Phase Sequence Over Current Relay Emergency Push Button |
| 37 | Busbar Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 1000 amps having a maximum current density of 0.8 amp per sq mm suitable to with stand symmetrical fault level of 50 kA at 433 volts. The neutral busbar is to be of 50% capacity.Outgoings:Bus Section-2 1 No. 200A FP MCCB(35 KA) complete with: 3 nos 200/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified.2 No. 160A FP MCCB(35 KA) complete with: 3 nos 160/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. |
| 38 | 2 No. 100A FP MCCB(35 KA) complete with: 3 nos 100/1A Class - 1.0, 5 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection. Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. 4 No. 63A FP MCCB(35 KA) complete with: 3 nos 63/1A Class - 1.0, 15 VA Burden CT's for metering ON / OFF & Auto Trip indicating lamps with MCB 10KA C Curve as backup protection.Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of Accuracy-1 as specified. LT Panel Descrived Above |
| 39 | SITC of Lift Panel Incomer 1 No. 63amps 4P MCCB(35KA) with thermal Magnetic release (PRTM) with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications. 1 No.63 amp 4 Pole ATS (automatic transfer switch) solenoid operated, Automatic operation & complete Neutral overlapping, equipped with built in controller, the controller and ATS should be one unit with LCD display, controller should be onsite replaceable at the time of event of fault. Metering & Indication for each Incomer 1 set of R,Y,B phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port.Sets of 63/1A, CL-1, 15VA CTs for measuring. Sets of On/Off indicating lamp with 2A control MCB 10KA C Curves. Emergency Push Button with Each Incomer Busbar 100 A TP+100%Neutral Aluminium Bus Bar with colour coded PVC SleevesOutgoings 3 Nos.25 Amp TP MPCB 10KA with short circuit, overload and phase loss protection 3 Nos.32 Amp FP MCB 10KA with short circuit 2 Nos.40 Amp DP MCB 10KA with short circuit Lift Panel as described above |
| 40 | SITC of Capacitor Panel (170kVAR) Incomer:- 1 No. 500A ACB FP MCCB 35KA with Microprcoesaor based integral protection as per PRMB mentioned in Premable 1 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB 10KA C Curve (96mm square) (one for each Incoming Breaker). 1 No. 0 to 500Amp digital ammeter (96mm square) with CT's. 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).1Set- of ON/OFF/Trip/ Spring Charged/ Supply On & Trip circuit healthy indicating lamps. 12 Step Automatic Power Factor Correction relay (APFC relay). Busbar 630 Amp TP+NEUTRAL busbars of aluminium alloy as per SLD. Outgoings 2 Nos.125 Amp TP MCCB. 2 Nos. capacitor duty contactor (one for each 50 KVAR capacitor unit with APP type Capacitor bank) 2 Nos. 63 Amp TP MCCB. 2 Nos. capacitor duty contactor (one for each 20 KVAR capacitor unit with APP type Capacitor bank) 2 Nos. capacitor duty contactor (one for each 10 KVAR capacitor unit with APP type Capacitor bank) 2 Nos. 32 Amp TP MCCB.2 Nos. capacitor duty contactor (one for each 5 KVAR capacitor unit with APP type Capacitor bank) 8 sets of push button stations with indicator Red and Green for manual operation of capacitor units with auto/manual selector switches. 1 No. Indicating lamp for each 50/ 20/ 10/ 5KVAR capacitor unit to indicate that the unit is 'ON'. 1 No. Toggle switch for changing automatic to manual operation of capacitor units.Power factor meter. Capacitor Panel Described as above |
| 41 | SITC of Basement VTPN DB, 1 No. 125amps 4P MCCB (35KA) with thermal Magnetic release (PRTM) with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications.200A TPN Copper Bus Bar with colour coded PVC Sleeves Outgoings 4 No. 63amps TP MCB 10KA C Curve 4 No. 40amps TP MCB 10KA C Curve Basement VTPN DB Described as above |
| 42 | SITC of Ground,2nd,3rd,4th,5th,6th,7th & 8th Floor Panel 1 No. 125amps 4P MCCB (35KA) with Thermal Magnetic release (PRTM) with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications. Metering & Indication for each Incomer 1 set of R,Y,B phase indicating lamps 1 set of On/Off phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port. Sets of 125/1A, CL-1, 15VA CTs for measuring. Busbar 160A TP+100%Neutral Aluminium Bus Bar with colour coded PVC Sleeves Outgoings, 5 No. 63amps FP MCCB 10KA C Curve 5 No. 40amps FP MCCB 10KA C Curve, 5 No. 40amps DP MCB 10KA C Curve 3 No. 100amps FP MCCB 10KA C CurveGround,2nd,3rd,4th,5th,6th,7th & 8th Floor Panel Described as above |
| 43 | SITC of 1st.Floor Panel 1 No. 160amps 4P MCCB (35KA) with Thermal Magnetic release (PRTM) with Class-C transient voltage surge suppression device suitable for 3 phases as per specifications. Metering & Indication 1 set of R,Y,B phase indicating lamps 1 set of On/Off phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port. Sets of 160/1A, CL-1, 15VA CTs for measuring. Busbar 200A TP+100%Neutral Aluminium Bus Bar with colour coded PVC Sleeves Outgoings, 4 No. 63amps FP MCCB 10KA C Curve 4 No. 40amps FP MCCB 10KA C Curve 4 No. 40amps DP MCB 10KA C Curve 1st.Floor Panel Described as above |
| 44 | SITC of Plumbing Panel Incomer 1 No. 100amps 4P MCCB(35KA) with overcurrent,earth fault and short circuit releases each complete with 1 No.100 amp 4 Pole ATS (automatic transfer switch) solenoid operated, Automatic operation & complete Neutral overlapping, equipped with built in controller, the controller and ATS should be one unit with LCD display, controller should be onsite replaceable at the time of event of fault. Metering & Indication for each Incomer 1 set of R,Y,B phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port Sets of 100/1A, CL-1, 15VA CTs for measuring. Sets of On/Off indicating lamp with 2A control MCB 10KA C Curves. Emergency Push Button with Each Incomer Busbar 125A TP+100%Neutral Aluminium Bus Bar with colour coded PVC Sleeves Outgoings 7 No. 40amps FP MCB 10KA C Curve with Suitable Startor 4 No. 25amps FP MCB 10KA C Curve with Suitable Startor 2 No. 125amps FP MCCB 25KA C Curve with Suitable Startor The contractor would be considerd startor rating as per final SLD without any extra cost.Plumbing Panel Descrived Avobe |
| 45 | Designing, SITC of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification (INCOMER & METERING) 400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Bus Bar 500Amps (OUTGOING) (a) MAIN FIRE PUMP- 03 Nos of 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets (b) JOCKEY PUMP 03 Nos of 63 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.(c) 2 No. of 40amps FP MCB 10KA C Curve with suitable startor (d)DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter The contractor would be considerd startor rating as per final SLD without any extra cost. Fire Fighting Panel Descrived Above |
| 46 | SITC of Drainage Sump Panel Described Above 1 No. 63amps 4P MCCB(36KA) with overcurrent,earth fault and short circuit releases each complete with Metering & Indication for each Incomer 1 set of R,Y,B phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port. Sets of 63/1A, CL-1, 15VA CTs for measuring. Sets of On/Off indicating lamp with 2A control MCB 10KA C Curves. Busbar 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves Outgoings 6 No. 32amps FP MCB 10KA C Curve Drainage Sump Panel Described Above |
| 47 | SITC of Ventilation & Pressurization Panel As Descrived Above 1 No. 160amps 4P MCCB(36KA) with overcurrent,earth fault and short circuit releases each complete with 1 No.160 amp 4 Pole ATS (automatic transfer switch) solenoid operated, Automatic operation & complete Neutral overlapping, equipped with built in controller, the controller and ATS should be one unit with LCD display, controller should be onsite replaceable at the time of event of fault. Metering & Indication for each Incomer 1 set of R,Y,B phase indicating lamps Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th order & %THD) with RS-485 Port. Sets of 160/1A, CL-1, 15VA CTs for measuring. Sets of On/Off indicating lamp with 2A control MCB 10KA C Curves. Emergency Push Button with Each Incomer Busbar 200A TP+100%Neutral Aluminium Bus Bar with colour coded PVC Sleeves Outgoings 16 No. 32amps FP MCB Ventilation & Pressurization Panel As Descrived Above |
| 48 | Providing, Installing, Testing and Commissioning of ‘Silent Type’ Diesel Generating set with AMF Panel along with having Require Power Rating, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor and consisting of the followings including making necessary civil foundation etc. complete as required: Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for delivering required output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The Engine mounted Instrument Panel fitted with and having digital display for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Battery charging indication (v) RPM indication (vi) Over speed indication (vii) Low lub. Oil trip indication (viii) Engine Hours indicationSynchronous alternator Require Capacity at, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class-F/H insulation.Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.Daily service fuel tank of 990 liters capacity respectively fabricated out of 2 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank Complete with valves, level indications & accessories as required as per specifications.Dry exhaust manifold with hospital exhaust silencer and catalytic convertor. 24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (180 AH capacity lead acid type) as required as per specifications. Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications, For in house power Generation for Suitable Emergency loads. |
| 49 | Supplying and fixing Exhaust gas piping of 1x125 dia. welded black MS, B Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50 mm thick wire mesh & aluminum cladding etc., as required as per specifications. and exhaust pipe shall be design as per CPWD/CPCB Specifications. |
| 50 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 51 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 52 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 53 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 54 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe FRLSom earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 55 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 56 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 57 | Providing and fixing 50 mm X 10 mm copper strip on surface or in recess for connections etc. as required. |
| 58 | Providing and fixing 50 mm X 10 mm G.I. strip on surface or in recess for connections etc. as required. |
| 59 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 60 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm |
| 61 | Above 35 sq. mm and upto 95 sq. mm |
| 62 | Above 95 sq. mm and upto 185 sq. mm |
| 63 | Above 185 sq. mm and upto 400 sq. mm |
| 64 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 65 | Above 35 sq. mm and upto 95 sq. mm |
| 66 | Above 95 sq. mm and upto 185 sq. mm |
| 67 | Above 185 sq. mm and upto 400 sq. mm |
| 68 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 69 | Above 35 sq. mm and upto 95 sq. mm |
| 70 | Above 95 sq. mm and upto 185 sq. mm |
| 71 | Above 185 sq. mm and upto 400 sq. mm |
| 72 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 73 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 74 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 75 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 76 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 77 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 300 sq. mm (70mm) |
| 78 | 3½ X 240 sq. mm (62mm) |
| 79 | 3½ X 185 sq. mm (57mm) |
| 80 | 3½ X 150 sq. mm (50mm) |
| 81 | 3½ X 120 sq. mm (45mm) |
| 82 | 3½ X 95 sq. mm (45mm) |
| 83 | 3½ X 70 sq. mm (38mm) |
| 84 | 3½ X 50 sq. mm (35mm) |
| 85 | 3½ X 35 sq. mm (32mm) |
| 86 | 4 X 25 sq. mm (28mm) |
| 87 | 4 X 16 sq. mm (28mm) |
| 88 | 4 X 10 sq. mm (25mm) |
| 89 | 4 X 6 Sqmm |
| 90 | 3C X 10 sq. mm (22mm) |
| 91 | 3 X 6 Sqmm |
| 92 | 2 X 10 sq. mm (19mm) |
| 93 | Supply, following sizes of PVC sheathed PVC/XLPE insulated Aluminium conductor/copper conductor power/ multicore control armoured cable of 1.1 KV grade. 3 ½ C - 300 sq mm Aluminium |
| 94 | 3 ½ C - 240 sq mm Aluminium |
| 95 | 3 ½ C - 185 sq mm Aluminium |
| 96 | 3 ½ C - 150 sq mm Aluminium |
| 97 | 3 ½ C - 120 sq mm Aluminium |
| 98 | 3 ½ C - 95 sq mm Aluminium |
| 99 | 3 ½ C - 70 sq mm Aluminium |
| 100 | 3 ½ C - 50 sq mm Aluminium |
| 101 | 3 ½ C - 35 sq mm Aluminium |
| 102 | 4C- 25 sq mm Aluminium |
| 103 | 4C- 16 sq mm Aluminium |
| 104 | 4C- 10 sq mm Aluminium |
| 105 | 4C X 6 Sqmm Aluminium Cable |
| 106 | 3C X 10 Sqmm Aluminium Cable |
| 107 | 3C X 6 Sqmm Aluminium Cable |
| 108 | 2C- 10 sq mm Aluminium |
| 109 | Supply, following sizes of Fire Survival Aluminium conductor power/ multicore control armoured cable. 3.5C x 300 sq mm Aluminium |
| 110 | 3.5 x 240 sq mm Aluminium |
| 111 | 3.5 x 185 sq mm Aluminium |
| 112 | 3.5 x 150 sq mm Aluminium |
| 113 | 3.5 x 120 sq mm Aluminium |
| 114 | 3.5 x 70 sq mm Aluminium |
| 115 | 3.5 x 50 sq mm Aluminium |
| 116 | 3.5 x 35 sq mm Aluminium |
| 117 | 4C- 25 sq mm Aluminium |
| 118 | 4C- 16 sq mm Aluminium |
| 119 | 4C- 10 sq mm Aluminium |
| 120 | Supply of following sizes XLPE insulated (Heavy duty) Aluminium or Copper conductor armoured cables suitable for working voltage upto and including 1100 Volts complete as required and as per specifications. 2 x 6 sq.mm |
| 121 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm |
| 122 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 123 | Termination of the following sizes of XLPE insulated Aluminium/ Copper conductor cable including providing terminal lugs,double compression gland , crimping the joints ,providing insulation tape,effecting terminal connections to the equipment complete as required. 2 x 6 sq,mm, Al conductor cable |
| 124 | Supply, laying and termination of the following sizes of 650/1100 volts grade PVC insulated copper conductor wires in existing conduits including end terminations with copper lugs. 3 x 2.5 sq.mm. Copper conductor ,PVC insulated PVC sheathed wires |
| 125 | Supplying and fixing in position of the following sizes of GI conduit buried in ground 600 mm deep including all accessories complete as required and as per specifications. 25 mm dia GI conduit |
| 126 | Supplying and fixing in position of the following sizes of GI conduit buried in ground 600 mm deep including all accessories complete as required and as per specifications. 25 mm dia GI conduit |
| 127 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 250mm dia |
| 128 | Supply,fixing and laying of Heavy duty PVC pipes complete buried in floor with joints and other accessories as required. 63 mm dia, 2mm thick |
| 129 | Supply of Polar pole made of square mild steel pipe (grade YST 210) 100mm Square x 2.9mm thick with 5500mm Height. The split constructed double arm bracket made of MS pipe 100mm square x 2.9mm thick having 900mm arm length and 484mm height inclined at 10 degree. Single arm bracket contains build-in 60W LED module. 60W LED Module with expected service life of at least 60,000 operating hours. High Brightness, LED Light source do not poseany environment risks. Excellent thermal management heat sink. High efficiency polycarbonate optical lens. IP68 Ingress protection. IK09 impact protection.Colour rendering index(Ra) >70. Available colour temperature 3000K / 4000K / 5700K. Driver efficiency > 85%, power factor > 0.95, THD <10%, Surge Protection 6KV. Pole section welded by certified welders using high end MIG welding processes. PDC aluminium service door 330mm height x 75mm width shall be provided with the company logo embossed on the bottom of the door and safety rope with IP protection rating. The control gear tray is prewired with2.5 Sq.mm cable, 6A SP MCB and 32A Ramanuj stud type 4 way terminal block for loop-in / loop-out arrangement, 5A 2 Way terminal connector and provision for earthing. Any other internal cables and connections shall not be covered in the scope of supply. Mild steel mounting plate 300mm Square x 16mm thick Steel of grade E250 to IS 2062 : 2011 with 4 elongated holes 48 x 24 to suit M20 x 500mm bolts of grade 4.6 at CC 215. This mounting steel plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed foundation. All dimension are within +/- 5% tolerance. Afterfabrication entire pole is shot blasted (Inhouse). The pole is coated with epoxy zinc phosphate primer and finished using environmentally stable powder coated (coating thickness 60-80 microns). The Pole shall be provided with Graphite grey / Anthracite grey / Black as standard colour options. Must have inhouse manufacuturing facilities along with powder coating shot blasting machines.KP-7229+KP-9108. Make: K- Lite/Ligman/Unilamp |
| 130 | Supply of Polar pole made of square mild steel pipe (grade YST 210) 100mm Square x 2.9mm thick with 5500mm Height. The split constructed double arm bracket made of MS pipe 100mm square x 2.9mm thick having 900mm arm length and 484mm height inclined at 10 degree. Double arm bracket contains build-in 2X60W LED module. 60W LED Module with expected service life of at least 60,000 operating hours. High Brightness, LED Light source do not poseany environment risks. Excellent thermal management heat sink. High efficiency polycarbonate optical lens. IP68 Ingress protection. IK09 impact protection.Colour rendering index(Ra) >70. Available colour temperature 3000K / 4000K / 5700K. Driver efficiency > 85%, power factor > 0.95, THD <10%, Surge Protection 6KV. Pole section welded by certified welders using high end MIG welding processes. PDC aluminium service door 330mm height x 75mm width shall be provided with the company logo embossed on the bottom of the door and safety rope with IP protection rating. The control gear tray is prewired with2.5 Sq.mm cable, 6A SP MCB and 32A Ramanuj stud type 4 way terminal block for loop-in / loop-out arrangement, 5A 2 Way terminal connector and provision for earthing. Any other internal cables and connections shall not be covered in the scope of supply. Mild steel mounting plate 300mm Square x 16mm thick Steel of grade E250 to IS 2062 : 2011 with 4 elongated holes 48 x 24 to suit M20 x 500mm bolts of grade 4.6 at CC 215. This mounting steel plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed foundation. All dimension are within +/- 5% tolerance. Afterfabrication entire pole is shot blasted (Inhouse). The pole is coated with epoxy zinc phosphate primer and finished using environmentally stable powder coated (coating thickness 60-80 microns). The Pole shall be provided with Graphite grey / Anthracite grey / Black as standard colour options. Must have inhouse manufacuturing facilities along with powder coating shot blasting machines.KP-7229+KP-9108. Make: K- Lite/Ligman/Unilamp |
| 131 | Supply of 45-50W Post top with LED 3000K, 4000K, 5700K 240Vac CRI >80 MacAdam step 3 Dimension not less than Ø400 x 807 mm, Light Distribution 360° Electronic driver ON/OFF, IP rating IP65/66, Spun aluminium top cover Ø400 mm of 1.6mm thickness, die cast aluminium decorative knob on top, Mild steel ( Sand Blasting with zinc primer supporting arm integrated with die-cast aluminium base suitable for mounting Ø76mm OD pipe. SS fasteners. Pure polyester powder coated process : Acid treatment & pure polyester powder coating. Clear acrylic diffuser with controlled downward light emission. Lamp fixed position. Lumen efficacy should be minimum 120lm/W. This luminaire should contains built-in LED modules. LED modules are engineered accordingly to the existing regulations of Lumen Maintenance (LM80) and Technical Memorandum (TM21), Lifespan of the luminaire L70B10>50,000 hours at 40°C. Operating ambient temperature range is from -15°C to +50°C. Driver efficiency>88%, power factor >0.96, THD <10%, Surge protection 6KV .the fixtures proposed must have passed LM 79 & LM- 80, latest Reports will be submitted post the issuance of LOA to the successful bidder and before the supply of material, Make of LEDs -LEDs of CREE / LUMINOUS / OSRAM / SEOUL / SAMSUNG/LUMILED /NICHIA/CITIZEN CE& BIS Certified manufactrurer must have inhouse NABL certified labs. Make: K-Lite/Ligman/Unilamp |
| 132 | Supply, laying, fixing Ladder and perforated type Cable Trays shall be manufactured as per IS /IEC 61537 and it shall be of Pre Galvanized bolted type and factory fabricated out of CRCA sheet with standard accessories like tees- Horizontal and Vertical, Circular bends- Horizontal and Vertical, Coupler plates, Reducers, 4-way cross, Tray covers, Fasteners. etc. for different loads and number and size of cables as given below. All indoor type cable trays shall be galvanized according to BS EN /IEC 10346 with 275 GSM and All outdoor type cable trays shall be Hot dip galvanized according to DIN EN ISO 1461 with 60 microns. 450mm x 100mm x 3mm Runners 20 x 150 x 20 x 2.5 mmRungs 20 x 30 x 20 x 2.5 mm 250 mm C/C |
| 133 | 300mm x 100mm x Runners 20 x 150 x 20 x 2.5 mmRungs 20 x 30 x 20 x 2.5 mm 250 mm C/C |
| 134 | 150mm x 50mm x 3mm Runners 20 x 150 x 20 x 2.5 mmRungs 20 x 30 x 20 x 2.5 mm 250 mm C/C |
| 135 | Providing & fixing 50mm x 50mm x 5mm GI angle suspenders & base supports for ladder cable trays upto 1500mm with all necessary fixing accessories. |
| 136 | Providing & fixing 40mm x 40mm x 5mm GI angle suspenders & base supports for ladder cable trays upto 900mm with all necessary fixing accessories. |
| 137 | Providing & fixing 32mm x 32mm x 5mm GI angle suspenders & 40mm x 40mm x 5mm base supports for ladder cable trays of size 750mm & 600mm with all necessary fixing accessories. |
| 138 | Providing & fixing 25mm x 25mm x 5mm GI angle suspenders & 40mm x 40mm x 5mm base supports for ladder cable trays of size 450mm & below with all necessary fixing accessories. |
| 139 | Supplying and installing following size of perforated pre-painted M.S cable trays with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts&nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6mm thickness |
| 140 | 150 mm width X 50 mm depth X 1.6mm thickness |
| 141 | 300 mm width X 50 mm depth X 1.6mm thickness |
| 142 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 143 | 600 mm width X 50 mm depth X 2.0mm thickness |
| 144 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 145 | Supplying and installing following size of perforated pre-painted M.S cable trays bends with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts&nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6mm thickness |
| 146 | 150 mm width X 50 mm depth X 1.6mm thickness |
| 147 | 300 mm width X 50 mm depth X 1.6mm thickness |
| 148 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 149 | 600 mm width X 50 mm depth X 2.0mm thickness |
| 150 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 151 | Supplying and installing following size of perforated pre-painted M.S cable trays reducers with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts&nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6mm thickness |
| 152 | 150 mm width X 50 mm depth X 1.6mm thickness |
| 153 | 300 mm width X 50 mm depth X 1.6mm thickness |
| 154 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 155 | 600 mm width X 50 mm depth X 2.0mm thickness |
| 156 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 157 | Supplying and installing following size of perforated pre-painted M.S cable trays Tee's with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts&nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6mm thickness |
| 158 | 150 mm width X 50 mm depth X 1.6mm thickness |
| 159 | 300 mm width X 50 mm depth X 1.6mm thickness |
| 160 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 161 | 600 mm width X 50 mm depth X 2.0mm thickness |
| 162 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 163 | Supplying and installing following size of perforated pre-painted M.S cable trays Cross members with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts&nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6mm thickness |
| 164 | 150 mm width X 50 mm depth X 1.6mm thickness |
| 165 | 300 mm width X 50 mm depth X 1.6mm thickness |
| 166 | 450 mm width X 50 mm depth X 2.0 mm thickness |
| 167 | 600 mm width X 50 mm depth X 2.0mm thickness |
| 168 | 750 mm width X 62.5 mm depth X 2.0 mm thickness |
| 169 | Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required |
| 170 | (Supply, installation, testing & commissioning of One Set of 15 KVA UPS. Each UPS of 15 KVA should have following specifications in addition to tender requirements : (i) True online double conversions, IGBT Rectifier & inverter based UPS. (ii) Three phases Input/ three phase output (Input Line Voltage: 340 - 478 Volt, 3 phase, Output Line Voltage 400 volt, 3 phase) (iii) SMF batteries complete with MS Fabricated battery rack to accomodate the complete battery system. (iv) Suitable for 30 Min backup on Full load at 0.8 Load P.F., with required nos. of Battery with each UPS. (v) Output THD is less than 3% for full linear load & Less than 5 % for nonlinear load. (vi) Crest factor 3:1 (vii) over load 125% for 10 min, 150% for 1 min and should be able to operate continuously at 115% load on bypass mode. (viii) Battery type should be Valve regulated lead-acid (VRLA). (ix) Inbuilt / External Isolation Transformer, parallel communication port, RS232, USB, EPO and SNMP interface, BMS interface. (x) Dust Filter at Air Inlet point are required. (xi) UPS should be provided with environment monitoring probe to measure temperature and humidity of UPS room on SNMP card software. xii) LCD Display indicating all important parameters. (xiii) UPS shall be provided with Temperature and Humidity Sensors to monitor Temperature and Humidity over LAN. (xiv) Battery open rack with top cover, battery interlinks and battery breaker. (xv) Battery to UPS cable as required should be provided with UPS systems. (xvi) UPS system shall be parallelable upto 6 units in case required in future. (xvii) Each UPS shall be compatible for working in parallel redundant mode with other. |
| 171 | Supplying, installation on wall, testing and commissionioning of following capacity Air insulated compact rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convient sections complete with 4 Nos.aluminium bus bars having current density 130A/sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc.as required. 500A, Isc=35KA for 1 Sec |
| 172 | Supplying, installation on wall, testing and commissionioning of following capacity Air insulated compact rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convient sections complete with 4 Nos.aluminium bus bars having current density 130A/sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc.as required. 315A, Isc=25KA for 1 Sec |
| 173 | Supplying, installation on wall, testing and commissionioning of following capacity End feed unit for the existing Air Insulated Compact type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel enclosure (IP-54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. 500A, Isc=35KA for 1 Sec |
| 174 | Providing and fixing following rating and breaking capacity and pole MCCB/ACB with thermonagnetic/microprocessor release and terminal spreaders in existing cubival panel board including drilling holes in cubical panel, making connections, etc. as required. 125A, Isc=36KA,FP,MCCB |
| 175 | Providing and fixing following rating and breaking capacity and pole MCCB/ACB with thermonagnetic/microprocessor release and terminal spreaders in existing cubival panel board including drilling holes in cubical panel, making connections, etc. as required. 200A, Isc=36KA,FP,MCCB |
| 176 | Supplying, installation, testing & commisioning of following capacity Plug In/ tap off box on the existing air insulated compact type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply made with provision of MCCB/ACB (but without MCCB/ACB) complete etc.as required 125A, Isc=15KA for 1 Sec |
| 177 | Supplying, installation, testing & commisioning of following capacity Plug In/ tap off box on the existing air insulated compact type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply made with provision of MCCB/ACB (but without MCCB/ACB) complete etc.as required 200A, Isc=25KA for 1 Sec Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail